DH100ACDCP Air Duct Smoke Detector

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing

Please thoroughly read the System Sensor 

Guide for Proper 

Use  of  Smoke  Detectors  in  Duct  Applications 

(A05-1004)

,

 

which  provides  detailed  information  on  detector  spacing, 
placement, zoning, wiring, and special applications. Copies 
of  this  manual  are  available  from  System  Sensor.  NFPA 
Standards 72 and 90A should also be referenced for detailed 
information. 

NOTICE:

 This manual shall be left with the owner/user of 

this equipment.

IMPORTANT:

 This detector must be tested and maintained 

regularly  following  NFPA  72  requirements.  The  detector 
should be cleaned at least once a year.

Table of Contents                                                 Page

[1] General Description                                                  1
[2] Limitations of Duct Smoke Detectors                          1
[3] Exploded View of Duct Smoke Detector Components  2
[4] Contents of the Duct Smoke Detector Kit                    2
[5] Installation Sequence                                                 2
[6] Duct Smoke Detector Maintenance and Test Procedures 5
[7] Detector Cleaning Procedures                                     7
[8] Board Replacement                                                    8
[9] Specifications                                                            8
Warranty                                                                        8

[1] General Description

An HVAC system supplies conditioned air to virtually every 
area of a building. Smoke introduced into this air duct sys-
tem will be distributed to the entire building. Smoke detec-
tors designed for use in air duct systems are used to sense 
the presence of smoke in the duct. 

Model  DH100ACDCP  Air  Duct  Smoke  Detector  utilizes 
photoelectric  technology  for  the  detection  of  smoke.  This 
detection method, when combined with an efficient hous-
ing design, samples air passing through the duct and allows 
detection of a developing hazardous condition. When suf-
ficient smoke is sensed, an alarm signal is initiated at the 
fire control panel monitoring the detector, and appropriate 
action can be taken to shut off fans, blowers, change over 
air handling systems, etc. These actions can facilitate the 
management of toxic smoke and fire gases throughout the 
areas served by the duct system.

The  DH100ACDCP  detector  is  designed  to  operate  on 
24  VDC/VAC,  120  VAC,  or  240  VAC.  Alarm  and  supervi-
sory relay contacts are available for control panel interface 
(alarm initiation), HVAC control, and other auxiliary func-
tions. Auxiliary relays are also provided for fan shut down 

or signaling of up to 9 other detectors in the loop for mul-
tiple  fan  shut  down.  These  detectors  are  not  designed  for 
2-wire applications.

For testing, the alarm can be enabled by a magnet activated 
test switch or by the optional remote test station. The duct 
smoke  detector  latches  into  alarm  state  when  an  alarm 
occurs. A green LED flashes to indicate power, a red LED 
signals  local  alarm  indication,  and  optional  accessories 
offer a variety of annunciation capabilities.

The  DH100ACDCP  can  be  reset  by  a  momentary  power 
interruption, the reset button on the front cover, the control 
panel, or remote reset accessory. 

The DH100ACDCP incor-

porates  a  cover  tamper  feature  that  provides  a  trouble 
signal after 7 minutes if the cover is removed or improp-
erly installed.

 Proper installation of the cover removes the 

trouble condition.

[2] Limitations Of Duct Smoke Detectors 

WARNING

The  National  Fire  Protection  Association  has  established 
that  DUCT  DETECTORS  MUST  NOT  BE  USED  AS  A 
SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION 
as a means of providing life safety. Nor are they a substi-
tute for early warning in a building’s regular fire detection 
system.
System  Sensor  supports  this  position  and  strongly  recom-
mends that the user read NFPA Standards 90A, 72, and 101. 
The DH100ACDCP Air Duct Smoke Detectors are listed per 
UL 268A.

WARNING

This device will not operate without electrical power. Fire 
situations may cause an interruption of power. The system 
safeguards should be discussed with your local fire protec-
tion specialist.

WARNING

This  device  will  not  sense  smoke  unless  the  ventilation 
system is operating and the cover is installed.

WARNING

For this detector to function properly, it MUST be installed 
according to the instructions in this manual. Furthermore, 
the  detector  MUST  be  protected  from  the  elements  and 
operated within ALL electrical and environmental specifi-
cations listed in this manual. Failure to comply with these 
requirements  may  prevent  the  detector  from  activating 
when smoke is present in the air duct.

Summary of Contents for INNOVAIR DH100ACDCP

Page 1: ...esigned to operate on 24 VDC VAC 120 VAC or 240 VAC Alarm and supervi sory relay contacts are available for control panel interface alarm initiation HVAC control and other auxiliary func tions Auxilia...

Page 2: ...Holes Remove the paper backing from the mounting template supplied Affix the template to the duct at the desired mounting location Make sure the template lies flat and smooth on the duct Center punch...

Page 3: ...the end opposite the duct smoke detector 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrows point into the air flow 3 Secure the tube flange...

Page 4: ...air flow in the duct is 10 to 12 Space the additional holes as evenly as possible over the length of the tube NOTE This procedure should only be used as a temporary fix It is not intended as a perman...

Page 5: ...ick or punk directly at the head to cause an alarm REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST OR THE DETECTOR WILL NOT FUNCTION PROPERLY 6 1 3 Filter Replacement The filters do not substantially aff...

Page 6: ...CONTACT MANUFACTURER NOTE THE SUPERVISORY RELAY NOW PROVIDES A FORM C CONTACT FOR CUSTOMIZED APPLICATIONS FOR STANDARD APPLICATIONS ONLY THE NO CONTACT IS USED POWER INPUTS ACCEPT 24 VDC 24 VAC 50 60...

Page 7: ...s in the alarm state TROUBLE n a n a n a n a 9mA Max D100 68 00 7 I56 1147 12R 6 2 3 Sensitivity Tests 6 2 3 1 MOD400 or MOD400R Test After verification of alarm capability use the MOD400R test module...

Page 8: ...n 2 0 VAC min 10 VAC min 20 VAC min Reset time with RTS451 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec Reset time by power down 0 6 sec max 0 6 sec max 0 6 sec max 0 6 sec max Power up tim...