TAE Antriebstechnik

Instruction & Operating Manual

7

Copyright © by T

AE Antriebstechnik

5.   Indicators

The following functions are indicated with LED´s:

LED 1 

green  Line Supply

LED 2 

clear  Thyristor triggering

LED 3 

yellow  Drive release

LED 4 

red 

Current limit, Over-speed

Caution ! 

Do not use any megohmmeter, buzzer or similar test instrument !
Measuring instruments must be galvanically seperated from line 
voltage.

6.   Functional tests and adjustments before operation

6.1  Armature-voltage control (UA-control)

1) 

Check all connections with an ohmmeter for short circuits to ground.

2) 

Check line supply voltage with reference to the Type Marking.

3) 

Set jumpers I, II, III (refer to layout chapter 9).

4) 

Measure the resistance between terminal 18dz and 16dz with an ohmmeter. The 
resistance has to be least 400 ohms (220 V connection). If necessary change the 
polarity of the ohmmeter.

5) 

Potentiometer  P2 

Deceleration-time, set in centre position.

Potentiometer  P3 

Acceleration-time, set in centre position.

Potentiometer  P5 

IxR compensation, set fully counter clockwise.

Potentiometer  P6 

Stability, set fully clockwise and turn back 30%.

Potentiometer  P1 

Minimum speed, set fully counter clockwise.

6) 

Switch on line voltage. The green LED 1 must now light up.

7) 

Measure field voltage between terminals 18dz (F+) and 16dz (F-) with a multime-
ter (moving coil instrument, min 333 Ohm/V). The field voltage must read 200 V at 
230 V line voltage. Measure potentiometer voltage between terminals 30z - 26z. 
If the potentiometer is turned clockwise the armature voltage (motor speed) will 
increase. Set speed potentiometer P4 (max. speed) fully clockwise and adjust the 
armature voltage (motor speed) for the requested maximum speed. Set speed 
potentiometer fully counter clockwise (output voltage must now return to 0 V) and 
adjust with P1 (min. speed) the requested minimum speed.

Summary of Contents for TA-05/C

Page 1: ...92 F TA 05 C Sh start at modification No 1601 CAUTION As with any form of electrical equipment there is always a risk involved in the handling of electrical machinery The greatest care must always be exercised during installation and maintenance and it is recommended that service is performed by authorized per sonnel only TA 05C PMD PT Änd Nr 00003 Stand 12 03 2012 The German text applies in cases...

Page 2: ...g a continuouse operation for 200 hours Before delivery all units are again tested for their correct functioning These extensive tests will assure that all supplied units are in perfect functional con dition If these units are installed adjusted and operated according to the instructions of this manual malfunctions are not to be expected Should despite of our preliminary tests any problems arise p...

Page 3: ...tants This symbol stands for notes and useful informations which shall make the operation easier for you Note disregard can damage or destruct the device Note disregard means a danger for the operator Table of content 1 Instructions of safety 2 1 1 Instructions and Rules 1 2 Safety 2 Technical data 3 2 1 Equipment 3 Connection of unit 3 4 Adjustments 4 5 Indicators 5 6 Functional tests and adjustm...

Page 4: ...he following stan dards DIN VDE 0100 Erection of power installations with nominal voltage up to 1000 V VDE 0113 Electrical equipment for machines VDE 0160 Electronic equipment to be used in electrical power installations VDE 0470 Part 1 Protection by frame 1 2 Safety Caution Danger Disconnect device from mains before making any repairs After the installa tion make sure that the device is properly ...

Page 5: ...uit is at line potential 3 Connection of unit refer to Connection diagram TA 05 C chapter 8 2dz 6dz Line supply refer to Type Marking 230V AC 50 60Hz 2dz Phase L1 6dz MP N neutral 10dz 14dz Armature connection 10dz A 14dz A 18dz 16dz Field connection 18dz F 16dz F 28d 26d Drive release by relay contact Jumper III internal refer to layout chapter 9 26d 12d Drive release by SPS free potential Jumper...

Page 6: ... of TAE blocking protection B 200 Nr 20003 F or B202 Nr 20163 F 4 Adjustments Minimum speed P1 Adjustment of minimum speed during operation set speed potentiometer fully counter clockwise Deceleration P2 Adjustment of the time for the linear deceleration of the rate motor from maximum to minimum speed adjustable from 2 sec to 20 sec Turning this control clockwise will decrease the deceleration tim...

Page 7: ...to be least 400 ohms 220 V connection If necessary change the polarity of the ohmmeter 5 Potentiometer P2 Deceleration time set in centre position Potentiometer P3 Acceleration time set in centre position Potentiometer P5 IxR compensation set fully counter clockwise Potentiometer P6 Stability set fully clockwise and turn back 30 Potentiometer P1 Minimum speed set fully counter clockwise 6 Switch o...

Page 8: ...0 sec otherwise dama ge to the commutator is possible 12 Acceleration time Adjust the requested acceleration time with potentiometer P3 13 Deceleration time Set speed potentiometer to 0 and adjust the requested decele ration time with potentiometer P2 Note the deceleration time cannot be less than the coasting time of the machine since the drive control operates in the first Qua drant only The dec...

Page 9: ...24V missing check supply LED 1 does not light up a Motor load is too high Drive ope rates at current limit LED 4 current limit lights up b Defective speed potentiometer c Adjustment of current limit is set too low Yellow LED 3 does not light up Output voltage does not increase when speedcontrol is turned up a I x R compensation is set too high when armature feedback control is used b Improper adju...

Page 10: ...ttent potentiometer P1 Mini mum speed b Defective speed potentiometer or connection from terminal 26z to po tentiometer a Defective power supply b Check relays and relay connections drive release c Defective speed potentiometer d Check motor and brushes e Defective fuse F1 10A FF Speed varies without change of speed potentiometer Main fuse blows Drive does not run Drive runs after control release ...

Page 11: ...TA 05 C ETA 05C PMD PT Misprints and technical changes reserved TAE Antriebstechnik Instruction Operating Manual 11 Copyright by TAE Antriebstechnik 8 Connection diagram Feld FIELD EXCITATION ...

Page 12: ...eserved TAE Antriebstechnik 12 Copyright by TAE Antriebstechnik 9 Layout Armature feedback TA 05 C ISO Art No 10091 F insulated BRI Tachometer feddback BRI BRII BRII external internal BRIII Armature feedback TA 05 C Sh Art No 10092 F with Shunt BRI Tachometer feddback BRI BRII BRII RUN ...

Page 13: ...ing circuit 33301 33503 00 Diode BY255 34221 00 SCR bridge 20 Amp L413F 34459 00 Fuse 20 x 5 super fast 10 0 A 35852 A0 Multiple plug 32pol 6 A 36360 00 Firing circuit transformer IT243 36495 C0 Current transformer CSLA1CD 58000 Q0 Transformer BV 5005 230V 10 Dimensions EMC Casing Plug in frame 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 2 p 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 EMC Casing Plu...

Reviews: