D200-33-00                                                                                              1                                                                                              I56-1944-07

38M3201

DH100ACDCLPX Air Duct Smoke Detector 
with Extended Air Speed Range

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

The  Innovair  DH100ACDCLPX  model  is  a  photoelectric 
detector approved for an extended air speed range of 

100 to 

4000 feet per minute

 (0.5 m/s to 20.3 m/s) and an opera-

tional temperature range of 32°F to 131°F (0°C to 55°C).

Before Installing

Please thoroughly read the System Sensor 

Guide for Proper 

Use  of  Smoke  Detectors  in  Duct  Applications 

(A05-1004)

,

 

which  provides  detailed  information  on  detector  spacing, 
placement, zoning, wiring, and special applications. Copies 
of  this  manual  are  available  from  System  Sensor.  NFPA 
Standards 72 and 90A should also be referenced for detailed 
information. 

NOTICE:

 This manual shall be left with the owner/user 

of this equipment.

IMPORTANT:

 This detector must be tested and main-

tained regularly following NFPA 72 requirements. The 
detector should be cleaned at least once a year.

Table of Contents                                                 Page

[1] General Description...................................................... 1
[2] Limitations of Duct Smoke Detectors..............................1
[3] Exploded View of Duct Smoke Detector Components .....2
[4] Contents of the Duct Smoke Detector Kit .......................2
[5] Installation Sequence ....................................................2
[6] Duct Smoke Detector Maintenance and Test Procedures..5
[7] Detector Cleaning Procedures ........................................7
[8] Board Replacement .......................................................8
[9] Specifications................................................................8
Warranty............................................................................8

[1] General Description

An HVAC system supplies conditioned air to virtually every 
area  of  a  building.  Smoke  introduced  into  this  air  duct 
system will be distributed throughout the entire building. 
Smoke  detectors  designed  for  use  in  air  duct  systems  are 
used to sense the presence of smoke in the duct. 

Model  DH100ACDCLPX  Air  Duct  Smoke  Detector  utilizes 
photoelectric  technology  for  the  detection  of  smoke.  This 
detection method, when combined with an efficient hous-
ing design, samples air passing through the duct and allows 
detection of a developing hazardous condition. When suf-
ficient  smoke  is  sensed,  an  alarm  signal  is  initiated  and 
appropriate action can be taken to shut off fans, blowers, 
change  over  air  handling  systems,  etc.  These  actions  can 
facilitate  the  management  of  toxic  smoke  and  fire  gases 
throughout the areas served by the duct system.

The DH100ACDCLPX detector is designed to operate on 24 
VDC/VAC. Alarm and supervisory relay contacts are avail-
able  for  control  panel  interface  (alarm  initiation),  HVAC 

control, and other auxiliary functions. Auxiliary relays are 
also provided for fan shut down or signaling of up to 9 other 
detectors  in  the  loop  for  multiple  fan  shut  down.  These 
detectors are not designed for 2-wire applications.

For testing, the alarm can be enabled by a magnet activated 
test switch or by the optional remote test station. The duct 
smoke  detector  latches  into  alarm  state  when  an  alarm 
occurs. A green LED flashes to indicate power, a red LED 
signals  local  alarm  indication,  and  optional  accessories 
offer a variety of annunciation capabilities.

The DH100ACDCLPX can be reset by a momentary power 
interruption, the reset button on the front cover, the control 
panel,  or  remote  reset  accessory. 

The  DH100ACDCLPX 

incorporates  a  cover  tamper  feature  that  provides  a 
trouble  signal  after  7  minutes  if  the  cover  is  removed 
or  improperly  installed.

  Proper  installation  of  the  cover 

removes the trouble condition.

[2] Limitations Of Duct Smoke Detectors 

WARNING

The National Fire Protection Association has established that 
DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE 
FOR OPEN AREA DETECTOR PROTECTION as a means of 
providing life safety. Nor are they a substitute for early warn-
ing in a building’s regular fire detection system.
System  Sensor  supports  this  position  and  strongly  recom-
mends that the user read NFPA Standards 90A, 72, and 101. 
The DH100ACDCLPX Air Duct Smoke Detectors are listed per   
UL 268A.

WARNING

This device will not operate without electrical power.

 

Fire situations may cause an interruption of power. The 
system safeguards should be discussed with your local 
fire protection specialist.

WARNING

This device will not sense smoke unless the ventilation 
system is operating and the cover is installed.

WARNING

For this detector to function properly, it MUST be installed 
according to the instructions in this manual. Furthermore, 
the detector MUST be operated within ALL electrical and 
environmental specifications listed in this manual. Failure 
to comply with these requirements may prevent the detec-
tor from activating when smoke is present in the air duct.

Summary of Contents for Innovair DH100ACDCLPX

Page 1: ...the management of toxic smoke and fire gases throughout the areas served by the duct system The DH100ACDCLPX detector is designed to operate on 24 VDC VAC Alarm and supervisory relay contacts are ava...

Page 2: ...product For optimal performance it is recommended that the sampling tube extend at least 2 3 of the way across the duct width Table 1 Sampling Tube Lengths Approximate Length Part Number to Order Repl...

Page 3: ...ccumulated Visually inspect the filters at least quarterly inspect them more often if the dust accumulation warrants it See Section 6 for more information Replacement filters can be ordered from Syste...

Page 4: ...Home Safeguard Industries Malibu CA Phone 310 457 5813 6 1 3 Smoke Entry Test To determine if smoke is capable of entering the sens ing chamber visually identify any obstructions Plug the exhaust and...

Page 5: ...ER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC 16 6 17 7 18 8 N C C N O N O C N C ALARM AUXILIARY CONTACTS SHOWN IN STANDBY CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS SUPERVISO...

Page 6: ...cessories are used with the DH100 Series detectors The functionality of the magnetic coil has been designed into the circuitry of the new Innovair duct smoke detec tors 6 2 2 3 SSK451 Multi Signaling...

Page 7: ...tage 20 29 VDC 24 VAC 50 60 Hz Input capacitance 270 F max Reset voltage 3 0 VDC min 2 0 VAC min Reset time with RTS451 03 to 0 3 sec Reset time by power down 0 6 sec max Power up time 34 sec max Alar...

Page 8: ...D200 33 00 8 I56 1944 07 2003 System Sensor...

Page 9: ...D200 33 00 9 I56 1944 07 2003 System Sensor...

Page 10: ...D200 33 00 10 I56 1944 07 2003 System Sensor...

Page 11: ...gned to protect property not life Warning devices including horns sirens and bells may not alert people or wake up sleepers who are located on the other side of closed or partially open doors A warnin...

Page 12: ...ication devices including sirens bells horns and or strobes In residential applica tions each automatic alarm initiating device when activated shall cause the operation of an alarm notification device...

Reviews: