TAC Xenta, TAC Xenta® 400 I/O Modules
3 Technical Description
TAC AB, Dec 2004
23 (48)
0-004-7771-3 (EN)
Technical data TAC Xenta 421A and 422A
Supply voltage (G, G0) .................................24 V AC ±20%, 50/60 Hz
or ...................................................................... 21.6–40 V DC
Power consumption ................................................................. max. 4 W
Transformer sizing .........................................................................8 VA
Universal inputs (U1–U4):
Quantity..........................................................................................4
A/D-resolution ......................................................................12 bits
–as Digital Inputs;
Voltage across open contact.............................................. 20 V DC
Current through closed contact ...............................................3 mA
Pulse input duration (TAC Menta CNT block)..............min. 20 ms
–as Thermistor Inputs;
TAC thermistor sensor ........................ 1800 ohms at 25 °C (77 °F)
Supply voltage..................................................................... 1 V DC
or (individually selectable)
TAC thermistor ..................................... 10 kohms at 25 °C (77 °F)
Supply voltage..................................................................... 5 V DC
Measuring range.................. –50 °C to +150 °C (–58 °F to 302 °F)
Inaccuracy:
–50 °C to –30 °C (–58 °F to –22 °F)........................................... ±1.5 °C (±2.7 °F)
–30 °C to 0 °C (–22 °F to +32 °F) .............................................. ±0.5 °C (±0.9 °F)
±0 °C to +50 °C (+32 °F to +122 °F).......................................... ±0.2 °C (±0.4 °F)
+50 °C to +100 °C (122 °F to 212 °F) ........................................ ±0.5 °C (±0.9 °F)
+100 °C to +150 °C (212 °F to 302 °F) ...................................... ±1.5 °C (±2.7 °F)
–as Current Inputs;
Input signal (terminals U–M; over-current protected) ......0–20 mA
Input resistance ................................................................... 47 ohm
Inaccuracy within ..........................± (0.03 mA + 0.4 % of reading)
–as Voltage Inputs;
Input signal.................................................................... 0–10 V DC
Input resistance ............................................................. >100 kohm
Inaccuracy within ...............................± (7 mV + 0.2 % of reading)
LED digital input status indicators (TAC Xenta 422A only):
Quantity..........................................................................................4
Color................................ red or green, selected using TAC Menta
Polarity ......... non-inverted or inverted, selected using TAC Menta
Digital outputs (K1–K5):
Quantity..........................................................................................5
Control voltage, relay outputs ......................... max. 2A, 250 V AC
Control current, to be protected by a max. 10 A fuse,
................max 2 A (greater current allowed for short periods)
Pulse length .....................................................................min. 0.5 s
Manual override for digital outputs (TAC Xenta 422A only):
Quantity..........................................................................................5
Switch positions .................................................. ON, AUTO, OFF
Indicators for Auto output status.................................. green LEDs
Summary of Contents for Xenta 400 Series
Page 1: ...TAC Xenta TAC Xenta 400 I O Modules...
Page 2: ......
Page 3: ...TAC Xenta TAC Xenta 400 I O Modules...
Page 6: ...Contents TAC Xenta TAC Xenta 400 I O Modules 6 48 TAC AB Dec 2004 0 004 7771 3 EN...
Page 7: ...INTRODUCTION 1 Introduction...
Page 8: ......
Page 11: ...REFERENCE 2 I O Modules in the TAC Xenta 400 series 3 Technical Description 4 Installation...
Page 12: ......
Page 47: ......