The outdoor temperature limits are set with
P:38 Outdoor temperature 100% night setback
(and 100% boost)
P:39 Outdoor temperature 0% night setback
(and 0% boost)
P:38 must always be greater or equal to P:39. If both values are set
equal
,
there will always be a full night setback, regardless of the outdoor tempera-
ture. Also the morning boost will have its maximum value for all outdoor
temperatures below the value P:38 (=P:39).
The boost time (time before Day time) and the amount of boost, in °C, are
specified with
P:40 Boost time (minutes)
P:41 Max-boost (°C)
The valid SP is calculated by removing any night setback and adding the boost
value determined by the outdoor temperature as shown in the figure.
If P:40 or P:41 is set to zero, the morning boost will be inhibited.
4.8 Extended day/night operation
Day operation is extended if terminal X1 is short-circuited to teminal M, via a
switch or a separate timer.
In the same way, night operation is extended if terminal X2 is connected to M.
This type of forced operation is indicated on the display by the flashing
apperance of the corresponding symbol. See also the description of P:00 in
section 3.2.
Night setback and Morning boost
P:39
P:38
0
20
0 %
50%
Max. boost
(P:41)
–20
30
Increase
of SP
supply
0
20
0 %
Night
setback
P:39
–20
30
50 %
100 %
t
outdoor
(°C)
P:38
t
outdoor
(°C)
Summary of Contents for TAC 200
Page 1: ...TAC 200 User s Manual 0 004 6921 0 GB 2000 02 09...
Page 38: ......
Page 39: ......
Page 40: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 vx...