Delta T Maximum

The Delta T Maximum sets the maximum temperature difference between the mixing
return sensor and the mixing supply sensor. This item is only available if Outdoor Design
setting is set to OFF. If a mixing return sensor is not installed, set this item to OFF.

Outdoor Design Temperature

The Outdoor Design Temperature is the outdoor temperature used in the heat loss calcu-
lation. If the VSMC is used in the outdoor reset mode, this item is set to the typical coldest
outdoor temperature. If the VSMC is used in the setpoint mode, this item is set to OFF.

Mixing Design Temperature

The mixing design temperature is the supply temperature used in the heat loss calcula-
tion. This is the supply temperature that is required to heat the building when the outdoor
temperature is as cold as the outdoor design temperature. This item is only available if the
Outdoor Design setting is not set to OFF.

Mixing Maximum Temperature

The mixing maximum temperature is the highest temperature that the control is allowed to
use as a mixing target temperature. This item is only available if the outdoor design set-
ting is not set to OFF.

Mixing Minimum Temperature

The mixing minimum temperature is the lowest temperature that the control is allowed to
use as a mixing target temperature. This item is only available if the outdoor design set-
ting is not set to OFF.

Heat Source Minimum Temperature

The heat source minimum temperature item should be set to the lowest water tempera-
ture at which the heat source can operate without causing the heat source flue gases to
condense. Consult the heat source manufacturer for recommended minimum heat source
supply temperatures. This item is only available if a heat source sensor is connected to
the control.

Warm Weather Shut Down (WWSD)

The warm weather shut down is the outdoor temperature at which the system is shut
down. This item is only available if the outdoor design temperature is not set to OFF.

Units

The units of temperature in which all of the View and Adjust items are viewed in.

The control automatically goes back to the view menu when the buttons are left alone for 20 seconds

All settings will be saved even during power down of the control

T

MAX

ADJUST

F

OUT

ADJUST

F

DSGN

MIX

ADJUST

F

DSGN

MIX

MAX

ADJUST

F

MIX

MIN

ADJUST

MIN

ADJUST

F

BOIL

ADJUST

F

WWSD

ADJUST

F

Summary of Contents for X Pump Block

Page 1: ...diant tubing glycol based snowmelt baseboard etc Extremely versatile the X Pump Block can be set up to operate in outdoor reset setpoint or delta T limiting mode Instruction Sheet X Pump Block XPB 102...

Page 2: ...r Pressure Relief X Pump Block XPB Multiple Temperature System Circulators Exp Tank Output to System Supply Sensor Return Sensor Outdoor Sensor Pressure Relief X Pump Block XPB Multiple Temperature Sy...

Page 3: ...pm 0 2 4 6 8 10 12 HEAD ft 0 2 4 6 8 10 12 14 16 18 20 SYSTEM SIDE HEAT SOURCE SIDE 1 2 1 2 Contents should include the following One X Pump Block preassembled unit consists of the following parts One...

Page 4: ...OUNTING 1 Mounting position The X Pump Block must be mounted in the vertical position with the Variable Speed Mixing Control VSMC located at the top of the X Pump Block 2 Mount the X Pump Block using...

Page 5: ...urce Operation section The VSMC also provides heat source protection as described in the Heat Source Operation section DEMAND The VSMC requires a demand signal before it will begin operation The VSMC...

Page 6: ...at source protection as described in the Heat Source Operation section DEMAND The VSMC requires a demand signal before it will begin operation The VSMC can use either a powered or an unpowered demand...

Page 7: ...T SOURCE CONTROL When the VSMC controls the heat source the VSMC opens and closes the heat source contact in order to control the temperature of the heat source supply water temperature When the VSMC...

Page 8: ...stances is required When a heat source sensor is connected to the control the VSMC is capable of providing heat source protection When providing heat source protection the VSMC limits the output of th...

Page 9: ...required at all times If a Heat Source Sensor is used install the heat source sensor on either the heat source supply or the heat source return Ensure that the DIP switch on the back of the circuit b...

Page 10: ...a powered demand is being used connect the switched side of the 24 V ac demand circuit to the Heat Dem terminal of the terminal block Connect the second side of the 24 V ac demand circuit to the Com...

Page 11: ...n the MIX RET elements are turned on This is the current temperature at the mixing return sensor The mixing return temperature is only displayed if the Outdoor Design temperature is turned OFF and a m...

Page 12: ...his item is only available if the outdoor design set ting is not set to OFF Mixing Minimum Temperature The mixing minimum temperature is the lowest temperature that the control is allowed to use as a...

Page 13: ...he rooms are cold increase the MIX DSGN setting by 5 F 3 C per day TESTING THE SENSORS Do not apply voltage to the sensor or to the sensor input of the control as this will result in damage to either...

Page 14: ...plastic housing to pump castings 5 Remove the body bolts and swing motor assembly away from the body 6 Pull cartridge out of the motor housing 7 Install replacement cartridge making sure that the cov...

Page 15: ...e Difference Between Mixing Supply and Return 10 to 70 F Off Design Outdoor Air Temperature 60 to 32 F Off Design Heating System Supply Water Temperature 70 to 185 F Maximum Mixing Target Supply 80 to...

Page 16: ...service under this warranty it is the responsibility of the purchaser to promptly notify the local Taco stocking distributor or Taco in writing and promptly deliver the subject product or part deliver...

Reviews: