Taco Viridian 15 Instruction Sheet Download Page 3

3

The pump has built-in over current fuse protection, temperature

protection  and  basic  overvoltage  protection.  It  does  not  require

additional  overload  protection  devices  unless  required  by  local

electrical codes. Power supply cabling should be capable of carry-

ing rated power and be properly fused. Ground lead connection is

essential for safety and should be connected first. Grounding is

only meant for pump safety. System piping should be grounded

separately. A ferrite core is supplied in a separate bag. Electronic

cabling and wires, by virtue of their length-to-width ratios, are per-

fect natural antennas. The ground, line and neutral power supply

wires should go through the ferrite core to help reduce unwanted

high-frequency interfering signals. The pump should not be oper-

ated without the electrical cover securely attached.

B.' RelaG Connections:

The  pump  is  supplied  with  normally  open,  normally  closed  and

common relay connections. See Section 9.2 

Electrical Data

for

specifications. These can be used to activate or deactivate a pri-

mary or secondary pump or alarm contact, actuate a damper for

combustion  air  or  switch  another  piece  of  equipment.  Factory

default is activation of relay on fault. Additional relay “triggers” are

standby, I2 activation and run digital input commands.

B.B Digital Inputs:

The pump can be switched between standby mode or maximum

power via the digital inputs.

B.B.1 Pump Ezternal Control Hiring Diagrams:

The following diagrams are examples of external control wiring to

digital inputs I1 and I2.

B.B.- Ezternal Control Settings:

On/Off/Standby/Max speed external control variances and subse-

quent  effects  are  listed  in  the  chart  below.  Refer  to  Section  6.5

Pump Settings

to modify digital input and relay settings from fac-

tory defaults.

B.4 Constant -B  olt DC PoWer SupplG:

There is a constant, unswitched 24Vdc/100mA output power supply

across terminals 24V/0V. This power is interrupted only if the main

power supply to the Viridian is turned off.

4. REbULATION MODES:

Pump defaults to provide 23 feet (7m) of head with variable differ-

ential  pressure  (

p-v)  regulation.  If  the  factory  settings  are  not

suitable they can be modified over an Ethernet connector or a web

interface.  Various  regulation  parameters  (constant  head,  supply

power, rpm limit) can adjust the head and flow characteristics until

the pump achieves desired response to suit the application.

4.1 Constant Pressure Control )

pYc0:

Electronic  regulation  can  provide

constant head by modifying power

input  and  is  set  with  the 

Limit

head  (Hmax)

setting.  The  duty

point  of  the  pump  will  move  left

and  right  along  a  constant-pres-

sure curve based upon the water

demand in the system. The pump

head (pressure) is kept constant,

irrespective of the water demand.

Hmax proportional to Q

needs to

be  set  to  0%  (see  Section  6

Connection  to  a  Network  -
Pump Setup

)

.

Selecting the constant pressure regulation is beneficial when the

Viridian is installed in a system where there is a much lower resis-

tance (friction loss) in the main distribution loop compared to the

resistance in the transfer part of the system (i.e. baseboard radia-

tion, radiant floors, terminal units). For example, this characteristic

of generally lower head loss can be found in converted gravity sys-

tems, systems operating with large temperature spreads or where

the pump is moving the total volume of flow through the boiler and

distribution lines. 

4.-  ariaVle Differential
Pressure Control )

pYv0

      Y FactorG Default Setting:

Additional  energy  savings  and

noise  reduction  is  achieved  with

proportional  head  regulation  that

also compensates for changes in

system friction losses during peri-

ods of changing flow rates. In this

mode  the  pump  head  changes

continuously  as  the  demand  for

water  changes,  reducing  as  the

water  demand  declines  and

increasing as the water demand rises. 
The 

Hmax  proportional  to  Q

setting provides a user adjustable

curve slope. An 

Hmax  proportional  to  Q

of 0% means that the

head  does  not  exhibit  any  dependence  to  flow  and  should  not

exhibit  noticeable  change  until  maximum  power  is  reached. An

Hmax proportional to Q

set to 60% means that the pressure will

drop for 60% from set value when there is no flow. For example if

the  head  is  set  to  20',  the  pump  will  only  provide  12'  when  the

valves are closed and the pump is dead headed (operating at zero

flow). The factory default is 23' at 50%. Note, a substantial per-

centage of glycol in the mixture can influence regulation.

Select the variable differential pressure control when the Viridian is

installed in a system where there is a much higher resistance (fric-

tion loss) in the main distribution loop compared to the resistance

in the transfer part of the system (i.e. baseboard radiation, radiant

floors, terminal units). For example, this characteristic of the prima-

ry circuit having a high pressure drop can be seen in systems using

modulating condensing boilers or heat exchanges, heavily throttled

branch shut-off valves, where the distribution lines are long or in

two pipe systems with thermostatic or zone valves.

FACTORw DEFAULT FUNCTION

I1 (IO1/0V)

Normally  open  or  2Vdc  and  less,  pump  runs  normally.

Closing  contact  (or  applying  8Vdc  or  above)  sets  the

pump to standby mode by disabling power to the motor

(eg: for Warm Weather Shut Down). Additional I1 input

signals are maximum power (speed) and no effect.

I2 (IO2/24V)

Closing I2 or 8Vdc and above (only when I1 is closed)

forces the pump to run at Max (eg: purge system of air

on start-up). Has no effect if I1 is open. Additional I2 input

signals are run and no function.

0

IO2

24

IO1

DC Source

IO1 “Open”

IO2 “Open”

IO2 “Closed”

IO1 “Closed”

Pump Control Using Switches or Other

“Dry” Contacts Such as a Relay 

0

IO2

24

IO1

IO2

> 8 Vdc = “Closed”

< 8 Vdc = “Open”

DC Source

IO1

> 8 Vdc = “Open”

< 2 Vdc = “Closed”

Pump Control Using a DC Source Such as

From a BMS or Other Controlling

Voltage Source 

Note: Maximum voltage on the IO terminals

is not to exceed 32 Vdc

H

H

set

Q

CONSTANT

PRESSURE

CONTROL

H

H

set

H

set

2

Q

PROPORTIONAL

PRESSURE

CONTROL

Summary of Contents for Viridian 15

Page 1: ...t O rings use part number 975 001RP See detailed Motor Rotation Procedure 4 1 below Instruction Sheet Viridian 15 30 1 and 2 Models 302 364 SUPERSEDES October 24 2013 EFFECTIVE November 2 2015 A Taco resource saving product CAUTION Use supplG Wires suitaVle for x6XC ATTENTION EmploGer des fils d alimentation ade2auts pour x6XC HARNINb Do not use in sWimming pool or spa areas Pump has not Veen inve...

Page 2: ...ck up the motor with the terminals properly orientated and carefully start to slide the motor over the rotor can The resis tance of the sliding will keep the rotor and rotor can assembly in place and the screwdriver can be moved Note Do not alloW the motor to droop or the OYring might get out of position 10 Line up the bolt holes reinstall the bolts and tighten in a cross pattern 11 Carefully open...

Page 3: ...neficial when the Viridian is installed in a system where there is a much lower resis tance friction loss in the main distribution loop compared to the resistance in the transfer part of the system i e baseboard radia tion radiant floors terminal units For example this characteristic of generally lower head loss can be found in converted gravity sys tems systems operating with large temperature sp...

Page 4: ... CLOSED CLOSED CLOSED OFF RUN OPEN MAX NF 0 OPEN OPEN MAX RUN CLOSED OPEN CLOSED MAX RUN CLOSED CLOSED OPEN RUN RUN CLOSED CLOSED CLOSED RUN RUN CLOSED NF 0 MAX OPEN OPEN RUN RUN CLOSED OPEN CLOSED MAX RUN CLOSED CLOSED OPEN RUN RUN CLOSED CLOSED CLOSED MAX RUN CLOSED RUN Default MAX Default OPEN OPEN RUN RUN CLOSED OPEN CLOSED MAX RUN CLOSED CLOSED OPEN OFF RUN OPEN CLOSED CLOSED OFF RUN OPEN MAX...

Page 5: ... one pump will be connected into network each indi vidual pump should have its IP address and NetBIOS name changed and noted That will prevent network confusion and pro vide naming service in relation to pump function 1 HeV Interface Settings When the Viridian is connected to a network or another computer it can be reached by typing its IP address or NetBIOS name into the internet explorer s addre...

Page 6: ...tion Active run Error detected error Active I2 i2 Input I1 is either Run Run the pump run Full power max No function 0 Overview Pump Network Log Help VR 30 Limit head adjusts the maximum pump head The pump will try to maintain that head between its ports Hmax proportional to Q will reduce the head at the low flow It will drop for a set percentage at zero flow Limit rpm can provide a head regulatio...

Page 7: ...e the system is filled with fluid to prevent bearing damage 2 Overload trip protective shutdown Overcurrent line surge or locked rotor caused the pump to restart If the issue persists check if the rotor is spinning freely 3 Motor too hot Motor has exceeded allowed temperature and is now stopped to cool down Extremely hot medium or hardware failure might have caused that 4 Frequency converter error...

Page 8: ...le device NOR Will it ma3e the iridian accessiVle over the internet 16 1 Hireless Setting This is where it is possible to personalize the name of the wireless network The example below illustrates a network called Viridian Wireless Regardless of the wireless network name once set up the wireless device iPhone iPad PC Mac or Android device is directed to connect to that network Viridian Wireless as...

Page 9: ...uniquement a l interieur 11 Electrical Data Pump Ratings 1 phase 110 240V 47 63Hz VR15 VR20 1 phase 200 240V 47 63Hz VR25 VR30 Power Consumption HP VR15 0 027 0 680 HP VR20 0 035 1 088 HP VR25 0 054 1 496 HP VR30 0 054 2 175 HP Power Consumption W VR15 20 500 W VR20 26 800 W VR25 46 1100 W VR30 40 1600 W Rated Current 1 phase 115 230V VR15 2 2 A 6 0 A VR20 3 5 A 6 0 A Rated Current 1 phase 230V VR...

Page 10: ...0 75 100 125 150 175 200 225 250 275 300 325 350 375 400 HEAD FT 0 5 10 15 20 25 30 35 40 45 50 Flow liter min 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 Head m 0 2 4 6 8 10 12 14 Performance 3 4 1 VR15 3 VR25 4 VR30 2 VR20 1 2 ...

Page 11: ...11 NOTES ...

Page 12: ...a Taco product or part or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defec tive product or part Taco reserves the right to make changes in details of design construction or arrangement of ...

Reviews: