System Sensor Innovair DH100ACDCLPX Installation And Maintenance Instructions Manual Download Page 11

D200-33-00                                                                                             11                                                                                             I56-1944-07

©

2003 System Sensor

Limitations of Fire Alarm Systems

Manufacturer recommends that smoke and/or heat detectors be locat-
ed throughout a protected premise following the recommendations of 
the current edition of the National Fire Protection Association Standard 
72, National Fire Alarm Code (NFPA 72), manufacturer’s recommenda-
tions, state and local  codes, and the recommendations contained in 
Guide for the Proper Use of System Smoke Detectors, which is made 
available at no charge to all installing dealers.  A study by the Federal 
Emergency Management Agency (an agency of the United States gov-
ernment) indicated that smoke detectors may not go off or give early 
warning in as many as 35% of all fires.  While fire alarm systems are 
designed to provide warning against fire, they do not guarantee warn-
ing or protection against fire.  Any alarm system is subject to compro-
mise or failure to warn for a variety of reasons.  For example:

•  Particles  of  combustion  or  “smoke”  from  a  developing  fire  may 
    not reach the sensing chambers of the smoke detector because:
    - Barriers  such  as  closed  or  partially  closed  doors,  walls,  or
      chimneys may inhibit flow.
    - Smoke  particles  may  become  “cold”  and  stratify,  and  may 
      not reach the ceiling or upper walls where detectors are located.
    - Smoke particles may be blown away from detectors by air outlets.
    - Smoke  particles  may  be  drawn  into  air  returns  before  reach-
      ing the detector.

In general, smoke detectors on one level of a structure cannot be 
expected to sense fires developing on another level.  

•  The  amount  of  “smoke”  present  may  be  insufficient  to  alarm 
    smoke  detectors.    Smoke  detectors  are  designed  to  alarm  at 
    various levels of smoke density.  If such density levels are not 
    created  by  a  developing  fire  at  the  location  of  detectors,  the 
    detectors will not go into alarm.
•  Smoke  detectors,  even  when  working  properly,  have  sensing 
    limitations.  Detectors  that  have  photoelectronic  sensing  cham-
    bers  tend  to  detect  smoldering  fires  better  than  flaming  fires, 
    which  have  little  visible  smoke.    Detectors  that  have  ionizing-
    type  sensing  chambers  tend  to  detect  fast  flaming  fires  better 
    than  smoldering  fires.    Because  fires  develop  in  different  ways 
    and  are  often  unpredictable  in  their  growth,  neither  type  of 
    detector is necessarily best and a given type of detector may not 
    provide adequate warning of a fire.
•  Smoke detectors are subject to false alarms and nuisance alarms.  
    For example, a smoke detector located in or near a kitchen may 
    go into nuisance alarm during normal operation of kitchen appli-
    ances.  In addition, dusty or steamy environments may cause a 
    smoke detector to falsely alarm.  If the location of a smoke detec-
    tor causes an abundance of false alarms or nuisance alarms,  do 
    not disconnect the smoke detector; call a professional to analyze 
    the situation and recommend a solution.
•  Smoke detectors cannot be expected to provide adequate warn-
    ing  of  fires  caused  by  arson,  children  playing  with  matches
    (especially  within  bedrooms),  smoking  in  bed,  violent  explo-
    sions  (caused  by  escaping  gas,  improper  storage  of  flammable 
    materials, etc.).
•  Heat detectors do not sense particles of combustion and are de-
    signed  to  alarm  only  when  heat  on  their  sensors  increase  at  a 
    predetermined rate or reaches a predetermined level. Heat detec-
    tors are designed to protect property, not life.
•  Warning  devices  (including  horns,  sirens,  and  bells)  may  not 
    alert people or wake up sleepers who are located on the other 
    side  of  closed  or  partially  open  doors.  A  warning  device  that 

    activates on a different floor or level of a dwelling or structure is 
    less  likely  to  awaken  or  alert  people.  Even  persons  who  are 
    awake  may  not  notice  the  warning  if  the  alarm  is  muffled  by 
    noise from a stereo, radio, air conditioner or other appliance, or 
    by  passing  traffic.  Audible  warning  devices  may  not  alert  the 
    hearing-impaired (strobes or other devices should be provided to 
    warn these people). Any warning device may fail to alert people 
    with a disability, deep sleepers, people who have recently used 
    alcohol or drugs, or people on medication or sleeping pills.
    - Please note that:
         i)  Strobes can, under certain circumstances, cause seizures 
              in people with conditions such as epilepsy.
         ii)  Studies have shown that certain people, even when they 
              hear a fire alarm signal, do not respond or comprehend 
              the meaning of the signal.  It is the property owner’s re-
              sponsibility to conduct fire drills and other training exer-
              cises to make people aware of fire alarm signals and in-
              struct on the proper reaction to alarm signals.
         iii) In rare instances, the sounding of a warning device can 
              cause temporary or permanent hearing loss.
•  Telephone lines needed to transmit alarm signals from a premis-
    es to a central station may be out of service or temporarily out 
    of  service.  For  added  protection  against  telephone  line  failure, 
    backup radio transmission systems are recommended.
•  System  components,  though  designed  to  last  many  years,  can 
    fail at any time. As a precautionary measure, it is recommended 
    that smoke detectors be checked, maintained, and replaced per 
    manufacturer’s recommendations.
•  System components will not work without electrical power.  If 
    system batteries are not serviced or replaced regularly, they may 
    not provide battery backup when AC power fails.
•  Environments  with  high  air  velocity  or  that  are  dusty  or  dirty 
    require more frequent maintenance.
•  To keep your fire alarm system in excellent working order, on-    
    going  maintenance  is  required  per  the  manufacturer’s  recom-
    mendations  and  UL  and  NFPA  standards.  At  a  minimum  the 
    requirements of Chapter 7 of NFPA 72 shall be followed. A main-
    tenance agreement should be arranged through the local manu-
    facturer’s  representative.  Maintenance  should  be  performed 
    annually by authorized personnel only.
•  The  most  common  cause  of  an  alarm  system  not  functioning 
    when  a  fire  occurs  is  inadequate  maintenance.  As  such,  the 
    alarm system should be tested weekly to make sure all sensors 
    and transmitters are working properly.  
•  Although  designed  for  long  life,  fire  alarm  devices  including 
    smoke  detectors  may  fail  at  any  time.  It  is  recommended  that 
    smoke detectors shall be replaced every 10 years.
•  Any smoke detector, fire alarm system or any component of that 
    system which fails shall be repaired or replaced immediately.  

In general, fire alarm systems and devices will not work without 
power and will not function properly unless they are maintained 
and tested regularly.

While installing a fire alarm system may make the owner eligible 
for a lower insurance rate, an alarm system is not a substitute for 
insurance.    Property  owners  should  continue  to  act  prudently  in 
protecting the premises and the people in the premises and should 
properly  insure  life  and  property  and  buy  sufficient  amounts  of 
liability insurance to meet their needs.

Summary of Contents for Innovair DH100ACDCLPX

Page 1: ...the management of toxic smoke and fire gases throughout the areas served by the duct system The DH100ACDCLPX detector is designed to operate on 24 VDC VAC Alarm and supervisory relay contacts are ava...

Page 2: ...product For optimal performance it is recommended that the sampling tube extend at least 2 3 of the way across the duct width Table 1 Sampling Tube Lengths Approximate Length Part Number to Order Repl...

Page 3: ...ccumulated Visually inspect the filters at least quarterly inspect them more often if the dust accumulation warrants it See Section 6 for more information Replacement filters can be ordered from Syste...

Page 4: ...Home Safeguard Industries Malibu CA Phone 310 457 5813 6 1 3 Smoke Entry Test To determine if smoke is capable of entering the sens ing chamber visually identify any obstructions Plug the exhaust and...

Page 5: ...ER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC 16 6 17 7 18 8 N C C N O N O C N C ALARM AUXILIARY CONTACTS SHOWN IN STANDBY CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS SUPERVISO...

Page 6: ...cessories are used with the DH100 Series detectors The functionality of the magnetic coil has been designed into the circuitry of the new Innovair duct smoke detec tors 6 2 2 3 SSK451 Multi Signaling...

Page 7: ...tage 20 29 VDC 24 VAC 50 60 Hz Input capacitance 270 F max Reset voltage 3 0 VDC min 2 0 VAC min Reset time with RTS451 03 to 0 3 sec Reset time by power down 0 6 sec max Power up time 34 sec max Alar...

Page 8: ...D200 33 00 8 I56 1944 07 2003 System Sensor...

Page 9: ...D200 33 00 9 I56 1944 07 2003 System Sensor...

Page 10: ...D200 33 00 10 I56 1944 07 2003 System Sensor...

Page 11: ...gned to protect property not life Warning devices including horns sirens and bells may not alert people or wake up sleepers who are located on the other side of closed or partially open doors A warnin...

Page 12: ...ication devices including sirens bells horns and or strobes In residential applica tions each automatic alarm initiating device when activated shall cause the operation of an alarm notification device...

Reviews: