8 - Technical Data (continued)
WQL/WQH/WQRC
50
60
75
90
120
150
170
190
Rated voltage
V/ph/Hz
400 (± 10%) / 3 / 50
Max. absorbed power
kW
20,6
25,4
30,8
34,8
47,7
59,9
65,4
70,8
Rated current
A
25,4
30,6
33,2
41,0
53,3
71,7
73,6
75,6
Max. current FLA
A
50,0
54,0
66,0
77,2
102,0
130,0
144,0
158,0
Max. start-up current LRA
A
135,0
167,0
191,0
235,6
266,0
325,0
385,0
399,0
External fuses
A
80
80
100
100
160
160
200
200
Max. cable section
(*)
mm
2
25
25
35
35
70
70
95
95
WQL/WQH/WQRC
20
25
30
35
40
45
Rated voltage
V/ph/Hz
400 (± 10%) / 3 / 50
Max. absorbed power
kW
8,3
10,2
12,0
13,5
14,8
17,1
Rated current
A
9,3
11,8
12,9
13,9
16,0
20,7
Max. current FLA
A
15,0
21,0
22,0
25,0
31,0
34,0
Max. start-up current LRA
A
101,0
111,0
118,0
118,0
140,0
174,0
External fuses
A
25
25
32
32
40
40
Max. cable section
(*)
mm
2
6
6
10
10
10
10
(*)
The dimensioning of the unit's power cables is the responsibility of the installer, who shall consider: the rating, the maximum working temperature in the room,
the type of insulation and the cable laying, the maximum length of the power supply line.