System Sensor Innovair DH100ACDCLPX Installation And Maintenance Instructions Manual Download Page 12

Requirements and recommendations 
for proper use of fire alarm systems 
including smoke detectors and other 
fire alarm devices:

Early fire detection is best achieved by the installation and main-
tenance of fire detection equipment in all rooms and areas of 
the house or building in accordance with the requirements and 
recommendations of the current edition of the National Fire Pro-
tection Association Standard 72, National Fire Alarm Code (NFPA 
72), the manufacturer’s recommendations, State and local codes 
and the recommendations contained in Guide for the Proper Use 
of System Smoke Detectors, which is made available at no charge 
to all installing dealers. For specific requirements, check with 
the local Authority Having Jurisdiction (ex. Fire Chief) for fire 
protection systems.
 
Requirements and Recommendations include:

•  For residential applications, smoke detectors shall be in 

 

  stalled outside of each separate sleeping area in the im 

 

  mediate vicinity of the bedrooms and on each additional  

 

  story of the family living unit, including basements and  

 

  excluding crawl spaces and unfinished attics. 
•  Smoke detectors shall be installed in sleeping rooms in new    
construction and it is recommended that they shall also be  

 

  installed in sleeping rooms in existing construction.
•  It is recommended that more than one smoke detector shall    
be installed in a hallway if it is more than 30 feet long. 
•  It is recommended that there shall never be less then two  

 

  smoke detectors per apartment or residence.

• 

It is recommended that smoke detectors be located in any    

  room where an alarm control is located, or in any room  

 

  where alarm control connections to an AC source or phone    
  lines are made.
  If detectors are not so located, a fire within the room could    
  prevent the control from reporting a fire.
•  All fire alarm systems require notification devices, including  
  sirens, bells, horns, and/or strobes. In residential applica 

 

  tions, each automatic alarm initiating device when activated  
  shall cause the operation of an alarm notification device 

 

  that shall be clearly audible in all bedrooms over ambient    
  or background noise levels (at least 15dB above noise)  

 

  with all intervening doors closed. 
•  It is recommended that a smoke detector with an integral  

 

  sounder (smoke alarm) be located in every bedroom and an  
  additional notification device be located on each level of a    
  residence.
•  To keep your fire alarm system in excellent working order,    
  ongoing maintenance is required per the manufacturer’s rec   
ommendations and UL and NFPA standards. At a minimum  

 

the requirements of Chapter 7 of NFPA 72 shall be followed.    
A maintenance agreement should be arranged through the  

 

  local manufacturer’s representative. Maintenance should be    
performed annually by authorized personnel only.
•  The most common cause of an alarm system not function 

 

  ing when a fire occurs is inadequate maintenance. As  

 

  such, the alarm system should be tested weekly to make sure  
  all sensors and transmitters are working properly. 
•  Although designed for long life, fire alarm devices including    
smoke detectors may fail at any time. It is recommended that    
residential smoke detectors shall be replaced every 10 years.
•  Any smoke detector, fire alarm system or any component of    
that system which fails shall be repaired or replaced immediately.

Typical System Installations per NFPA 72

DINING

KITCHEN

BEDROOM

BEDROOM

BEDROOM

LIVING ROOM

BEDROOM

TV ROOM

KITCHEN DINING BDRM

BDRM

LIVING ROOM

LIVING

ROOM

BEDROOM

BEDROOM

BEDROOM

KITCHEN

TO
BR

CLOSED

DOOR

BASEMENT

GARAGE

- Smoke Detectors required

- Smoke Detectors required with integral sounders recommended

- Heat Activated Detectors required

- Smoke Detectors for additional protection

- Notification Devices

As of January 2000, this document supersedes any previous liability information

enclosed with this product.

D400-84-00                                                                                             12                                                                                             I56-2443-00

©2003 System Sensor

Summary of Contents for Innovair DH100ACDCLPX

Page 1: ...the management of toxic smoke and fire gases throughout the areas served by the duct system The DH100ACDCLPX detector is designed to operate on 24 VDC VAC Alarm and supervisory relay contacts are ava...

Page 2: ...product For optimal performance it is recommended that the sampling tube extend at least 2 3 of the way across the duct width Table 1 Sampling Tube Lengths Approximate Length Part Number to Order Repl...

Page 3: ...ccumulated Visually inspect the filters at least quarterly inspect them more often if the dust accumulation warrants it See Section 6 for more information Replacement filters can be ordered from Syste...

Page 4: ...Home Safeguard Industries Malibu CA Phone 310 457 5813 6 1 3 Smoke Entry Test To determine if smoke is capable of entering the sens ing chamber visually identify any obstructions Plug the exhaust and...

Page 5: ...ER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC 16 6 17 7 18 8 N C C N O N O C N C ALARM AUXILIARY CONTACTS SHOWN IN STANDBY CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS SUPERVISO...

Page 6: ...cessories are used with the DH100 Series detectors The functionality of the magnetic coil has been designed into the circuitry of the new Innovair duct smoke detec tors 6 2 2 3 SSK451 Multi Signaling...

Page 7: ...tage 20 29 VDC 24 VAC 50 60 Hz Input capacitance 270 F max Reset voltage 3 0 VDC min 2 0 VAC min Reset time with RTS451 03 to 0 3 sec Reset time by power down 0 6 sec max Power up time 34 sec max Alar...

Page 8: ...D200 33 00 8 I56 1944 07 2003 System Sensor...

Page 9: ...D200 33 00 9 I56 1944 07 2003 System Sensor...

Page 10: ...D200 33 00 10 I56 1944 07 2003 System Sensor...

Page 11: ...gned to protect property not life Warning devices including horns sirens and bells may not alert people or wake up sleepers who are located on the other side of closed or partially open doors A warnin...

Page 12: ...ication devices including sirens bells horns and or strobes In residential applica tions each automatic alarm initiating device when activated shall cause the operation of an alarm notification device...

Reviews: