System Sensor Innovair DH100 Installation And Maintenance Instructions Manual Download Page 5

For signal wiring, (the wiring between interconnected de-
tectors or from detectors to auxiliary devices), it is usually
recommended that single conductor wire be no smaller
than 18 gauge. The duct smoke detector terminals accom-
modate wire sizes up to 12 gauge. The last foot of conduit
should be flexible conduit (available in electrical supply
houses), which facilitates easier installation and puts less
strain on the conduit holes in the housing. Solid conduit
connections may be used if desired.

Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel manufacturer’s specifications for the total
loop resistance allowed for the particular model control
panel being used before wiring the detector loop.

Wiring Instructions

The DH100 detectors are designed for easy wiring. The
housing provides a terminal strip with clamping plates.
Wiring connections are made by stripping about 

3

/

8

-inch of

insulation from the end of the wire, sliding the bare end un-
der the plate, and tightening the clamping plate screw.

The DH100 duct smoke detector is designed to operate with
12 or 24 VDC UL listed 2-wire compatible control panels.
Alarm current must be limited by the control panel to
100mA or less. An example of a UL listed compatible con-
trol panel is the Fire-Lite model Sensiscan 1000 using zone
card ANC-2 and compatibility identification “A”. Install per
installation instruction S1000/801. A maximum of 20 detec-
tors may be installed per zone.

[5.7] Perform Detector Check

1. Perform STANDBY AND TROUBLE TEST per Section

[6.2.1].

2. Perform MAGNET TEST per Section [6.2.2.1]. The

RTS451 test of Section [6.2.2.2] may substitute for this
requirement.

3. Perform AIR FLOW TEST per Section [6.1.1].
4. Perform SMOKE RESPONSE TEST per Section [6.1.2].
5. Perform SENSITIVITY TEST per Section [6.2.3].

[5.8] Install The Cover

Install the cover using the four screws that are captured in
the housing cover. Be certain filters are installed as speci-
fied in Section [5.5]. Make sure that the cover fits into the
base groove and that all gaskets are in their proper posi-
tions. Tighten the four screws.

[6] Duct Smoke Detector Maintenance And Test

Procedures

Test and maintain duct smoke detectors as recommended in NFPA
72. The tests contained in this manual were devised to assist main-
tenance personnel in verification of proper detector operation.

Before conducting these tests, notify the proper authorities
that the smoke detection system will be temporarily out of
service. Disable the zone or system under test to prevent
unwanted alarms.

[6.1] Smoke Entry Tests

[6.1.1] Air Flow

To verify sufficient sampling of ducted air, use a manometer
to measure the differential pressure created from air flow
across the sampling tubes. The pressure should measure no
less than 0.03 inches of water and no greater than 1.4 inches
of water. The air handler must be operating for this test.

[6.1.2] Smoke Response

To determine if smoke is capable of entering the sensing
chamber, visually identify any obstructions. Plug the ex-
haust and inlet tube holes to prevent ducted air from carry-
ing smoke away from the detector head, then blow smoke
such as cigarette, cotton wick, or punk directly at the head
to cause an alarm. REMEMBER TO REMOVE THE PLUGS
AFTER THIS TEST, OR THE DETECTOR WILL NOT FUNC-
TION PROPERLY.

[6.1.3] Filter Replacement

The filters do not substantially affect smoke performance
even when up to 90% of the filter is clogged. Quarterly vi-
sual inspection usually suffices to determine whether the
filters should be replaced because only a high percentage of
contamination affects performance. If further testing is re-
quired, compare differential pressure readings with and
without the filters installed. If the difference exceeds 10%
replace the filters. In no case should the pressure differen-
tial fall below 0.03 inches of water.

[6.2] Standby, Alarm, And Sensitivity Tests

[6.2.1] Standby And Trouble

Standby —

Look for the presence of the flashing green
LED through the transparent housing cover.
The LED should flash approximately every 10
seconds.

Trouble —

If the Green LED does not flash, then the de-
tector lacks power (check wiring, panel, or
power supply), the detector board is missing
(replace), or the unit is defective (return for
repair)

Test —

The trouble condition can be caused inten-
tionally to verify correct operation of the sys-
tem. Remove the detector board to cause a
trouble condition locally and at the system
control panel.

D100-67-00

5

I56-1148-04

Summary of Contents for Innovair DH100

Page 1: ...etc These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system DH100 detectors are designed to operate with 12 or 24 VDC UL listed compatible 2 wire control panels Alarm current must be limited to 100mA or less by the control panel Auxiliary relay contacts for control purposes are not available for use with the DH100 Control must ini ti...

Page 2: ...pling tube end plug 11 One telescoping sampling tube 12 One 8 self tapping screw for the telescoping sampling tube NOTE For ducts over 11 2 feet longer inlet sampling tubes must be ordered to complete the installation They must be the correct length for the width of the duct where they will be installed See Table 1 on page 3 to determine the inlet tube required for different duct widths 5 Installa...

Page 3: ... Than 8 Feet Wide 1 If the tube is longer than the width of the air duct drill a 3 4 inch hole in the duct opposite the hole already cut for the inlet tube Make sure the hole is 1 to 2 below the in let hole on the opposite side of the duct to allow for mois ture drainage If the tube is shorter than the width of the air duct install the end plug into the inlet tube as shown in Figure 4 Sampling tub...

Page 4: ...nside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch floor flange available at most plumbing supply stores may be used to fasten the sampling tube to the other side of the duct When using the flange connector mounting technique drill a 1 to 11 4 inch hole where the flange will be used 5 4 3 Modifications of Inlet Sampling Tubes The...

Page 5: ...Smoke Detector Maintenance And Test Procedures Test and maintain duct smoke detectors as recommended in NFPA 72 The tests contained in this manual were devised to assist main tenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the zone or system under te...

Page 6: ... INITIATION LOOP EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections 1 2 3 4 5 6 7 3 4 5 Test Test Reset Reset Test Reset RA RA V Out V In 8 7 8 V In V Out V In V In V Out DH100 RTS451 KEY 6 2 1 Alarm LED No Connection Panel Figure 8 Wiring diagram for RTS451 RTS451KEY Remote Test S...

Page 7: ...ing Procedures Notify the proper authorities that the smoke detector sys tem is undergoing maintenance and that the system will temporarily be out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 7 1 Air Filters 1 Turn off power to the system 2 Remove and inspect sampling tube filters 3 If filters are heavily coate...

Page 8: ...he obligations or limitations of this Warranty The Company s obligation of this Warranty shall be limited to the repair or re placement of any part of the air duct smoke detector which is found to be defective in materials or workmanship under normal use and service dur ing the three year period commencing with the date of manufacture After phoning System Sensor s toll free number 800 SENSOR2 736 ...

Reviews: