Topvex Series
HWC - Hot Water Coil,
ELP - Electric Pre-Heater installation instructions
Systemair Inc.
4
5
Replace the cover plate and fasten it with 2 screws
(pos. 1).
3
Connect the water piping to the coil connections.
Cover plates around the pipes are fixed to the unit
(reinforcement).
The arrows in the figure display how the hot water
should be connected to the coil. Connect the hot
water inlet to position 1 and the return water to
position 2.
Connect the frost protection sensor (pos. 3) to
terminals 44 and 40 in the electrical connection box.
Use the prepared internal lead through to draw the
wiring between the compartments.
4
Connect all necessary accessories such as water valves and valve actuators. See enclosed wiring diagram
for more information
Important
Take care not to damage the water coil when
connecting water pipes to connectors.
1 Warnings
The following admonitions will be presented in the different sections of the document.
Danger
• Make sure that the Mains supply to the unit is disconnected before performing any maintenance or
electrical work!
• All electrical connections must be carried out in accordance with local rules and regulations.
Warning
• In order for the unit to be considered safely installed the doors if equipped with handles have to be
locked with a key to prevent unauthorized or accidental opening
• The unit must be duct connected or in some other way provided with protection so that it is not
possible to come in contact with the fans through the duct connections
• The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
protective clothing.
• Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is
used. Use protective clothing.
Caution
• If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
• Duct connections/duct ends should be covered during storage and installation
• Do not connect tumble dryers to the ventilation system
• Take care not to damage the water battery when connecting water pipes to connectors. Use a
spanner to tighten the connection.
Topvex FR03, FR06, FR08, and FR11
Installation instructions
206638
1
Systemair AB
2
1