3 Technical Description
TAC Xenta, TAC Xenta® 400 I/O Modules
TAC AB, Dec 2004
0-004-7771-3 (EN)
3.6
TAC Xenta 451A/452A Universal Input and
Analog Output module
The modules have eight universal inputs and two analog outputs. The
universal inputs can be used as analog inputs, digital inputs or pulse
counters.
The TAC Xenta 452A is also equipped with LED status indicators for
each universal input (when used as a digital input) and manual override
controls for the analog output values. The LED input status colors, red
or green, and the polarity (lit when contact is open or closed) can be
selected individually by altering the parameter settings in TAC Menta.
Terminals (451A, 452A) and Controls/Indicators (452A)
These modules can also be used as certified L
ON
M
ARK
® devices. The
configuration and use of SNVTs are explained in the 0FL-4182 Config-
uration Instruction.
Fig. 3.7: TAC Xenta 451A/452A terminals and TAC Xenta 452A Analog output override controls and
Indicators
MAN 1
AUTO
MAN 2
AUTO
0-10V
0-10V
TAC Xenta 452A
AO
DI
7
6
5
4
3
2
1
8
1 2
3
4 5 6 7
8
9 10
11 12 1
3
14 15 16 17 1
8
19 20
G G0 C1C2 U1 M U2 U
3
M U4
Y1 M Y2 U5 M U6 U7 M U
8
UI
~
0
24 V AC
}
Comm
}
AO
UI
(21.6
−
40 V DC)
20 V DC
2 Analog outputs:
Override controls
8 DI Indicators:
red/green
Table 3.5: TAC Xenta 451A/452A summary
Type
No.
TAC Menta Block type
Terminal ref.
Ind./Override
(452A)
Universal inputs
8
AI - Analog input
or
DI - Digital input
or
CNT - Pulse counter
U1 - U8
U1 - U8
U1 - U8
-
red or green / -
-
Analog outputs
2
AO - Analog output
Y1 - Y2
- / Man-Auto
Summary of Contents for Xenta 400 Series
Page 1: ...TAC Xenta TAC Xenta 400 I O Modules...
Page 2: ......
Page 3: ...TAC Xenta TAC Xenta 400 I O Modules...
Page 6: ...Contents TAC Xenta TAC Xenta 400 I O Modules 6 48 TAC AB Dec 2004 0 004 7771 3 EN...
Page 7: ...INTRODUCTION 1 Introduction...
Page 8: ......
Page 11: ...REFERENCE 2 I O Modules in the TAC Xenta 400 series 3 Technical Description 4 Installation...
Page 12: ......
Page 47: ......