Taco X Pump Block Instruction Sheet Download Page 6

6 of 16

70    60    50    40    30    20    10      0   -10    -20

Outdoor Temperature (F)

150

140

130

120

110

100

90

80

70

60

Supply T

emperature (F)

Mix Maximum

Outdoor

Design

Mix

Design

Outdoor Reset

WWSD

Starting

Point

Setpoint and Delta T Mode of Operation

In certain applications, it is desirable to maintain a fixed supply water temperature. This type of application is a setpoint application.
Examples of setpoint applications include heat pump loops, reheat coils and floor warming.
In specialized applications, such as snow melting, it is desirable to limit the rate of temperature increase in the system from the system‘s
starting temperature to its operating setpoint. This is desired in order to prevent thermal shock of the system. This type of application is
a Delta T application.
If the VSMC is to operate as a setpoint control, the Outdoor Design temperature must be set to OFF and the Mixing Target temperature
must be set to the desired temperature.
If the VSMC is to operate as a Delta T control, a mixing return sensor must be installed, the Outdoor Design temperature must be set to
OFF and both the Delta T Max setting and the Mixing Target temperature must be set to the desired temperature.
In both of these applications, the outdoor sensor is not to be installed.

SEQUENCE OF OPERATION

When the VSMC receives a Demand, the system pump is turned on.
If the Delta T Max setting is set to OFF, the variable speed injection pump is operated to maintain the mixing supply sensor at the
Mixing Target temperature set by the installer.
If the Delta T Max setting is not set to off, the variable speed heat source pump is operated to maintain the mixing supply sensor at
either the Mixing Return temperature plus the Delta T Max setting or the Mixing Target temperature set by the installer whichever is
lower. The heat source contact operates as described in the Heat Source Operation section. The VSMC also provides heat source
protection as described in the Heat Source Operation section.

DEMAND

The VSMC requires a demand signal before it will begin operation. The VSMC can use
either a powered or an unpowered demand signal. Once a demand signal is received, the
VSMC displays the demand pointer in the display and operates as described above.

Powered Demand

The VSMC recognizes a Powered Demand Signal when 24 V (ac) is applied across the
Com and Heat Dem terminals.

Outdoor Design

The Outdoor Design temperature is the average coldest day of the
year for the area in which the building is located.

Design Supply

The Design Supply temperature is the supply water temperature that
is required to heat the building when the outdoor air temperature is
as cold as the Outdoor Design temperature.

Maximum System Supply

Some systems, such as hydronic radiant floor heating, may require the
maximum supply water temperature to be limited in order to protect
certain system components from high temperatures. The VSMC has a
Maximum Supply setting that can be used to limit the maximum tem-
perature that the control is allowed to use for a Mixing Target (MIX TRG)
temperature.

Minimum System Supply

Some applications, such as floor warming, may require the minimum
supply water temperature to be limited in order to provide a certain
level of occupant comfort. The VSMC has a Minimum Supply setting
that can be used to limit the minimum temperature that the control is
allowed to use for a Mixing Target (MIX TRG) temperature. This mini-
mum applies as long as the VSMC has a demand and is not in WWSD.

Warm Weather Shut Down (WWSD)

When the outdoor temperature is warmer than the WWSD setting, the VSMC turns off the heat source and the system pump. If a
demand is received while the VSMC is in a WWSD, the VSMC indicates that the demand has been received by displaying the
Demand pointer however, the MIX TRG remains as “- - -”. The VSMC has a freeze protection feature that does not allow the supply
water temperature to drop below 35

°

F (2

°

C) as long as there is a mixing demand signal.

Com Heat

Dem

Boil Out

Powered

Demand

C

24 V (ac)

R

Switch

Summary of Contents for X Pump Block

Page 1: ...diant tubing glycol based snowmelt baseboard etc Extremely versatile the X Pump Block can be set up to operate in outdoor reset setpoint or delta T limiting mode Instruction Sheet X Pump Block XPB 102...

Page 2: ...r Pressure Relief X Pump Block XPB Multiple Temperature System Circulators Exp Tank Output to System Supply Sensor Return Sensor Outdoor Sensor Pressure Relief X Pump Block XPB Multiple Temperature Sy...

Page 3: ...pm 0 2 4 6 8 10 12 HEAD ft 0 2 4 6 8 10 12 14 16 18 20 SYSTEM SIDE HEAT SOURCE SIDE 1 2 1 2 Contents should include the following One X Pump Block preassembled unit consists of the following parts One...

Page 4: ...OUNTING 1 Mounting position The X Pump Block must be mounted in the vertical position with the Variable Speed Mixing Control VSMC located at the top of the X Pump Block 2 Mount the X Pump Block using...

Page 5: ...urce Operation section The VSMC also provides heat source protection as described in the Heat Source Operation section DEMAND The VSMC requires a demand signal before it will begin operation The VSMC...

Page 6: ...at source protection as described in the Heat Source Operation section DEMAND The VSMC requires a demand signal before it will begin operation The VSMC can use either a powered or an unpowered demand...

Page 7: ...T SOURCE CONTROL When the VSMC controls the heat source the VSMC opens and closes the heat source contact in order to control the temperature of the heat source supply water temperature When the VSMC...

Page 8: ...stances is required When a heat source sensor is connected to the control the VSMC is capable of providing heat source protection When providing heat source protection the VSMC limits the output of th...

Page 9: ...required at all times If a Heat Source Sensor is used install the heat source sensor on either the heat source supply or the heat source return Ensure that the DIP switch on the back of the circuit b...

Page 10: ...a powered demand is being used connect the switched side of the 24 V ac demand circuit to the Heat Dem terminal of the terminal block Connect the second side of the 24 V ac demand circuit to the Com...

Page 11: ...n the MIX RET elements are turned on This is the current temperature at the mixing return sensor The mixing return temperature is only displayed if the Outdoor Design temperature is turned OFF and a m...

Page 12: ...his item is only available if the outdoor design set ting is not set to OFF Mixing Minimum Temperature The mixing minimum temperature is the lowest temperature that the control is allowed to use as a...

Page 13: ...he rooms are cold increase the MIX DSGN setting by 5 F 3 C per day TESTING THE SENSORS Do not apply voltage to the sensor or to the sensor input of the control as this will result in damage to either...

Page 14: ...plastic housing to pump castings 5 Remove the body bolts and swing motor assembly away from the body 6 Pull cartridge out of the motor housing 7 Install replacement cartridge making sure that the cov...

Page 15: ...e Difference Between Mixing Supply and Return 10 to 70 F Off Design Outdoor Air Temperature 60 to 32 F Off Design Heating System Supply Water Temperature 70 to 185 F Maximum Mixing Target Supply 80 to...

Page 16: ...service under this warranty it is the responsibility of the purchaser to promptly notify the local Taco stocking distributor or Taco in writing and promptly deliver the subject product or part deliver...

Reviews: