The one with empty Link Port 0 is the Master Battery Module, others are slaves (1
master battery configure with maximum 15 slave batteries):
3.
Press the red SW button of master battery to power on, all the battery LED light will
be on one by one from the Master battery:
Note:
•
After the battery module powered on, the soft-start function takes 3sec to active. Af-
ter soft-starts battery ready to output high power.
•
During capacity expansion or replacement, when parallel different SOC/voltage of
module together, please maintain the system in idle for ≥15mins or till the SOC LEDs
becomes similar(≤1dot difference) before normal operation.