SN of RJ45cable
Mark
Pin
WI0SCAN30RJ1
With
blue
mark:
Battery-Inverter
Pin1~3: NULL
Pin4~8: pin to pin
For connection to inverter
WI0SCAN35RJ3
With silver mark:
Battery-Battery
Pin1~8: pin to pin
For parallel connection
between master batteries
5.2 Installation location
Make sure that the installation location meets the following conditions:
1.
The area is completely waterproof
2.
The floor is flat and level.
3.
There are no flammable or explosive materials.
4.
The ambient temperature is within the range from 0°C to 50°C.
5.
The temperature and humidity are maintained at a constant level.
6.
There is minimal dust and dirt in the area.
7.
The distance from heat source is more than 2 meters.
8.
The distance from air outlet of inverter is more than 0.5 meters.
9.
The installation areas shall avoid of direct sunlight.
10.
There is no mandatory ventilation requirements for battery module, but please
avoid of installation in confined area. The aeration shall avoid of high salinity, hu
-
midity or temperature.
Caution
If the ambient temperature is out of the operating range, the battery stops operating to pro-
tect itself. The optimal temperature range for the battery pack to operate is 10°C to 40°C.
Frequent exposure to harsh temperatures may deteriorate the performance and life of the
battery.
5.3 Grounding
Grounding cables shall be 10AWG or higher yellow-green cables.
After connection, the resistance from battery grounding point to
Ground connection point of room or installed place shall smaller
than 0.1Ω.
1) Based on metal directly touch between the module’s surface
and rack’s surface. If using painted rack, the corresponding
place shall remove the painting.