INSTALLATION

Warning:

 Electrical shock hazard. To prevent electrical shock or equipment damage, disconnect 

ALL

 

power sources to controllers and loads before installing or servicing this equipment or modifying any wir-
ing.

Thermistors are resistive elements, and therefore, are NOT polarity sensitive. It is recommended that wir-
ing for these units not be run in the same conduit as line voltage wiring or with wiring used to supply highly 
inductive loads such as motors, generators, and coils.

Mounting the Device

When mounting on a pipe, the unit should be mounted on the bottom side of the pipe to ensure proper heat transfer 
and an accurate temperature reading. Heat transfer compound and proper insulation will help the overall accuracy of 
the sensor.

WIRING INFORMATION

The following electrical connection can be made to the iWorx® TRP series sensors:

• Wiring to the temperature inputs of iWorX controllers

CAUTION:

 Do not connect any power wiring to the sensor. Failure to observe this precaution will damage 

the sensor. 

Wiring

Wiring includes a connection between an iWorx® controller and an iWorx® TRP Series sensor.

Wiring requires at least 18 gauge (0.205 mm

2

), shielded twisted-pair wire.

Note:

• Wiring is polarity insensitive.
• Shielded cable is required.
• Wiring can be in the same conduit with UI, AO, and DI Wiring.
• If the cable is installed in areas of high RIF/EMI, the cable must be in conduit.

Connecting the iWorx® TRP Series Sensor 

Requires 2-wire connection to the controller. To connect the thermistor outputs, attach the wires from the sensor to suit-
able terminals of the controller, as shown in Figure

 1.

Figure 1: Wiring Connections.

Wiring Checkout 

Verify wiring between TRP sensor and the iWorx® Controller is installed according to job wiring diagram, national and 
local wiring codes.

Summary of Contents for iWorx TRP Series

Page 1: ...Sensor 2 Overview 2 Features 2 Applicable Documentation 2 Installation Instructions 3 Precautions 3 General 3 Static Electricity 3 Location 3 Before Installing 3 About this Document 3 Inspecting the...

Page 2: ...via low cost shielded twisted pair cable Stainless steel probe Output 10K Ohm 77 F Applicable Documentation Model Total Length TRP1 24 inches TRP2 11 feet Description Audience Purpose iWorx TRP Series...

Page 3: ...a known securely grounded object to discharge any charge you may have accumulated Use a wrist strap when handling printed circuit boards The strap must be secured to earth ground Location Avoid locati...

Page 4: ...sensor WIRING INFORMATION The following electrical connection can be made to the iWorx TRP series sensors Wiring to the temperature inputs of iWorX controllers CAUTION Do not connect any power wiring...

Page 5: ...sensor follow the steps below before contacting your local TES representative or TES technical service 1 Make sure sensors are connected and communicating to desired devices 2 Record precise hardware...

Page 6: ...iWorx TRP Series Sensor 6 502 019 Effective October 17 2011 2011 Taco Electronic Solutions Inc Notes...

Page 7: ...iWorx TRP Series Sensor 502 019 Effective October 17 2011 7 2011 Taco Electronic Solutions Inc...

Page 8: ...this warranty TES products are not intended for use to sup port fire suppression systems life support sys tems critical care applications commercial aviation nuclear facilities or any other applica t...

Reviews: