background image

D100-67-00

7

I56-1148-04

[6.2.2] Alarm Tests

[6.2.2.1] M02-04-00 Magnet Test

1. Place the painted surface of the magnet onto the TEST

locator on the bottom of the housing (Figure 9).

2. The red alarm LEDs on the detector should latch on, as

should any accessories (i.e. RA400Z, RTS451). Verify
system control panel alarm status, and control panel ex-
ecution of all intended auxiliary functions (i.e. fan shut-
down, damper control, etc.).

3. The detector must be reset by the system control panel,

the local reset button, or the remote accessory.

Figure 9. Testing detector alarm:

[6.2.2.2] RTS451/RTS451KEY Remote Test Station

The RTS451/RTS451KEY Remote Test Station facilitates test
of the alarm capability of the duct smoke detector as indi-
cated in the RTS451/RTS451KEY manual. The DH100 duct
smoke detector can be reset by the RTS451/RTS451KEY. If a
system control panel is used, the panel itself may also re-
quire testing.

To install the RTS451/RTS451KEY, connect the device as
shown in Figure 8; wire runs must be limited to 25 ohms or
less per interconnecting wire.

[6.2.3] Sensitivity Tests

[6.2.3.1] MOD400 or MOD400R Test

After verification of alarm capability, use the MOD400R test
module with a voltmeter to check detector sensitivity as in-
dicated in the test module’s manual. The housing cover
must be removed to perform this test.

If test module readings indicate that the detector head is
outside of the acceptable range that is printed on the label
of the detector, the detector requires cleaning per Section
[7] of this manual.

[7] Detector Cleaning Procedures

Notify the proper authorities that the smoke detector sys-
tem is undergoing maintenance, and that the system will
temporarily be out of service. Disable the zone or system
undergoing maintenance to prevent unwanted alarms and
possible dispatch of the fire department.

[7.1] Air Filters

1. Turn off power to the system.
2. Remove and inspect sampling tube filters.
3. If filters are heavily coated with dirt, replace them with

new filters. If they are not heavily coated, use a vacuum
cleaner or compressed air nozzle to remove dust, then
reinstall the filters.

[7.2] Photo Detector Boards

1. Remove the screen by gently grasping on each side and

pulling straight off

2. Lift the photo chamber in the same fashion. Vacuum the

screen and cover. Use clean, compressed air to loosen
and blow out any remaining debris. Replacement
screens (S08-39-01) are available.

3. Vacuum photo chamber, then use clean compressed air

to blow area clean.

4. Replace the chamber by pressing it onto the base. Press

the screen into place. It should fit tightly on the chamber.

[8.0] Board Replacement

[8.1] Detector Board Replacement

1.

Remove the two detector board mounting screws.

2.

Pull gently on the board to remove it.

3.

To replace the board, align the board mounting fea-
tures, holes, and the interconnect terminals. Push the
board into place.

4.

Secure board with the two mounting screws.

[8.2] Power Board replacement

1.

Disconnect wiring from the terminal block.

2.

Remove the two power board mounting screws.

3.

Pull gently on the board to remove it.

4.

To replace the board, align the board mounting fea-
tures, holes, and the interconnect terminals. Push the
board into place.

5.

Secure board with the two mounting screws.

6.

Re-connect wiring to terminal block.

A78-2325-00

Summary of Contents for Innovair DH100

Page 1: ...etc These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system DH100 detectors are designed to operate with 12 or 24 VDC UL listed compatible 2 wire control panels Alarm current must be limited to 100mA or less by the control panel Auxiliary relay contacts for control purposes are not available for use with the DH100 Control must ini ti...

Page 2: ...pling tube end plug 11 One telescoping sampling tube 12 One 8 self tapping screw for the telescoping sampling tube NOTE For ducts over 11 2 feet longer inlet sampling tubes must be ordered to complete the installation They must be the correct length for the width of the duct where they will be installed See Table 1 on page 3 to determine the inlet tube required for different duct widths 5 Installa...

Page 3: ... Than 8 Feet Wide 1 If the tube is longer than the width of the air duct drill a 3 4 inch hole in the duct opposite the hole already cut for the inlet tube Make sure the hole is 1 to 2 below the in let hole on the opposite side of the duct to allow for mois ture drainage If the tube is shorter than the width of the air duct install the end plug into the inlet tube as shown in Figure 4 Sampling tub...

Page 4: ...nside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch floor flange available at most plumbing supply stores may be used to fasten the sampling tube to the other side of the duct When using the flange connector mounting technique drill a 1 to 11 4 inch hole where the flange will be used 5 4 3 Modifications of Inlet Sampling Tubes The...

Page 5: ...Smoke Detector Maintenance And Test Procedures Test and maintain duct smoke detectors as recommended in NFPA 72 The tests contained in this manual were devised to assist main tenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the zone or system under te...

Page 6: ... INITIATION LOOP EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections 1 2 3 4 5 6 7 3 4 5 Test Test Reset Reset Test Reset RA RA V Out V In 8 7 8 V In V Out V In V In V Out DH100 RTS451 KEY 6 2 1 Alarm LED No Connection Panel Figure 8 Wiring diagram for RTS451 RTS451KEY Remote Test S...

Page 7: ...ing Procedures Notify the proper authorities that the smoke detector sys tem is undergoing maintenance and that the system will temporarily be out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 7 1 Air Filters 1 Turn off power to the system 2 Remove and inspect sampling tube filters 3 If filters are heavily coate...

Page 8: ...he obligations or limitations of this Warranty The Company s obligation of this Warranty shall be limited to the repair or re placement of any part of the air duct smoke detector which is found to be defective in materials or workmanship under normal use and service dur ing the three year period commencing with the date of manufacture After phoning System Sensor s toll free number 800 SENSOR2 736 ...

Reviews: