TAC AB, Feb 2000
4:9
Special functions, P:16 -
TAC 200 User’s Manual
4.7 Night setback and Morning boost
TAC 200 uses a night SP during the night time operation.
The actual SP value depends on several factors.
If there
is
a room sensor,
without
a SP dial, EGRL:
P:06 Setpoint room, night
(used as
SP
room
)
If there
is
a room sensor,
with
a SP dial, EGF1:
P:07 Night setback SP
(affecting the
SP
room
)
(A positive value means
raising
the night temperature.)
If there is
no
room sensor:
P:07 Night setback SP
(affecting the
SP
supply
)
To summarise:
Application
S P
d a y
SP
night
EGRL
P:05
P:06
EGF1
SP-dial
SP-dial adjusted with P:07
No sensor
SP
supply
SP
supply
adjusted with P:07
The SP value is also affected by the variable Night setback and the
Morning boost.
The Night setback of the supply temperature varies to ensure that the
heating system will be able to reach the correct room temperature even
after nights with low outdoor temperatures.
The magnitude of the setback is determined via a curve with two variable
outdoor temperatures, P:38 and P:39, see figure on the next page.
These two outdoor temperatures are also used to determine the Morning boost.
A certain time before time program 1 will indicate Day time operation, the
controller boosts the supply temperature.
The boost varies with the outdoor temperatures. It reaches its maximum at the
P:38 temperature and is reduced to zero at 20°C and at the P:39 temperature
(where there is no longer any night setback), please refer to the figure.
Summary of Contents for TAC 200
Page 1: ...TAC 200 User s Manual 0 004 6921 0 GB 2000 02 09...
Page 38: ......
Page 39: ......
Page 40: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 vx...