34
Special functions
Under no circumstances switch off the controller during update, this can lead to irrevocable damages.
Settings may be changed by an update. Reset the controller to factory settings after reset and commence the
commissioning process.
Current settings are over written.
Caution
Caution
6.22. - SD-Card
Settings for the data logging and
fi
rmware update function with SD card.
6.22.1. - Logging
Activate the logging function and set the
fi
le format used.
Settings range: On / Off
6.22.2. - Free storage
Displays the available space on the SD card.
6.22.3. - Load con
fi
guration
This is used to load settings from the SD card.
6.22.4. - Save con
fi
guration
All settings can be stored on the SD card.
6.22.5. - Firmware update
This is used to update the controllers
fi
rmware with one saved on the SD card.
6.22.6. - Unmount
To prevent damage to the SD card or loss of data, please unmount the card before removing it from the controller.
With some solar systems, especially with vacuum tube collectors, it may occur that the measurement value acquisition at the
collector sensor occurs too slowly or too inaccurately because the sensor is often not at the hottest location. When the start
help is activated the following sequence is carried out:
If the temperature at the collector sensor increases by the value speci
fi
ed under “Increase” within one minute, then the solar
pump is switched on for the set “Purging time” so that the medium to be measured can be moved to the collector sensor. If this
still does not result in a normal switch-on condition, then the start help function is subject to a 5-minute lockout time.
Start help setting range: on, off/default setting: off
Purging time setting range: 2 ... 30 sec./default setting: 5 sec.
Increase setting range: 1°C....10°C/default setting: 3°C/min.
6.23. - Start aid function
Caution
This function should only be activated by a specialist if problems arise with acquisition of measurement values.
In particular follow the instructions from the collector manufacturer.
Caution
This menu is used to set the current time and date.
When this function is active, the controller’s clock changes automatically to and from DST (DST, Daylight Savings Time).
6.24. - Time and date
6.25. - Daylight saving time
For analysis of the system data it is essential for the time to be set accurately on the controller. Please note
that the clock does not continue to run if the mains voltage is interrupted, and must therefore be reset.