background image

D100-68-00                                                                                               8                                                                                            I56-1147-12R

Three-Year Limited Warranty

System  Sensor  warrants  its  enclosed  air  duct  smoke  detector  to  be  free 

from  defects  in  materials  and  workmanship  under  normal  use  and  ser-

vice for a period of three years from date of manufacture. System Sensor 

makes  no  other  express  warranty  for  this  air  duct  smoke  detector.  No 

agent, representative, dealer, or employee of the Company has the author-

ity to increase or alter the obligations or limitations of this Warranty. The 

Company’s  obligation  of  this  Warranty  shall  be  limited  to  the  repair  or 

replacement of any part of the air duct smoke detector which is found to 

be defective in materials or workmanship under normal use and service 

during the three year period commencing with the date of manufacture. 

After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) 

for a Return Authorization number, send defective units postage prepaid 

to:  System  Sensor,  Returns  Department,  RA  #__________,  3825  Ohio 

Avenue, St. Charles, IL 60174. Please include a note describing the mal-

function and suspected cause of failure. The Company shall not be obli-

gated to repair or replace units which are found to be defective because 

of  damage,  unreasonable  use,  modifications,  or  alterations  occurring 

after the date of manufacture. In no case shall the Company be liable for 

any consequential or incidental damages for breach of this or any other 

Warranty, expressed or implied whatsoever, even if the loss or damage is 

caused by the Company’s negligence or fault. Some states do not allow 

the exclusion or limitation of incidental or consequential damages, so the 

above limitation or exclusion may not apply to you. This Warranty gives 

you specific legal rights, and you may also have other rights which vary 

from state to state.

[9] Model DH100ACDCP Air Duct Smoke Detector Specifications 

Temperature:                                 
    DH100ACDCP                            32° to 131° F                                     0° to 55° C
Storage Temperature:                      –22° to 150° F                                   –30° to 70° C
Humidity:                                      10% to 93% R.H. noncondensing
Air Velocity:                                   500 to 4000 ft./min.                            2.5 to 20.3 m/sec.
Dimensions:                                   14.38

 L x 5.5

 W x  2.75

 D               37cm L x 14cm W x 7cm D 

 

Weight:                                          3.75 pounds                                       1.7 kg

Electrical Specifications

Power supply voltage:                   20-29 VDC         24 VAC 50-60-Hz       120 VAC 50-60 Hz    220/240 VAC 50-60 Hz
Input capacitance:                        270 µF max.            270 µF max.                     N/A                            N/A
Reset voltage:                              3.0 VDC min.           2.0 VAC min.             10 VAC min.                20 VAC min.
Reset time (with RTS451):            .03 to 0.3 sec.         .03 to 0.3 sec.             .03 to 0.3 sec.              .03 to 0.3 sec.
Reset time (by power down):       0.6 sec. max.           0.6 sec. max.              0.6 sec. max.                0.6 sec. max.
Power up time:                             34 sec. max.           34 sec. max.               34 sec. max.                34 sec. max.
Alarm response time:                   2 to 17 sec.             2 to 17 sec.                2 to 17 sec.                  2 to 17 sec.
Sensitivity Test:                        See detector label   See detector label        See detector label        See detector label

[7.3] Ion Detector Boards 

1. Brush  or  vacuum  inside  area  of  cover.  Chamber  may 

then be blown out using clean, compressed air. 

2. Vacuum sensing chamber before using clean, compressed 

air to loosen and blow out any remaining debris. 

[8.0] Board Replacement
[8.1] Detector Board Replacement (Part No. A5190)

1.   Remove the two detector board mounting screws.
2.   Pull gently on the board to remove it. 
3.   To  replace  the  board,  align  the  board  mounting  fea-

tures, holes, and the interconnect terminals. Push the 

board into place.

4.   Secure board with the two mounting screws.

[8.2] Power Board replacement (Part No. A5064)

1.   Disconnect wiring from the terminal block.
2.   Remove the two power board mounting screws.
3.   Pull gently on the board to remove it. 
4.   To  replace  the  board,  align  the  board  mounting  fea-

tures, holes, and the interconnect terminals. Push the 
board into place.

5.   Secure board with the two mounting screws.
6.   Re-connect wiring to terminal block.

Power Supply Voltage

20 - 29 VDC

24 VAC 50 - 60 Hz

120 VAC 50 - 60 Hz

220/240 VAC 50 - 60 Hz

CURRENT REQUIREMENTS (USING NO ACCESSORIES)

Max. standby current

15 mA

35 mA RMS

25 mA RMS*

15 mA RMS*

Max. alarm current

70 mA

125 mA RMS

35 mA RMS*

25 mA RMS*

CONTACT RATINGS

Alarm initiation contacts (SPST)

2.0A @ 30 VDC (resistive)

Alarm auxiliary contacts (DPDT)

10A @ 30 VDC
10A @ 250 VAC

Trouble contacts (SPDT)

2.0A @ 30 VDC (resistive)
2.0A @ 125 VAC (resistive)

Note:

Alarm auxiliary contacts must switch 100 mA minimum at 5VDC. Alarm auxiliary contacts shall not be
connected to inititaing circuits of control panels. Use the alarm initiation contact for this purpose.

* NOTE: When a unit is powered at the 120VAC or 220/240VAC input, any 

combination of accessories may be used such that the given accessory loads are: 

60 mA or less in the standby state,

110 mA or less in the alarm state.

ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE
APA451
PA400
RA400Z
RTS451
RTS451KEY
SSK451

STANDBY
12.5mA Max.
0mA
0mA
0mA
12mA*
5mA Max.

ALARM
30mA Max.
15mA Max.
10mA Max.
7.5mA Max.
7.5mA Max.
30mA Max.

TROUBLE
n/a
n/a
n/a
n/a
n/a
9mA Max.

Please refer to insert for the Limitations of Fire Alarm Systems

Summary of Contents for INNOVAIR DH100ACDCP

Page 1: ...esigned to operate on 24 VDC VAC 120 VAC or 240 VAC Alarm and supervi sory relay contacts are available for control panel interface alarm initiation HVAC control and other auxiliary func tions Auxilia...

Page 2: ...Holes Remove the paper backing from the mounting template supplied Affix the template to the duct at the desired mounting location Make sure the template lies flat and smooth on the duct Center punch...

Page 3: ...the end opposite the duct smoke detector 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrows point into the air flow 3 Secure the tube flange...

Page 4: ...air flow in the duct is 10 to 12 Space the additional holes as evenly as possible over the length of the tube NOTE This procedure should only be used as a temporary fix It is not intended as a perman...

Page 5: ...ick or punk directly at the head to cause an alarm REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST OR THE DETECTOR WILL NOT FUNCTION PROPERLY 6 1 3 Filter Replacement The filters do not substantially aff...

Page 6: ...CONTACT MANUFACTURER NOTE THE SUPERVISORY RELAY NOW PROVIDES A FORM C CONTACT FOR CUSTOMIZED APPLICATIONS FOR STANDARD APPLICATIONS ONLY THE NO CONTACT IS USED POWER INPUTS ACCEPT 24 VDC 24 VAC 50 60...

Page 7: ...s in the alarm state TROUBLE n a n a n a n a 9mA Max D100 68 00 7 I56 1147 12R 6 2 3 Sensitivity Tests 6 2 3 1 MOD400 or MOD400R Test After verification of alarm capability use the MOD400R test module...

Page 8: ...n 2 0 VAC min 10 VAC min 20 VAC min Reset time with RTS451 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec Reset time by power down 0 6 sec max 0 6 sec max 0 6 sec max 0 6 sec max Power up tim...

Reviews: