TAC Xenta 411/412 Digital Input module
The modules have ten digital inputs, these inputs can also be used as
pulse counters.
The TAC Xenta 412 is also equipped with LED status indicators, one
for each digital input. The LED colors, red or green, can be selected
individually by the setting switches under the front cover.
Terminals (411, 412) and Indicators (412)
Technical data TAC Xenta 411 and 412
Supply voltage (G, G0) .................................24 V AC ±20%, 50/60 Hz
or .......................................................................... 19–40 V DC
Power consumption ................................................................. max. 2 W
Transformer sizing .........................................................................2 VA
Digital inputs (X1–X10):
Quantity........................................................................................10
Voltage across open contact.............................................. 33 V DC
Current through closed contact ...............................................4 mA
Pulse input duration (TAC Menta CNT block)..............min. 20 ms
LED digital input status indicators (TAC Xenta 412 only):
Quantity........................................................................................10
Color.................................red or green, selected with a DIP switch
Fig. 3.3: TAC Xenta 411/412 terminals and TAC Xenta 412 DI indicators
2 3 4 5 6 7 8 9 10
DI
TAC Xenta 412
~ 0
24 V AC/DC
}
1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20
X5 M X6 X7 M X8 X9 M X10
G G0 C1C2 X1 M X2 X3 M X4
Comm
}
10 DI Indicators:
⇑
red
⇓
green
Table 3.1: TAC Xenta 411/412 summary
Type
No.
TAC Menta Block type
Terminal ref.
Indicators (412)
Digital input
10
DI - Digital input
or
CNT - Pulse counter
X1 - X10
X1 - X10
red or green
red or green
Summary of Contents for Xenta 400 Series
Page 1: ...TAC Xenta TAC Xenta 400 I O Modules...
Page 2: ......
Page 3: ...TAC Xenta TAC Xenta 400 I O Modules...
Page 6: ...Contents TAC Xenta TAC Xenta 400 I O Modules 6 48 TAC AB Dec 2004 0 004 7771 3 EN...
Page 7: ...INTRODUCTION 1 Introduction...
Page 8: ......
Page 11: ...REFERENCE 2 I O Modules in the TAC Xenta 400 series 3 Technical Description 4 Installation...
Page 12: ......
Page 47: ......