5

4.'  Constant  DutG  Curve
)Unregulated 

Pump0

Control:

An  unregulated  pump

decreases  its  head  with

increasing flow.  This unreg-

ulated  setting  can  be

achieved by setting the 

limit

head  (Hmax)

to  “no  limit

(99)” in the 

pump

tab (see

below) with a jumper across

IO2/24V  (or  8Vdc  and

above).  Note:  I1  must  be

closed and set to "no function". 

Limit rpm to

should be set to the

maximum value to achieve full pump curve. This allows the pump to

run  just  like  a  conventional

non-variable speed pump.

4.B RPM° Regulation:

Provides  regulation  similar

to  a  manually  adjustable

pump.

4.4 PoWer Limitation:

Artificially limits power con-

sumption  and  output  by

selecting  a  maximum  amp

draw.

,. CONNECTION TO A NETHOR& Y PUMP SETUP:

In order to change the factory default operating parameters of the

pump or to use various web tools the pump needs to be connected

to a network or a personal computer over the Ethernet plug. Use

CAT-4 or better network cable connected to “PATCH” configuration

if  plugged  into  a  network  or  connect  an  Ethernet  cable  directly

between a PC and the Viridian.

To  achieve  pump  IP  protection,  network  cable  should  be  fed

through  the  glanded  inlet  and  then  crimped  to  a  connector.

Ethernet plug is galvanically insulated, but the rest of the cabling

could still present shock hazard.

If more than one pump will be connected into network, each indi-

vidual  pump  should  have  its  IP  address  and  NetBIOS  name

changed and noted. That will prevent network confusion and pro-

vide naming service in relation to pump function.

,.1 HeV Interface Settings:

When the Viridian is connected to a network or another computer,

it can be reached by typing its IP address or NetBIOS name into

the  internet  explorer’s  address  line.  The  default  IP  address  is

192.168.0.245 and default NetBIOS name is “viridian”. The pump

can be switched between standby mode or maximum power via

the digital inputs.

,.- Setting Up the Default IP Address:

Once the Ethernet cable is connected between the Viridian pump

and  either  the  laptop  or  network,  go  to  your  Control  Panel  and

select Network Connections. Right click on Local Area Connection

and  choose  properties.  Highlight  Internet  Protocol  Version  4

(TCP/IPv4) then click on properties. In the TCP/IP address use the

following IP address “192.168.0.XXX” (example  192.168.0.123).

Click OK to finish.

CAUTION:  All  connections  should  Ve  made  With
the poWer to the pump turned off.
ATTENTION: Tous les raccordements doivent 8tre
effectués  avec  l(alimentation  électri2ue  vers  la
pompe coupée.

INTERNET

ROUTER

ROUTER

LAPTOP

PC

LAPTOP

CONNECTING VIRIDIAN with ETHERNET CABLE

CONNECTING VIRIDIAN on LAN

ETyERNET CAqLE CONNECTED TO  IRIDIAN

H

Q

CONSTANT

DUTY

CONTROL

Max RPM or

Unregulated Curve

Reduced RPM

Curves

H

Q

POWER

LIMITATION

CONTROL

Max Power

Curve

Reduced Power

(watt) Curves

Summary of Contents for Viridian 15

Page 1: ...t O rings use part number 975 001RP See detailed Motor Rotation Procedure 4 1 below Instruction Sheet Viridian 15 30 1 and 2 Models 302 364 SUPERSEDES October 24 2013 EFFECTIVE November 2 2015 A Taco resource saving product CAUTION Use supplG Wires suitaVle for x6XC ATTENTION EmploGer des fils d alimentation ade2auts pour x6XC HARNINb Do not use in sWimming pool or spa areas Pump has not Veen inve...

Page 2: ...ck up the motor with the terminals properly orientated and carefully start to slide the motor over the rotor can The resis tance of the sliding will keep the rotor and rotor can assembly in place and the screwdriver can be moved Note Do not alloW the motor to droop or the OYring might get out of position 10 Line up the bolt holes reinstall the bolts and tighten in a cross pattern 11 Carefully open...

Page 3: ...neficial when the Viridian is installed in a system where there is a much lower resis tance friction loss in the main distribution loop compared to the resistance in the transfer part of the system i e baseboard radia tion radiant floors terminal units For example this characteristic of generally lower head loss can be found in converted gravity sys tems systems operating with large temperature sp...

Page 4: ... CLOSED CLOSED CLOSED OFF RUN OPEN MAX NF 0 OPEN OPEN MAX RUN CLOSED OPEN CLOSED MAX RUN CLOSED CLOSED OPEN RUN RUN CLOSED CLOSED CLOSED RUN RUN CLOSED NF 0 MAX OPEN OPEN RUN RUN CLOSED OPEN CLOSED MAX RUN CLOSED CLOSED OPEN RUN RUN CLOSED CLOSED CLOSED MAX RUN CLOSED RUN Default MAX Default OPEN OPEN RUN RUN CLOSED OPEN CLOSED MAX RUN CLOSED CLOSED OPEN OFF RUN OPEN CLOSED CLOSED OFF RUN OPEN MAX...

Page 5: ... one pump will be connected into network each indi vidual pump should have its IP address and NetBIOS name changed and noted That will prevent network confusion and pro vide naming service in relation to pump function 1 HeV Interface Settings When the Viridian is connected to a network or another computer it can be reached by typing its IP address or NetBIOS name into the internet explorer s addre...

Page 6: ...tion Active run Error detected error Active I2 i2 Input I1 is either Run Run the pump run Full power max No function 0 Overview Pump Network Log Help VR 30 Limit head adjusts the maximum pump head The pump will try to maintain that head between its ports Hmax proportional to Q will reduce the head at the low flow It will drop for a set percentage at zero flow Limit rpm can provide a head regulatio...

Page 7: ...e the system is filled with fluid to prevent bearing damage 2 Overload trip protective shutdown Overcurrent line surge or locked rotor caused the pump to restart If the issue persists check if the rotor is spinning freely 3 Motor too hot Motor has exceeded allowed temperature and is now stopped to cool down Extremely hot medium or hardware failure might have caused that 4 Frequency converter error...

Page 8: ...le device NOR Will it ma3e the iridian accessiVle over the internet 16 1 Hireless Setting This is where it is possible to personalize the name of the wireless network The example below illustrates a network called Viridian Wireless Regardless of the wireless network name once set up the wireless device iPhone iPad PC Mac or Android device is directed to connect to that network Viridian Wireless as...

Page 9: ...uniquement a l interieur 11 Electrical Data Pump Ratings 1 phase 110 240V 47 63Hz VR15 VR20 1 phase 200 240V 47 63Hz VR25 VR30 Power Consumption HP VR15 0 027 0 680 HP VR20 0 035 1 088 HP VR25 0 054 1 496 HP VR30 0 054 2 175 HP Power Consumption W VR15 20 500 W VR20 26 800 W VR25 46 1100 W VR30 40 1600 W Rated Current 1 phase 115 230V VR15 2 2 A 6 0 A VR20 3 5 A 6 0 A Rated Current 1 phase 230V VR...

Page 10: ...0 75 100 125 150 175 200 225 250 275 300 325 350 375 400 HEAD FT 0 5 10 15 20 25 30 35 40 45 50 Flow liter min 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 Head m 0 2 4 6 8 10 12 14 Performance 3 4 1 VR15 3 VR25 4 VR30 2 VR20 1 2 ...

Page 11: ...11 NOTES ...

Page 12: ...a Taco product or part or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defec tive product or part Taco reserves the right to make changes in details of design construction or arrangement of ...

Reviews: