6. Inspection of the proper fire damper closure
7. Inspection of the damper's functionality – opening and closing using the control system, physical examination of
the damper’s behavior, possible correction and logging (where needed)
8. Inspection of the end switches’ functionality in the open and closed position, possible correction and logging
(where needed)
9. Inspection of whether the damper is fulfilling its role as part of the regulation system (where needed)
10. Inspection of whether the damper remains in its standard operating position.
11. The damper is usually part of a system. In such case, the whole system needs to be checked as described in its
operation requirements published by the builder of the system.
Supplement
Any deviations from the technical specifications contained in SystemairDESIGN and the terms should be discussed with
the manufacturer. We reserve the right to make any changes to the product without prior notice, provided that these
changes do not affect the quality of the product and the required parameters.