TAC Xenta 511 and 911 Handbook
2 TAC Xenta 511
TAC AB, 16 May 2003
0-004-7870-0 (EN), 15 (32)
2.4
Operation and Service
2.4.1 LED Indicators
LON Neuron status
Off
Normal Mode
Red, blinking
Unconfigured Node
Red, steady
Hardware Fault
Fail-safe state
Shorting terminals Fail-safe 9 and 10 will put the unit in the “fail-safe”
state. This may be used in an emergency if the system program keeps
halting.
The position of the switch is noted directly after powering on.
Overall status indicator
Green, steady
Normal Mode
Green, blinking
Start Mode
Red, steady
Fail-safe Mode (see description above)
Red, blinking
Unit Error
2.4.2 Service Utilities
System service functions are available using the web browser and are
located under the Utilities menu. They are primarily intended to provide
technical information about the system and its status and can be printed
to a file or a printer.
System Info
MMC
10Base-T
A RS232 B
LON
Fail-
safe
Rx/Tx
9 10
TAC Xenta 511 status indicators
Rx indicator RS232 B (yellow)
Tx indicator RS232 A (yellow)
Overall Run indicator (green/red)
Neuron status (red)
Ethernet activity (yellow)
Ethernet connector
Socket for MMC memory and activity indicator (yellow)
Service Pin
Summary of Contents for TAC Xenta 511
Page 1: ...0 004 7870 0 EN 16 May 2003 TAC Xenta 511 and 911 Handbook TAC Xenta...
Page 2: ......
Page 18: ...TAC Xenta 511 and 911 Handbook 2 TAC Xenta 511 18 32 0 004 7870 0 EN TAC AB 16 May 2003...
Page 32: ...TAC Xenta 511 and 911 Handbook 3 TAC Xenta 911 30 32 0 004 7870 0 EN TAC AB 16 May 2003...
Page 34: ...TAC Xenta 511 and 911 Handbook Index 30 32 0 004 7870 0 EN TAC AB 16 May 2003...
Page 35: ......