BACnet Interoperability
Building Blocks Supported
(Annex K)
BACnet Standard Object
Types Supported
No dynamic Creation or Deletion supported. Objects, and object instances, are assigned to fixed
functions within the proprietary control application of the product as follows
Application Service
Initiate
Execute
BIBB
ReadProperty
Yes
DS-RP-B
ReadPropertyMultiple
Yes
DS-RPM-B
WriteProperty
Yes
DS-WP-B
ReinitializeDevice
Yes
Who-Is
Yes
DM-DDB-B
I-Am
Yes
Who-Has
Yes
DM-DOB-B
I-Have
Yes
DeviceCommunicationControl
Yes
DM-DCC-B
TimeSynhronisation
Yes
DM-TS-B
Object
Number Of
Instances
Instance Assignments
Device Object
1
Analog Input
5
AI(0) – Sensor 3 (Built-In Sensor)
AI(1) - Setpoint (Calculated)
AI(2) - Humidity Measurement
AI(3) – Sensor 1 (RI1)
AI(4) – Sensor 2 (RI2)
Analogue Value
5
AV(0) - Nominal Setpoint
AV(1) - Sensor 1 Temp
AV(2) - Sensor 2 Temp
AV(3) - Sensor 3 Temp
AV(4) - Brightness
Binary Input
4
BI(0) – Digital Input (DI1)
BI(1) – Boost (Party Mode) Status
BI(2) – Schedule Status (only SRI-P70)
BI(3) – Time Lost (only SRI-P70)
Binary Output
8
BO(0) – Relay
BO(1) - OFF Status
*1
BO(2) - ECO Status
"1
BO(3) – Lights
*2
BO(4) – AC
*2
BO(5) – Lock
*1
BO(6) – Frost Icon
BO(7) - Non Volatile Update (updates
setpoints/configuration parameters)
MutliState Input
3
MSI(0) - Device Mode (1=Comfort,
3=OFF, 4=Boost)
MSI(1) - Alarm (Add 1 to to bit values)
Bit 0 - Internal NTC (1)
Bit 1 - RI1 (2)
Bit 2 - RI2 (4)
Bit 3 - Humidity Sensor (8)
Bit 4 - DI1 (16)
Bit 5 - DI2 (Not Applicable)
Bit 6 - Time Lost (64)
MSI(2) - Mode Icon Status (1=Auto,
2=Heating, 3=Cooling, 4=Fan)
MSI(3) - Fan Speed Status 1..7
(corresponding speeds 0..6)
*4
MutliState Value
3
MSV(0) - Set Ring Colour (1-White,
2=Red, 3=Blue, 4=Green, 5=Orange,
6=Yellow, 7=Magnenta, 8=Cyan,
9=Sensor1, 10=Sensor2, 11=Sensor3)
MSV(1) - Set Mode Icon (1=Auto,
2=Heating, 3=Cooling, 4=Fan, 5=None)
*3
MSV(2) - Auto Fan Speed 1..7
(corresponding speeds 0..6)
*4