Taco X Pump Block Instruction Sheet Download Page 13

13 of 16

As in any troubleshooting procedure, it is important to isolate the problem as much as possible. By using the Error Messages located on
page 14, the trouble shooting process can be greatly simplified. When an error message is displayed on the VSMC, refer to the error
messages on page 14 to identify the cause of the error and use standard testing procedures to confirm the fault. If you suspect an
external wiring fault, return to step three and carefully check all external wiring connections.
Once the fault has been corrected, press any button on the face of the control to clear the error message.

TEST ROUTINE

The main control functions of the VSMC can be tested by pressing and holding the UP button for more than three (3) seconds.

Continue

 to hold the UP button and the VSMC will test the outputs in the following sequence.

Step One

The variable speed output is increased from 0% to 100% over 10 seconds.

Step Two

The variable speed output is decreased from 100% to 0% over 10 seconds.

Step Three

The System Pump is turned on for 10 seconds.

Step Four

The Boiler Contact is turned on. After 10 seconds, the Boiler Contact and the
System Pump contact are turned off. The VSMC continues normal operation.

MANUAL OVERRIDE

In the event that the VSMC fails to operate, a manual operation switch is located
on the VSMC’s circuit board. When the manual operation switch is set to Man, the
variable speed pump and the system pump outputs are turned on. This operation
continues until the manual switch is returned to its original position.

FUSE REPLACEMENT

The Variable Speed output of the VSMC is fuse protected. This fuse is located on
the circuit board on the back of the VSMC. This is a field replaceable item.
Fuse rating: 1 A 

1

12

 hp, fuse T1 A 250 V

ADJUSTMENT OF SETTINGS

If the outdoor temperature is cold and the rooms are cold, increase the MIX DSGN
setting by 5

°

F (3

°

C) per day.

TESTING THE SENSORS

Do not apply voltage to the sensor or to the sensor input of the control as this will result in damage
to either the sensor, the control, or both the sensor and the control.

A quality testing meter capable of measuring up to 2,000,000 ohms and a good quality digital
thermometer are required to test the sensors. If a digital thermometer is not available, place a
second sensor next to the original sensor and compare the readings.

Begin by measuring the temperature at the sensor location using the digital thermometer. Next,
measure the resistance of the sensor using the testing meter. Ensure that the sensor is discon-
nected from the control at the time of testing. Using the reference chart below, determine the
sensor’s temperature. Compare the sensor’s temperature to that measured by the digital ther-
mometer. The two temperature readings should be close.
If the sensors temperature is too high, this can indicate that there is a partial short in the sensor
wiring. If the sensor’s temperature is too low, this can indicate that there is a loose connection or
break in the sensor wiring. Isolate and repair the problem. If the problem is isolated to the sensor,
replace the sensor.

Trouble Shooting

OHM

-30
-20
-10

0

10
20

30
40
50
60
70
80

90

100

110

120
130
140

150
160
170
180
190
200

-34
-29
-23
-18
-12

-7

-1

4

10
16
21
27

32
38
43
49
54
60

66
71
77
82
88
93

234,000
165,000

118,000

85,500
62,500
46,000

34,500
26,000
20,000
15,500
12,000

9,300

7,300
5,800
4,700
3,800
3,100
2,500

2,000
1,700
1,400
1,200
1,000

800

Temperature

Resistance

F

C

Ohms

Temperature

Resistance

F

C

Ohms

Temperature

Resistance

F

C

Ohms

Temperature

Resistance

F

C

Ohms

Com Sup Sys

Ret

Com Boil Out Com Heat

Dem

Var

T1A 250V

Sys

Man

N

H

Pmp

Use copper

conductors only

Power: 120 V +/- 10%

50/60 Hz, 750 VA

Var. Speed: 120 V

(ac) 1A

Pmp Relay: 120 V

(ac) 5 A, 1/6 hp

Injection Mixing 

967-01

Meets Class B Canadian ICES FCC Part 15

ON

OFF

1

2

3

4

5

C

US

158033

BOILER

R

Summary of Contents for X Pump Block

Page 1: ...diant tubing glycol based snowmelt baseboard etc Extremely versatile the X Pump Block can be set up to operate in outdoor reset setpoint or delta T limiting mode Instruction Sheet X Pump Block XPB 102...

Page 2: ...r Pressure Relief X Pump Block XPB Multiple Temperature System Circulators Exp Tank Output to System Supply Sensor Return Sensor Outdoor Sensor Pressure Relief X Pump Block XPB Multiple Temperature Sy...

Page 3: ...pm 0 2 4 6 8 10 12 HEAD ft 0 2 4 6 8 10 12 14 16 18 20 SYSTEM SIDE HEAT SOURCE SIDE 1 2 1 2 Contents should include the following One X Pump Block preassembled unit consists of the following parts One...

Page 4: ...OUNTING 1 Mounting position The X Pump Block must be mounted in the vertical position with the Variable Speed Mixing Control VSMC located at the top of the X Pump Block 2 Mount the X Pump Block using...

Page 5: ...urce Operation section The VSMC also provides heat source protection as described in the Heat Source Operation section DEMAND The VSMC requires a demand signal before it will begin operation The VSMC...

Page 6: ...at source protection as described in the Heat Source Operation section DEMAND The VSMC requires a demand signal before it will begin operation The VSMC can use either a powered or an unpowered demand...

Page 7: ...T SOURCE CONTROL When the VSMC controls the heat source the VSMC opens and closes the heat source contact in order to control the temperature of the heat source supply water temperature When the VSMC...

Page 8: ...stances is required When a heat source sensor is connected to the control the VSMC is capable of providing heat source protection When providing heat source protection the VSMC limits the output of th...

Page 9: ...required at all times If a Heat Source Sensor is used install the heat source sensor on either the heat source supply or the heat source return Ensure that the DIP switch on the back of the circuit b...

Page 10: ...a powered demand is being used connect the switched side of the 24 V ac demand circuit to the Heat Dem terminal of the terminal block Connect the second side of the 24 V ac demand circuit to the Com...

Page 11: ...n the MIX RET elements are turned on This is the current temperature at the mixing return sensor The mixing return temperature is only displayed if the Outdoor Design temperature is turned OFF and a m...

Page 12: ...his item is only available if the outdoor design set ting is not set to OFF Mixing Minimum Temperature The mixing minimum temperature is the lowest temperature that the control is allowed to use as a...

Page 13: ...he rooms are cold increase the MIX DSGN setting by 5 F 3 C per day TESTING THE SENSORS Do not apply voltage to the sensor or to the sensor input of the control as this will result in damage to either...

Page 14: ...plastic housing to pump castings 5 Remove the body bolts and swing motor assembly away from the body 6 Pull cartridge out of the motor housing 7 Install replacement cartridge making sure that the cov...

Page 15: ...e Difference Between Mixing Supply and Return 10 to 70 F Off Design Outdoor Air Temperature 60 to 32 F Off Design Heating System Supply Water Temperature 70 to 185 F Maximum Mixing Target Supply 80 to...

Page 16: ...service under this warranty it is the responsibility of the purchaser to promptly notify the local Taco stocking distributor or Taco in writing and promptly deliver the subject product or part deliver...

Reviews: