31/49 |
F-R60
Electrical Connections
IMPORTANT
• Danger of electric shock!
• Switch off the power supply before working on any electrical equipment.
• Only qualified electricians are permitted to work on the electrical system.
Electrical Parameters per Activation and Actuator Type
A
DN (mm)
100
125
140
150
160
180
200
225
250
280
315
355
400
Belimo BFL… / Gruner 340TA-…-05
Actuator Size Map of F-R60
AT
A
T
(Nm)
NV
(V)
F
(Hz)
CO
CR
WS
(VA)
WN
(W)
H0, H2 -
-
DC 12/24
AC 150/250
50/60
-
-
-
3A
B230T
BFL230-T
4
AC 230
3,5
1,1
6,5
Imax 4 A @ 5 ms
G230T 340TA-230-…-05-…
5
AC 230
5,5
2
9,5
-
BST0
BFL24-T-ST & BKN230-24
4
AC 230
10
3,5
11
Imax 4 A @ 5 ms
GST0
340TA-24-…-05-.../ST01
& FSC-UFC24-2
5
AC/DC 24
8,5
4
11
-
B24T,
B24T-W
BFL24-T, BFL24-T-ST
4
AC/DC 24
2,5
0,8
4
Imax 8,3 A @ 5 ms
G24T,
G24T-W
340TA-24-…-05-...
340TA-24-…-05-.../ST01
5
AC/DC 24
6,5
2
9
-
B24T-SR BFL24-SR-T
4
AC/DC 24
3
1
6,5
Imax 8,3 A @ 5 ms
G24T-SR 340CTA-24-…-05-…
5
AC/DC 24
6,5
2
7,5
DC (0)2 V ...10 V /
Ri > (100 kΩ)
50 kΩ (0)4 ... 20 mA
Notes
AT
- Activation type
A
- Belimo Actuator type
T
- Torque
NV
- Nominal Voltage
F
- Frequency
CO
- Consumption in Operation
CR
- Consumption in Rest
WS
- Wire sizing consumption
WS
- Wire sizing consumption Note