Assembly

NOTE

The safety information in Section 6 applies to all the fans described in these operating instructions.

6.1 

Safety information

Keep to the following order in order to rule out the risk of injuries from rotating parts:
Assemble
Connect to energy

HAZARD

Hazard of explosion of an ignition-capable atmosphere!

On the intake side, a protective grid has been attached in order to rule out the risk from foreign bodies. 

It guarantees a protection class of IP20.
On the pressure side, protection class IP 20 must be guaranteed by assembly of the fan in a duct/
channel system or by fitting a protective grid. 

• 

Seal the system carefully.

• 

Install accessory parts correctly.

Upstream or downstream components or those located directly in the air flow may not manifest any 

unprotected aluminium or steel surfaces. Varnishing or a plastic coating fulfilling at least grid section 
characteristic 2 according to DIN EN ISO 2409 is necessary, in order to prevent an alumino-thermal 

reaction.

• 

Assembly may only be done by trained qualified personnel paying attention to the relevant directives.

• 

Comply with the system-related conditions and the requirements of the system manufacturer or plant builder.

• 

Only install the fan when and if

 

the fan has not been damaged,

 

the fan wheel runs freely when turned by hand.

• 

The fan housing may not be deformed during assembly.

• 

Safety components, e.g. protective grids, may not be dismantled or circumvented or put out of function.

• 

Install the fan with protection against dust, moisture and the influences of the weather.

• 

Do not distort the fan housing in installation. Surfaces must be flat.

• 

Pay attention to the direction of flow (arrows).

• 

For maintenance and repair, ensure secure access to the fan.

• 

Provide for contact, intake protection and safety distances according to DIN EN 294 and DIN 24167-1.

• 

Ensure uninhibited and even admission into the device and free blow-out.

• 

In EX fans, the blade angle may not be amended subsequently.

• 

In installation, guarantee that no vibrations are transferred to the duct/channel system or the housing frame of the 

fan in operation. For this purpose, use connecting sleeves and flanges from the accessories.

6.2 

Axial fans AW-EX, AXC-EX and AXCBF-EX

6.2.1  Preconditions 

AW-EX

Only install the fan if the distance between the fan wheel and the housing is constant.

AXC-EX and 

AXCBF-EX

Only install the fan if the minimum air gap between the blade tip and the housing matches the 

value of your fan in Table 11.

  

Assembly

55

 

Summary of Contents for AW-EX Series

Page 1: ...d Operating Instructions Anvisningar f r montering och drift Instrukcja obs ugi i monta u EX Ventilatoren EX Fans Ventilatoren f r den Einsatz in explosionsgef hrdeten Bereichen Fans for use in area i...

Page 2: ...nformation shown in the work area concerning personal protective equipment Wear protective gloves in work to which specific reference is made in these instructions 2 5 Safety devices An internal therm...

Page 3: ...rotor or the admission nozzle Transport the EX fan carefully and with suitable lifting equipment Transport the EX fan either in the original packaging or the transport attachments provided for this pu...

Page 4: ...ation e increased safety nA not sparking IIB Groups T3 Temperature class Gb EPL Equipment Protection Level Sira 07ATEX6341X EC type test certificate number Table 1 Identification Designation Device gr...

Page 5: ...B Hydrogen Temperature class T1 T2 T3 T4 450 C 300 C 200 C 135 C I Methane IIA Acetone Ammoniac Methane Methanol Propane Toluene IIB Town gas IIC Hydrogen IIA Ethyl alcohol n Butane IIB Ethylene IIC...

Page 6: ...al fan series 5 4 1 Types AW 355 D4 2 EX AW 420 D4 2 EX AW 550 D6 2 EX AW 650 D6 2 EX 5 4 2 Description Ignition protection class Ex e increased safety Motor protection by posistor in combination with...

Page 7: ...4 poled variable motor S 6 6 poled variable motor 4 4 4 poled 6 6 6 poled 2 Mechanical version EX Explosion protected fan Table 5 Type key of the AW EX series 5 4 4 Name plate example 1 2 3 4 5 6 7 F...

Page 8: ...om 20 C to max 60 C see Table 6 AXC EX supplied with Ex e connection box on the outside of the housing AXCBF EX motor outside the air flow The divided medium pressure axial fans of the AXCBF EX AXC EX...

Page 9: ...9 10 Fig 3 Fans of the AXCBF EX AXC EX series with accessories Legende 1 SG Protection guard 6 MP 4x angle 90 Mounting brackets up to size 1000 2 ESD F Inlet cone 7 LRK Air operated damper 3 RSA Silen...

Page 10: ...w systemair de Ref Nr Typ Nr P2 kW P2 kW H chst kW H chst kW Ampere Ampere 26 2011 50 400 3 2890 Winkel Baujahr Hz Volt Phase U min U min AXC EX 500 9 26 2 5 50 5 10 12 0820 II 2G c Ex d e IIC T4 Sira...

Page 11: ...better quality Das Vervielf ltigen dieser Zeichnung und Mitteilen an dritte ist Verboten F r diese Zeichnung behalten wir uns alle Rechte gem Urheberschutz vor Zuwiderhandlungen werden verfolgt SYSTE...

Page 12: ...8 Type key of the RVK EX series 5 6 4 Name plate example 1 Manufacturer s information 2 Type designation 3 Voltage frequency current date 4 Current motor insulation class 5 Output protection class 6 S...

Page 13: ...l rotor of the vertical blow out DVEX roof fans has backward bent rotor blades Its housing comprises saltwa ter proof aluminium The base frame and an integrated bird protection grid are on powder coat...

Page 14: ...speed 4 Trigger time starting nominal current insula tion class motor 5 Speed variation 6 Type test certification for U EK230E motor pro tection device 7 Identification to ATEX 8 EC type test certifi...

Page 15: ...e requirements of the system manufacturer or plant builder Only install the fan when and if the fan has not been damaged the fan wheel runs freely when turned by hand The fan housing may not be deform...

Page 16: ...n cannot escape Installation and operation only admissible in a horizontal shaft position NOTE for an optimised characteristic To ensure achievement of the characteristic it is necessary for a constan...

Page 17: ...Current dependent protection is not admissible and also not possible as secondary protection 6 3 2 Assembly Use the enclosed holding clamps Screw the holding clamps tight by hand NOTE If the cable gla...

Page 18: ...ng Fit the air connection lines and the accessories NOTE The channel installation must be such that protection class IP 20 contact distance rotating part 12 mm is fulfilled on the admission side and p...

Page 19: ...d short circuit cover or fence off neighbouring live parts Do not use gland bolt connections of metal if the terminal boxes are of plastic Always connect the thermo contacts to a motor protection devi...

Page 20: ...data sheet Ex motors additionally have a marked external earth conductor connection Earth the fan on the earth conductor connection If there is an increased risk of static charge a separate earthing...

Page 21: ...position and arrangement of the condensation bores match DVEX series Voltage tolerances according to IEC 38 with a maximum of 6 or 10 are complied with Nominal current does not exceed the nominal vol...

Page 22: ...m bursting parts Wear goggles when checking the direction of rotation of the rotor Briefly switch the fan on and off Check the direction of rotation direction of conveying The direction of rotation lo...

Page 23: ...circumvented or put out of function Only operate the EX fan within the limits stated on the name plate Intake of foreign bodies can destroy the fan Switching frequency The EX fan has been admitted fo...

Page 24: ...t switching on again establish freedom from voltage earth and short circuit cover or fence off neighbouring live parts 10 1 Maintenance intervals Carry out maintenance at least twice a year We recomme...

Page 25: ...to a great extent After the end of the period of use for the grease about 30 000 to 40 000 h in standard applications replacement of the bea rings is necessary WARNING Risk from electrical voltage In...

Page 26: ...direction of rotation of rotor Change direction of rotation Loss of pressure in lines too high Different line guidance Throttle organs not or only partly open Check opening position on site Intake or...

Page 27: ...cts and cutting Wear protective gloves when dismantling Dismantle carefully Remove the fitting material carefully Place the EX fan on the floor 12 Disposal Both the device and the matching transport p...

Page 28: ...Systemair GmbH Seeh fer Str 45 D 97944 Boxberg Tel 49 0 7930 9272 0 Fax 49 0 7930 9273 92 info systemair de www systemair de imo_ATEX_160324_de en se ru pl_003_312435...

Reviews: