9
STANDARD
The fan is operated using a separate ON/OFF switch or via a light switch (fig. 14A).
WITH TIMER (over-run)
The fan is provided with a timer circuit which is adjustable from aprox. 1 minute to 25
minutes via trimmer (fig. 15B).
Operation: connected according to the diagram in fig. 14B, after the light is switched on,
the fan activates with a delay of max 1.5 seconds. After the light is switched off, the fan
continues to function for a pre-set period of time.
WITH HUMIDISTAT & TIMER
The fan is equipped with a humidity detector, whose threshold is adjustable from 50% to
95% Relative Humidity, and with a timer which is adjustable from aprox. 1 minute to 25
minutes via corresponding trimmer (fig. 15D).
Turn the trimmer HY completely clockwise and the humidistat function is deactivated.
Automatic humidistat operation: connected according to the diagram in fig. 14D, when
the percentage of Relative Humidity exceeds the pre-set intervention threshold, the
fan starts up automatically. When the percentage of Relative Humidity goes below the
threshold, the fan continues to function for a pre-set period of time.
Operation with switch connection: connected according to the diagram in fig. 14D, after
the light is switched on, the fan activates with a delay of aprox. 1.5 seconds. After it is
switched off, the fan continues to function for a pre-set period of time.
Attention
: When the relative humidity level is higher than the pre-set threshold,
automatic operation with humidistat has priority over manual operation, or rather the fan
cannot be stopped via switch.
VERSIONS