background image

F-26159-5

©

 

Copyright 2008 TAC All Rights Reserved.

7

0 to 10 or 6 to 9 V 
Range (CP-8552 only)

To check transducer operation:

1. Check for foreign material such as dirt or oil in the air supply. Also check for clogged filters. 

Supply air contamination by dirt or oil is the most likely cause of malfunction.

2. Verify that the unit is mounted upright and wired correctly.

3. Verify that 24 Vac power is available and 20 psig (138 kPa) main air is present.

4. Verify with a digital voltmeter that an input signal between 0 to 10 or 6 to 9 V is present 

and of correct polarity.

5. Use a digital voltmeter to verify the presence of the correct power supply voltage 

between terminals 1 and 2.

6. Adjust the input signal to bottom of range (0 or 6 V).

7. Branch pressure should be 3 psig (21 kPa). If not, adjust start point potentiometer 

(Figure-4 ) to obtain a 3 psig (21 kPa) output.

8. Adjust input to top of range (9 or 10 V).

9. Branch pressure should be 15 psig (103 kPa). If not, adjust SPAN potentiometer 

(Figure-4 ) to obtain a 15 psig (103 kPa) output.

10. Recheck steps 6 through 9.

11. Unit is functional if correct pressures are indicated. Replace an inoperative transducer 

with a functional unit.

MAINTENANCE

Regular maintenance of the total system is recommended to assure sustained optimum 
performance.

FIELD REPAIR

Field repair is not recommended. Replace an inoperative transducer with a functional unit.

DIMENSIONAL DATA

Figure-5 CP-8551 and CP-8552 Dimensions.

Dimensions shown are in inches (mm). 

4-5/8

(118)

4

(102)

2-1/4

(57)

2-13/16

(71)

9/16

(14)

2-3/4

(70)

5/16

(8)

Side View

Front View

2-5/32

(55)

1/2

(13)

1-21/32

(42)

4-1/4
(108)

1-3/32

  (28)

Summary of Contents for CP-8551

Page 1: ...il mounting for quick snap on installation Two wire loop powered or three wire voltage input High accuracy with low hysteresis Long term driftless operation with high repeatability Low air consumption...

Page 2: ...Acting Maximum Pneumatic Output 1 to 18 psig 7 to 124 kPa Output Air Capacity Pressure 515 scim 141 ml s maximum with a 20 psig 138 kPa supply Operating Characteristics Linearity 1 of span 75 F 24 C...

Page 3: ...screws not provided M 636 4 in T and B wire tie not provided Training Installer must be a qualified experienced technician CP 8551 M B M 3 to 15 psig 21 to 103 kPa to controlled device direct acting...

Page 4: ...marily to provide a degree of protection against contact with the enclosed equipment Do not locate unit in areas subject to incidental contact vibration severe mechanical shock excessive moisture or c...

Page 5: ...per selection as follows 1 Choose input range 2 Consult Table 1 for jumper position 3 Place jumper over square posts on appropriate lettered block Figure 4 4 Calibrate by performing appropriate CHECKO...

Page 6: ...unction 2 Verify that the unit is mounted upright and wired correctly 3 Verify that 20 psig 138 kPa main air is present 4 Verify with a digital multimeter that a 4 to 20 mAdc signal is present and of...

Page 7: ...gnal to bottom of range 0 or 6 V 7 Branch pressure should be 3 psig 21 kPa If not adjust start point potentiometer Figure 4 to obtain a 3 psig 21 kPa output 8 Adjust input to top of range 9 or 10 V 9...

Page 8: ...marks and registered trademarks are the property of their respective owners Information contained within this document is subject to change without notice F 26159 5 www tac com TAC 1354 Clifford Avenu...

Reviews: