7.2
Wiring diagram
prio
Air EC
Client side
max. speed
adjustable speed
10 V
n = max
1 V
n = min
<1 V
n = 0
adjustable speed through
PWM 1 ... 10 KHz
adjustable speed through
potentiometer
100 % PWM
n = max
10 % PWM
n = min
<10 % PWM
n = 0
Fig. 6: Wiring diagram of the prio 160 EC + prio 200 EC
Wire no.
Connection
Colour
Function/assignment
1
PE
green/yellow
Protective conductor
2
L
brown
Power supply 230 V AC, 50 ... 60 Hz, see type plate for voltage range
3
N
blue
Neutral conductor
4
GND
blue
GND-connection of the controller interface
5
speedometer
white
Speed output: Open Collector, 1 impulse per revolution, electrically isolated,
Isink_max = 10 mA
6
10 V / max. 1.1 mA
red
Voltage output 10 V / 1.1 mA, electrically isolated
7
0 ... 10 V PWM
yellow
Controller input 0 ... 10 V or PWM, electrically isolated
7.1
Wiring diagram
prio
Air E2
Color
Function/pin assignment
blue
L
Power supply 230 V AC, 50 ... 60 Hz
black
N
Neutral conductor
green/
yellow
PE
Protective conductor
Fig. 5: Wiring diagram of the prio 160 E2 + prio 200 E2
28
Electrical connection
Summary of Contents for prio 160 E2
Page 50: ...50 Systemair GmbH...
Page 52: ...52 1 1 1 ATTENTION 1 1 1 1 1 2 1 2 3 1 2 prioAir...
Page 54: ...54 2 4 prioAir 3 4 4 1 prioAir prioAir 4 2 prioAir...
Page 55: ...55 prioAir 07 2014 4 3 1 prioAir 5 5 1 prioAir EC prioAir E2 EN 13779 EC...
Page 56: ...56 5 1 1 5 4 3 1 2 2 prio 200 EC 1 4 2 5 3 6 7 3 4 1 5 2 3 prio 200 E2 1 5 2 6 3 7 4...
Page 59: ...59 prioAir 07 2014 6 3 1 7 5 prioAir E2 4 prioAir E 5 1 Befestigungswinkel...
Page 62: ...62 10 5 10 1 Systemair Systemair Systemair Systemair 2 9 3...
Page 63: ...63 prioAir 07 2014 10 2 5 10 3 Systemair 10 4...
Page 64: ...64 11 5 12 12 1 12 2...