When using an iSeries Mixing Valve, the following piping require-

ments must be considered for proper operation.

1) In order to hydraulically isolate the boiler loop from the injection 

or  system  loop    primary/secondary  piping  must  be  used.  There 

must be no more than 4 pipe diameters between the tees in the 

boiler loop (Note 1).

2) There must be at least 6 pipe diameters of straight pipe on either 

side of the tees (Note 2) in order to prevent the momentum of water 

in the boiler loop from pushing flow through the injection loop.

3) There should be a minimum of 1 foot drop on the return pipe 

of the injection loop, in order to create a thermal trap (Note 3) and 

prevent unwanted heat transfer.

4)  When  using  a  2-way  iSeries  Mixing  Valve,  a  balancing  valve 

must be located between the tees in the system loop, in order to 

provide a pressure drop to induce flow through the mixing loop.

2-Way iSeries Mixing Valve Selection

In order to properly size the 2-Way iSeries Mixing Valve, follow the design procedure below:

1) Determine the design radiant heating load.

2) Determine the design boiler supply temperature.

3) Determine the radiant system return temperature which is based on the design temperature drop across the radiant system.
4) Determine the design injection flow rate using the following equation:

Eq.1:

5) From the 2-Way Cv chart below, select the valve size with the closest Cv value to the injection flow rate calculated in step 4. Do not 

size the 2-Way iSeries Mixing Valve based soley on pipe size.

3-Way iSeries Mixing Valve Selection

Select the 3-Way iSeries Mixing Valve based on the 3-way Pressure Drop chart below.

Sequence of Operation

Power Up and Heat Request

Whenever the iSeries-R is powered up, the LED turns on and the control starts operation. The power to the iSeries-R may be switched 

through an end switch (e.g. Taco ZVC/SR style zone control) or a thermostat for intermittent operation, or the power source may be 

connected directly to the iSeries-R for continuous operation.

2

Cbmbodjoh

Wbmwf

Cpjmfs

Mppq

Tztufn

Mppq

Jokfdujpo

Wbmwf

Opuf!4

Opuf!2

Opuf!3

jTfsjft.S

Nvmujqmf!Ufnqfsbuvsf!Tztufn

jTfsjft.S

jTfsjft.S

Pvuepps

Tfotps

Tvqqmz

Tfotps

Pvuepps

Tfotps

Tvqqmz

Tfotps

Cpjmfs!Tfotps

Cpjmfs!Tfotps

C

D

B

C

D

B

4.xbz!Wbmwf!xjui!Ijhi!Ufnqfsbuvsf![poft

)Bmufsobuf!Qjqjoh*

Tvqqmz

Tfotps

jTfsjft.S

C

D

B

Pvuepps

Tfotps

C

D

B

Design Injection Flow Rate (US GPM) =

 

Design Radiant Heating Load (Btu/hr)

500 x (Boiler Supply - Radiant System Return)

1/2"

(Cv = 1.5)

PSI

GPM

Flow

Ft Head

0.11
0.44

1.03

0.09

0.21

0.11

0.26

1.00

2.31

0.21

0.48

0.25

0.58

1.78

4.11

0.37

0.85

0.44

1.03

1.47

3.39

1.78

4.11

3.31

7.64

4.00

9.24

5.88

13.58

1/2

1

2
4
6
8

1 1/2

0.26

3/4"

(Cv = 3.3)

PSI

i Series: 3-Way Valve Pressure Drop

Ft Head

0.02

0.05

1"

(Cv = 3.0)

PSI

Ft Head

0.03

0.06

1/2"

4.9

10.3

8.9

3/4"

1"

i Series: 2-Way Cv

Size

Cv

Summary of Contents for i Series

Page 1: ...mperature drop For example if a Reset Ratio of 1 2 is selected the supply water temperature is increased by 1 2 degrees of every 1 degree of outdoor temperature drop 2 Way 3 Way Mixing An iSeries Mixing Valve may be used to mix the hot boiler water temperature with the cooler return water temperature from the system loop The position of the iSeries Mixing Valve is modulated in order to inject diff...

Page 2: ...1 5 From the 2 Way Cv chart below select the valve size with the closest Cv value to the injection flow rate calculated in step 4 Do not size the 2 Way iSeries Mixing Valve based soley on pipe size 3 Way iSeries Mixing Valve Selection Select the 3 Way iSeries Mixing Valve based on the 3 way Pressure Drop chart below Sequence of Operation Power Up and Heat Request Whenever the iSeries R is powered ...

Page 3: ...he minimum setting The minimum setting is selected via DIP switch 3 When the switch is turned on the minimum temperature is set to 120 F and when the DIP is turned off the minimum tempera ture is 135 F When using low temperature boilers such as condensing or electric the boiler minimum temperature may be disabled by powering up the control without a boiler return sensor Whenever the iSeries R is b...

Page 4: ...able In order to prevent damage to the electronics disconnect all plugs before the power is turned on and check voltages and sensors Once the circuits are tested plug in the ter minals Powering the Control For intermittent operation connect one side of the end switch e g Taco ZVC SR series zone control or thermostat to an external 24 V ac trans former Connect the other side of the zone control s e...

Page 5: ...eatly simplify troubleshooting of the iSeries R When the control flashes an error message identify the fault and follow standard test ing procedures to confirm the problem If you suspect a wiring fault return to the wiring section on this brochure and carefully check all external wiring and wiring connections Multi Status LED Adjustment of Settings If the outdoor temperature is cold and the buildi...

Page 6: ... rings EPDM Dimensions Ufnqfsbuvsf Sftjtubodf Ufnqfsbuvsf Sftjtubodf Ufnqfsbuvsf Sftjtubodf Ufnqfsbuvsf Sftjtubodf G D X G D G D G D 41 31 21 1 21 31 41 51 61 71 81 91 1 211 221 231 241 251 261 271 281 291 2 1 311 45 3 34 29 23 8 2 5 21 27 32 38 43 49 54 5 65 71 77 82 88 93 99 4 345 2 7 276 291 229 129 96 473 73 576 57 329 45 669 37 1 2 11 26 422 22 994 3 8 445 6 939 5 776 4 871 4 161 3 5 1 3 156 ...

Page 7: ...tion 9300 2044RP Strap on Sensor 9300 2052RP Outdoor Sensor iT024Q6A1 Outdoor Reset Actuator iU024Q6A1 Setpoint Actuator Notes 7 2 j jWbmwf Tj f 161 203 186 405 211 2 Dpoofdujpo D Txfbu U Uisfbe Cbmm Uzqf 3 3 Xbz 4 4 Xbz Bduvbups Uzqf S Sftfu T Tfuqpjou ...

Page 8: ...epair Any Taco product or part not installed or operated in conformity with Taco instructions or which has been subject to misuse misapplica tion the addition of petroleum based fluids or certain chemical additives to the systems or other abuse will not be covered by this warranty If in doubt as to whether a particular substance is suitable for use with a Taco product or part or for any applicatio...

Reviews: