3.4
Storage
•
The device must be stored in its original packaging in a dry and weather-proof room.
•
Avoid exposure to extreme heat and cold.
•
Avoid over-long storage periods (we recommend a maximum of one year).
3.5
Disposal / recycling
Disposal must be carried out professionally and environmentally friendly in accordance with the legal
stipulations.
4
Mounting
4.1
General notes
Attention!
The following points must be complied with during the mechanical installation to avoid causing a defect
in the device due to assembly errors or environmental in
fl
uences:
•
Before installation remove the device from the packing and check for any possible shipping
damage!
•
Assemble the device on a clean and stable base. Do not distort during assembly! Use the
appropriate mounting devices for proper installation of the unit!
•
Do not mount equipment on vibrating base!
•
When mounted onto lightweight walls, there must be no impermissibly high vibrations or shock
loads. Any banging shut of doors that are integrated into these lightweight walls, can result in
extremely high shock loads. Therefore, we advise you to decouple the devices from the wall.
•
Do not allow drilling chips, screws and other foreign bodies to reach the device interior!
•
The device should be installed in a location where it will not be disturbed, but at the same time
can be easily accessed!
•
Depending on the housing model use supplied stoppers for cable inlets, cut off necessary cable
inlets respectively to the cable diameter. Or alternative use cable inlet for cable glands. Any
cable ducts openings not used must be sealed!
•
Care must be taken to avoid direct radiation from the sun!
•
The device is designed for vertical installation (cable inlet down). A horizontal or reclined
installation is only permissible after technical release of the manufacturer!
•
Be sure to observe proper heat dissipation (
Technical data, heat dissipation).
4.2
Minimum space requirement
In order to ensure suf
fi
cient ventilation of the device, clearance on all sides of at least 50 mm has to
be maintained to the housing walls, switch cabinet doors, wiring ducts, etc. The same clearance
applies to the installation of several devices next to each other.
When installing several devices on top of each other, the danger of reciprocal heating exists. This
layout is only then permissible when the air suctioned from the upper unit does not become warmer
than the permissible ambient temperature (
Technical data). I.e., a correspondingly larger clearance
or thermal shielding is required.
4.3
Outdoor installation
Outdoor installation is possible up to -20
°
C when the controller supply is not switched off. Installation
must be protected from the effects of weather as much as possible, including protection from direct
sunlight!
Operating Instructions
RETP6 / RETP10
Mounting
L-BAL-E082-GB 1237 Index 002
Part.-No. 00163339-GB
7/31