4 Installation
TAC Xenta, TAC Xenta® 400 I/O Modules
TAC AB, Dec 2004
0-004-7771-3 (EN)
4.2
Electrical installation
4.2.1
General considerations
Installation is normally treated as category CAT III (IEC 664), which in
principle means permanent connection to a 230 V AC mains supply. For
the Xenta 400, this is only applicable to the relay outputs of the I/O
modules.
All equipment connected to the TAC Xenta units must comply with the
following standards:
•
EN 60 742 (or other relevant safety standard; for example ETL
listing UL 3111-1, first version and CAN/CSA C22.2 No. 1010.1-
92) for the device(s) that provide an ELV-type power supply (nor-
mally 24 V AC) to the controller and other connected equipment.
•
EN 61 010 or IEC 950 (or other relevant safety standard) for com-
puters, modems and other equipment powered by a 230 V mains
supply.
If equipment using a 230 V mains supply is connected to a relay output
terminal of the I/O modules, low-voltage equipment connected to the
other relay terminals of the controller must provide at least basic insu-
lation to all touchable parts.
We strongly recommend that switches are installed to make it possible
to separate external equipment when the relay output terminals control
equipment using a 230 V mains supply.
4.2.2
Input/Output Circuit Principles
The input/output circuit principles and key values are shown below.
Current Input 0-20 mA
Fig. 4.3: Current Input - internal resistance
Table 4.1:
Unit
R
i
ohm
Xenta 420A
47
Xenta 450A
47
Xenta 470
20
Summary of Contents for Xenta 400 Series
Page 1: ...TAC Xenta TAC Xenta 400 I O Modules...
Page 2: ......
Page 3: ...TAC Xenta TAC Xenta 400 I O Modules...
Page 6: ...Contents TAC Xenta TAC Xenta 400 I O Modules 6 48 TAC AB Dec 2004 0 004 7771 3 EN...
Page 7: ...INTRODUCTION 1 Introduction...
Page 8: ......
Page 11: ...REFERENCE 2 I O Modules in the TAC Xenta 400 series 3 Technical Description 4 Installation...
Page 12: ......
Page 47: ......