System Sensor INNOVAIR DH100ACDCP Installation And Maintenance Instructions Manual Download Page 6

D100-68-00                                                                                               6                                                                                            I56-1147-12R

24V

120

VAC

220/240

VAC

9

10

A

B

C

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC.

16

6

17

7

18

8

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN

STANDBY. CONTACTS TRANSFER DURING

ALARM AS INDICATED BY THE ARROWS.

SUPERVISORY TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.

CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS

REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN 

CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.

24V

220/240

VAC

9

10

A

B

C

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC.

16

6

17

7

18

8

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN

STANDBY. CONTACTS TRANSFER DURING

ALARM AS INDICATED BY THE ARROWS.

SUPERVISORY  TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.

CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS

REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN 

CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.

14

3

3

14

4

5

ALARM

INITIATION

CONTACTS

CONTACTS SHOWN

OPEN IN STANDBY.

CONTACTS CLOSE

IN ALARM.

4

5

ALARM

INITIATION

CONTACTS

CONTACTS SHOWN

OPEN IN STANDBY.

CONTACTS CLOSE

IN ALARM.

ALARM

INITIATION

LOOP

UL LISTED 4-WIRE

CONTROL PANEL

FIRST DETECTOR IN THE LOOP

DH100ACDCP

LAST DETECTOR IN THE LOOP

DH100ACDCP

EOL RESISTOR

SPECIFIED BY

PANEL MANUFACTURER

CONNECT POWER SOURCE

TO APPROPRIATE TERMINALS

OF EACH DETECTOR. SEE

SPECIFICATIONS FOR

ADDITIONAL POWER SUPPLY

INFORMATION.

FOR WIRING OF AUXILIARY

DEVICES, REFER TO

MANUFACTURER'S

INSTALLATION INSTRUCTIONS

OR CONTACT MANUFACTURER.

NOTE:

 THE SUPERVISORY RELAY NOW

PROVIDES A "FORM C" CONTACT FOR

CUSTOMIZED APPLICATIONS.

FOR STANDARD APPLICATIONS, ONLY

THE "NO" CONTACT IS USED

POWER INPUTS ACCEPT

24 VDC, 24 VAC  50-60 HZ,

120 VAC 50-60 HZ, OR

220/240 VAC 50-60 HZ.

CONNECT POWER SOURCE

TO APPROPRIATE TERMINALS

OF EACH DETECTOR.      

AUX. CONTACT RATINGS

10A @ 30 VDC RESISTIVE

10A @ 250 VAC

100mA MINIMUM @ 5 VDC

NOT INTENDED FOR

CONNECTION TO CONTROL

PANELS.

TROUBLE CONTACT RATING

2.0 A @ 30 VDC resistive

2.0 A @ 125 VAC resistive

+

120

VAC

CAUTION

Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.

Figure 8. Wiring diagram for DH100ACDCP to APA451:

A78-2352-27

Figure 7. System wiring diagram for 4-wire duct smoke detectors:

��

��

��

��

������������

������������

����������

��������

������������

������ �������������������������������������������������

�������������������������������������������������������

�����

���������

�����

�����������
������

4-Wire Wiring to APA451

������

����������

Figure 9. Wiring diagram for DH100ACDCP to 
RTS451KEY and interconnect feature:

15

19

14

3

20

2

11

2

6

1

Alarm Signal

Aux. Power +

Sup. N. O.

Sup. COM

Aux. Power –

Reset

Test

(Red LED) Alarm

(Green LED)
Power

DH100ACDCP

RTS451/RTS451KEY

5

4

3

*

For RTS451KEY
only without a
control panel.

*

Important Interconnect Notes

•   When using the interconnect feature, all in-
    terconnected  units  must  be  powered  with 
    the same, independent supply.
•  Polarity must be maintained throughout the 
    interconnect wiring. Connect terminal 12 on 
    unit  1  to  terminal  12  on  unit  2  and  so  on. 
    Similarly, connect terminal 1 on unit 1 to ter-
    minal 1 on unit 2 and so on.

Figure 10. Multiple fan shutdown (interconnect):

1

6

12

16

A

B

C

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

1

6

12

16

A

B

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

DETECTOR 1

C

DETECTOR 2

1

6

12

16

A

B

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

C

DETECTOR 3

1

12

+

NEXT

DETECTOR

Summary of Contents for INNOVAIR DH100ACDCP

Page 1: ...esigned to operate on 24 VDC VAC 120 VAC or 240 VAC Alarm and supervi sory relay contacts are available for control panel interface alarm initiation HVAC control and other auxiliary func tions Auxilia...

Page 2: ...Holes Remove the paper backing from the mounting template supplied Affix the template to the duct at the desired mounting location Make sure the template lies flat and smooth on the duct Center punch...

Page 3: ...the end opposite the duct smoke detector 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrows point into the air flow 3 Secure the tube flange...

Page 4: ...air flow in the duct is 10 to 12 Space the additional holes as evenly as possible over the length of the tube NOTE This procedure should only be used as a temporary fix It is not intended as a perman...

Page 5: ...ick or punk directly at the head to cause an alarm REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST OR THE DETECTOR WILL NOT FUNCTION PROPERLY 6 1 3 Filter Replacement The filters do not substantially aff...

Page 6: ...CONTACT MANUFACTURER NOTE THE SUPERVISORY RELAY NOW PROVIDES A FORM C CONTACT FOR CUSTOMIZED APPLICATIONS FOR STANDARD APPLICATIONS ONLY THE NO CONTACT IS USED POWER INPUTS ACCEPT 24 VDC 24 VAC 50 60...

Page 7: ...s in the alarm state TROUBLE n a n a n a n a 9mA Max D100 68 00 7 I56 1147 12R 6 2 3 Sensitivity Tests 6 2 3 1 MOD400 or MOD400R Test After verification of alarm capability use the MOD400R test module...

Page 8: ...n 2 0 VAC min 10 VAC min 20 VAC min Reset time with RTS451 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec 03 to 0 3 sec Reset time by power down 0 6 sec max 0 6 sec max 0 6 sec max 0 6 sec max Power up tim...

Reviews: