SPECIFICATIONS

Transducer Inputs

Input Signal:

CP-8551, 4 to 20 mA.
CP-8552, 4 to 20 mA, 6 to 9 V, and 0 to 10 V.

Input Impedance: 

CP-8551, 550 ¾ maximum, 400 ¾ minimum.
CP-8552, 550 ¾ maximum, 400 ¾ minimum, 4 to 20 mA input; >10,000 ¾ voltage input.

Power Input Requirements:

4 to 20 mA Input, None.
0 to 10 and 6 to 9 V Input, 
Requires 20 to 30 Vac, 3.9 VA (CP-8552), 50/60 Hz, or 24 
to 30 Vdc power supply, 1.6 watts maximum.

Input Range Selection: 

CP-8551, None.
CP-8552, Jumper selectable.

Air Supply Required: 20 psig (138 kPa) nominal, 30 psig (207 kPa) maximum. Clean, 
dry, oil free air required (refer to EN-123, F-22516).
Air Consumption for Sizing Air Compressor: Maximum 0.012 scfm (5.66 ml/s) @ 20 
psig (138 kPa) supply.
Air Capacity for Sizing Air Mains: Minimum 550 scim (150.24 ml/s).
Air Connections: Male barbed fittings for flexible 1/4" O.D. pneumatic tubing.
Wiring Connections: Screw terminals for use with 16 to 22 AWG wire.

Transducer Outputs

Output Signal: 3 to 15 psig (21 to 103 kPa) nominal, Direct Acting.
Maximum Pneumatic Output: 1 to 18 psig (7 to 124 kPa).
Output Air Capacity & Pressure: 515 scim (141 ml/s) maximum with a 20 psig (138 kPa) 
supply.
Operating Characteristics:

Linearity, ±1% of span @ 75°F (24° C).
Hysteresis, 0.75% of span @ 75°F (24° C).

Adjustments:

CP-8551, None.
CP-8552,

4 to 20 mA Range None.
0 to 10 and 6 to 9 V Range Adjustable start point and span potentiometers.

Environment

Ambient Temperature Limits:

Shipping and Storage, -40 to 160°F (-40 to 71° C).
Operating, 32 to 140°F (0 to 60° C).

Humidity: 5 to 95% R.H., non-condensing.
Locations: NEMA Type 1.
Agency Listings:

UL 873: Underwriters Laboratories (File #E9429 Category Temperature-Indicating and 
Regulating Equipment).
CSA: Certified for use in Canada by Underwriters Laboratories. Canadian Standards 
C22.2 No. 24-93.
European Community: EMC Directive (89/336/EEC). Low Voltage Directive 
(72/23/EEC).

Accessories

AL-3X2

Pressure gauge.

K-335

In-line air filter.

B-371

Branch tee.

M-127

90° drop ear elbow.

M-636

4 in. T and B wire tie.

P-610

35 mm DIN rail (1-3/8 W x 36 L x 3/10 H in).

Note: Order the AL-3X2 Pressure Gauge, the B-371 Branch Tee, and the M-127 90° 
Drop Ear Elbow separately and field assemble to provide optional pressure indication for 
the CP-8551 and CP-8552 transducers.

Summary of Contents for CP-8551

Page 1: ...il mounting for quick snap on installation Two wire loop powered or three wire voltage input High accuracy with low hysteresis Long term driftless operation with high repeatability Low air consumption...

Page 2: ...Acting Maximum Pneumatic Output 1 to 18 psig 7 to 124 kPa Output Air Capacity Pressure 515 scim 141 ml s maximum with a 20 psig 138 kPa supply Operating Characteristics Linearity 1 of span 75 F 24 C...

Page 3: ...screws not provided M 636 4 in T and B wire tie not provided Training Installer must be a qualified experienced technician CP 8551 M B M 3 to 15 psig 21 to 103 kPa to controlled device direct acting...

Page 4: ...marily to provide a degree of protection against contact with the enclosed equipment Do not locate unit in areas subject to incidental contact vibration severe mechanical shock excessive moisture or c...

Page 5: ...per selection as follows 1 Choose input range 2 Consult Table 1 for jumper position 3 Place jumper over square posts on appropriate lettered block Figure 4 4 Calibrate by performing appropriate CHECKO...

Page 6: ...unction 2 Verify that the unit is mounted upright and wired correctly 3 Verify that 20 psig 138 kPa main air is present 4 Verify with a digital multimeter that a 4 to 20 mAdc signal is present and of...

Page 7: ...gnal to bottom of range 0 or 6 V 7 Branch pressure should be 3 psig 21 kPa If not adjust start point potentiometer Figure 4 to obtain a 3 psig 21 kPa output 8 Adjust input to top of range 9 or 10 V 9...

Page 8: ...marks and registered trademarks are the property of their respective owners Information contained within this document is subject to change without notice F 26159 5 www tac com TAC 1354 Clifford Avenu...

Reviews: