M800 is an electro-mechanical actuator for the control of
two-way and three-way plug valves in:

domestic hot water systems

heating systems

air handling systems

M800 is either controlled by an increase/decrease signal
or by a modulating 2–10 V control signal. Modulating
control makes for a faster positioning of the actuator.

The electronic circuitry of the actuator ensures that the
running time is the same, regardless of the stroke of the
valve in question.

It is easy to mount and connect the actuator. It can be
mounted directly onto TAC’s control valves, without any
mounting kit.

The working range of the actuator is adjusted
automatically depending on the stroke of the valve.  The
electronic circuitry of the actuator then takes care of the
adjustment of the valve end positions.

The actuator is supplied by 24 V AC. It can provide
16 V DC voltage supply for older TAC controllers.

Actuator for valves

G-40-36

11 Jan 2005

TECHNICAL DATA, M800

Part numbers ....................... see the table on the next page
Supply voltage .................. 24 V AC +10%/ -40%, 50–60 Hz
Power consumption ...................................... average 15 VA
Transformer sizing ...................................................... 50 VA
Running time:

Modulating 10–25 mm (0.39 - 1 in.) ........................... 15 s
Modulating 25–32 mm (1 - 1.26 in.) ........................... 20 s
Modulating 10–52 mm (0.39 - 2.05 in.) ...................... 30 s
Increase/decrease ............................................ 300 s/60 s

Close off time with STS, at power failure:

Stroke 10–25 mm (0.39 - 1 in.) ......................... max. 20 s
Stroke 25–32 mm (1 - 1.26 in.) ......................... max. 25 s
Stroke 32–52 mm (1.26 - 2 in.) ......................... max. 35 s

Stroke ............................................. 10–52 mm (0.39 - 2 in.)

Factory set stroke ................................... 41 mm (1.61 in.)

Thrust .......................................................... 800 N (180 lbf.)
Duty cycle .......................................... max. 20%/60 minutes
Analog input:

Voltage .................................................................. 0–10 V
Impedance ..................................................... min 100 k

Digital inputs VH–VC:

Voltage across open input .................................. 24 V AC
Current through closed input .................................... 5 mA
Pulse time ....................................................... min. 20 ms

Output G1:

Voltage ..................................................... 16 V DC ±0.3 V
Load ......................................... 25 mA, short-circuit proof

Output  Y:

Voltage ................................................... 2-10 V (0-100%)
Load ......................................................................... 2 mA

Ambient temperature:

Operation ............................ –10 – +50 °C (14°F - 122°F)
Storage ................................ –10 – +50 °C (14°F - 122°F)

Ambient humidity ............................................ max. 90% RH
Enclosure rating ........................................................... IP 54
Sound power level ........................................... max. 40 dBA
Standards:

Emission ............................................... EN 50081-1:1992
Immunity ............................................... EN 50082-1:1992
Heat ................................................................. IEC-68-2-2
Humidity .......................................................... IEC-68-2-3
Cold ................................................................. IEC-68-2-1
Vibration .......................................................... IEC-68-2-6

Material:

Housing ............................................................ aluminium
Cover ........................................................ ABS/PC plastic

Color ........................................................... aluminium/black
Weight ......................................................... 1.8 kg (3.96 lb.)
Dimensions (mm) .......... refer to the table on the next page

TAC Forta M800

Summary of Contents for Forta M800

Page 1: ...next page Supply voltage 24 V AC 10 40 50 60 Hz Power consumption average 15 VA Transformer sizing 50 VA Running time Modulating 10 25 mm 0 39 1 in 15 s Modulating 25 32 mm 1 1 26 in 20 s Modulating 1...

Page 2: ...rease decrease signal or by a variable direct voltage If an increase decrease signal is used the actuator normally moves inwards on an increase signal and outwards on a decrease signal see Settings Ma...

Page 3: ...over it is charged continuously for maintenance purposes Batteries for the STS uses NiCd SELF TESTING SAFETY DEVICE STS Figure 4 TECHNICAL DATA STS Supply voltage G 24 V AC 10 G0 return Output voltage...

Page 4: ...accepted in simplified installations on the following conditions the cables between the controller and actuator are shorter than 100 m 328 ft the cross sectional area is larger than 1 5 mm2 AWG 16 an...

Page 5: ...a Controller Normal installation 4 wires to the actuator Short cable installation 3 wires to the actuator Forta Controller Forta Controller Normal installation 5 wires to the actuator Short cable inst...

Page 6: ...AC supply to the controller TAC 239W TAC 6711 TAC Xenta TAC 8000 TAC 230U TAC 2000 TAC 9000 TAC 77xx Modulating control 16 V DC supply to the controller TAC 218E RM TAC 221L TAC 228R RL RF TAC 239W T...

Page 7: ...OFF position as the switch MOD INC is not valid during sequence or parallel control 4 Voltage range 0 10 2 10 You can choose whether to use the control signal voltage range 0 10 V or 2 10 V 5 Part of...

Page 8: ...ent is finished by the actuator closing the valve again the electronic circuitry then adjusts the stroke and the running time to the valve The set values are stored in the EEPROM of the actuator so th...

Reviews: