11
4.4.3
External connections
Terminal block
Description (GB)
Remark
PE
Ground
N
N
Earthed neutral (supply voltage)
L1
L1
Phase (supply voltage)
Used for phase 230V 1~ if the unit
has this mains power supply
400V 3~
L2
L2
Phase (supply voltage)
400V 3~
L3
L3
Phase (supply voltage)
400V 3~
1
G
Mains power supply (Water valve actuator)
24V AC
2
G0
Reference (Water valve actuator)
24V AC
10
DO ref
DO reference
G (24V AC)
12
1
DO 2
Outdoor/Exhaust air damper
24V AC
Max. 2,0 A continuous load
WP
L1
Circulation pump hot water system
230V AC
DO 3
Activate cooling
DO 4
Sum alarm
24 VAC
D0 5
Start external extract fan
24 VAC
30
AI ref
Supply air sensor reference
Neutral
31
AI 1
Sensor supply air
40
Agnd
UI reference
Neutral
41
2
UAI 1/(UDI 1)
Pressure transmitter extract air
UAI 2/(UDI 2)
Pressure transmitter supply air
44
UAI 3/(UDI 3)
Frost protection sensor water heating battery
Use terminal 40 as reference
4
3
DI ref
External function reference
+ 24V DC
50/60/B
B
Exo-line B
Modbus, Exo-line connection
51/61/A
A
Exo-line A
Modbus, Exo-line connection
52/62
N
Exo-line N
Modbus, Exo-line connection
DI 4
Extended running
Normally open contact
Use terminal 4 as reference
DI 5
Fire alarm
Normally open contact
Use terminal 4 as reference
DI 6
External stop
Normally open contact
Use terminal 4 as reference
90
Agnd
AO Reference
Neutral
91
AO 1
Control signal, water heating
0–10V DC
93
AO 3
Control signal, cooling
0–10V DC
94
A0 4
Control signal, external extract fan (optional)
chapter 4.4.5
0-10V DC
1
Maximum current load for all DO combined: 8A
2
Connection to external pressure sensor in case of pressure controlled unit (VAV)
3
These inputs may only be wired to voltage free contacts
130324 | A004