module switched OFF and wait for the battery voltage drop down naturally
(15mins) then restart. If then no alarm comes out, this means the module is ready
for work
6.
Buzzer rings and
ALM solid red
j) Reverse connection of cables.
Solution:
Power off all battery and inverters. Disconnect breaker. Check the cable
connection and disconnect all power cables. Check the power port damaged or
not. Then try turn on the single module, without any cable connected. If no alarm,
then it is reverse connection of cables. Switch off the module and contact your
local distributor.
k) MOSFAIL.
Solution:
Power off all battery and inverters. Disconnect breaker. Check the cable
connection and disconnect all power cables. Check the power port damaged or
not. Check the setting of inverter or charger, check the communication between
inverter and battery system.
Try turn on the single module, without any cable connected. If still buzzer rings.
Then switch off the module and contact your local distributor.
7.
After switch On, the module turns on directly
l) BMS failure.
Solution:
Switch off the module and contact your local distributor.
Excluding the points above, if the faulty still cannot be located, turn off battery
and contact your local distributor.
7. Emergency Situations
1.
Leaking Batteries
If the battery pack leaks electrolyte, avoid contact with the leaking liquid or gas.
If one is exposed to the leaked substance, immediately perform the actions de-
scribed below.
a) Inhalation: Evacuate the contaminated area and seek medical attention.
b) Contact with eyes: Rinse eyes with flowing water for 15 minutes and seek med
-
ical attention.
c) Contact with skin: Wash the affected area thoroughly with soap and water and
seek medical attention.