TAC Xenta 511 and 911 Handbook
3 TAC Xenta 911
TAC AB, 16 May 2003
0-004-7870-0 (EN), 29 (32)
3.6
Technical Data for the TAC Xenta 911
Supply voltage ...............................................24 V AC ±20%, 50/60 Hz
...................................................................................or 19–40 V DC
Power consumption ................................................................. max. 5 W
Transformer sizing .........................................................................5 VA
Ambient temperature:
Storage......................................–20 °C to +50 °C (-4 °F to +122 °F)
Operation................................ ±0 °C to +50 °C (+32 °F to +122 °F)
Humidity................................................ max. 90% RH non-condensing
Mechanical:
Enclosure..............................................................................ABS/PC
Enclosure rating ........................................................................ IP 20
Dimensions....... see section 3.2 “Hardware Installation” on page 17
Weight ...................................................................... 0.2 kg (0.44 lb.)
Real time clock:
Accuracy at +25 °C ..........................................±14 minutes per year
Power outage protection..............................................................72 h
Communication:
A: Modem ............................. 9,600-57,600 bps RS232A, RJ45, 8-p
B: PC, configuration........................................... RS232B, RJ10, 4-p
L
ON
W
ORKS
...............................................TP/FT-10, terminal block
Agency Compliances:
Emission ......................................C-Tick, EN 50081-1, FCC Part 15
Immunity ........................................................................ EN 50082-1
Safety:
CE................................................................................... EN 61010-1
UL 916 ...........................................Energy Management Equipment
ETL listing .................................................. UL 3111-1, first edition
....................................................... CAN/CSA C22.2 No. 1010.1-92
Flammability rating ........................................................... UL 94V-0
Part numbers:
Electronics part TAC Xenta 911 ..................................... 0-073-0831
Terminal part TAC Xenta 400 ........................................ 0-073-0902
TAC Xenta: PC to Serial Kit........................................... 0-073-0917
TAC Xenta: Serial Link Kit ............................................ 0-073-0918
TAC Xenta: General Serial Kit ....................................... 0-073-0919
TAC Xenta: Programming Serial Kit.............................. 0-073-0920
TAC Xenta: Modem Connect Kit ................................... 0-073-0916
Summary of Contents for TAC Xenta 511
Page 1: ...0 004 7870 0 EN 16 May 2003 TAC Xenta 511 and 911 Handbook TAC Xenta...
Page 2: ......
Page 18: ...TAC Xenta 511 and 911 Handbook 2 TAC Xenta 511 18 32 0 004 7870 0 EN TAC AB 16 May 2003...
Page 32: ...TAC Xenta 511 and 911 Handbook 3 TAC Xenta 911 30 32 0 004 7870 0 EN TAC AB 16 May 2003...
Page 34: ...TAC Xenta 511 and 911 Handbook Index 30 32 0 004 7870 0 EN TAC AB 16 May 2003...
Page 35: ......