background image

D200-102-00

5

I56-3888-203

Table 2: Wiring Terminal Designations

(Note - Terminals marked CH2 will only be available on 2 channel 

models)

Sensor

The sensor address is set on rotary decade 

switches on the back of the smoke sensing 

devices. The smoke sensors are located under 

the sensor cover inside the unit (see Figure 9). 

The 

Smoke Sensors

 section of 

Maintenance

 

- later in the manual - shows how to remove the 

sensors. As supplied, the default for channel 1 

is Address 1; in 2 channel units (or when two 

sensors are fitted) the second device is set to 

Address 2.

Module

The module address is set by means of rotary 

decade address switches located behind the 

door of the unit. Use a screwdriver to rotate the 

wheels to the desired address. The selected 

address refers to channel 1; on 2 channel 

units the device assigns the next (+1) module 

address to channel 2 automatically. Hence, 

address 159 is not valid for channel 1. (Note: 

for control panels that use only 99 addresses, 

99 is invalid for channel 1.)

Note:

 The module address will only respond to 

a panel poll when in 

Normal

 mode.

POWERING UP
Using Default Settings

1.   Connect a suitable 24VDC supply (complying 

with European Standard EN 54-4) to pins 1 

and 2 on terminal block T1 (See Table 2)

2.  Check the voltage at the connector. Make 

sure it is within the required voltage range.

3.   If the voltage is within the specified range, 

connect the power connector to the unit.

4.   Close and secure the housing door; verify the fan starts up and 

air flows out of the exhaust port. The unit takes 1-3 minutes to 

initialise and stabilise in normal mode.

Configuring Other Options

To change any of the default options, it will be necessary to 

connect the detector to a PC/laptop with the PipeIQLT software 

installed; see 

USB connection

 section later in this guide for 

more information on this (and the FAAST LT Advanced Setup and 

Control Guide).

EXTERNAL RESET

The  default  setting  for  the  configurable  external  input  is  Device 

Reset (terminal block T8). A short circuit connection between these 

terminals will cause the FAAST LT unit to perform a reset.

Table 3: Relays

No.

Function

Ext Power In + 

 

Primary PSU  

T1

Ext Power In - 

 

Primary PSU  

Aux Power In + 

 

Not used in default 

Aux Power In  - 

 

Not used in default 

NC Alarm Relay  

CH1  

T2

C Alarm Relay  

CH1  

NO Alarm Relay  

CH1  

NC Alarm Relay  

CH2  

T3

C Alarm Relay  

CH2  

10 

NO Alarm Relay  

CH2  

11 

NC Fault Relay  

CH1  

T4

12 

C Fault Relay  

CH1  

13 

NO Fault Relay  

CH1  

14 

NC Fault Relay (AUX) 

CH2  

T5

15 

C Fault Relay (AUX) 

CH2  

16 

NO Fault Relay (AUX) 

CH2  

17 

Sounder Output 1 - 

47 k-ohm EOL Resistor 

T6

18 

Sounder Output 1 + 

19 

Sounder Output 2 - 

47 k-ohm EOL Resistor 

T7

20 

Sounder Output 2 +  

21 

Configurable Input + 

(Reset) Default is active = short circuit 

(unsupervised)

T8

22 

Configurable Input - 

(Reset)

23 

Not Used  

T9

24 

Loop out - 

25 

Loop switched out +   

 

To use isolator 

26 

Loop in - 

T10

27 

Loop in +  

28 

Loop not switched out +    

Internally connected to 27 

RELAY 

ACTION: 

NOTES

ALARM 1 or 2 

Controlled by panel when it determines 

alarm condition has been met.  

Set ON and OFF by panel; not latched 

FAULT 1 or 2 

When FAULT CONDITION on Ch1 or Ch2 

or a common FAULT occurs. Fault is also 

signalled when in Service Mode and when 

the device is unpowered. 

Fault state is not latched. 

SOUNDER 1 or 2 

Set ON when a channel is in ALARM. 

Sounder 1 corresponds to Ch1 and 

Sounder 2 corresponds to Ch2 

Default condition = set on in ALARM. 

SETTING THE ADDRESSES

Figure 10: Address Switches

X 10

X 1

Each aspiration channel uses loop communications to report its 

status information to the CIE (Fire Panel). As a factory default, 

the unit will report smoke alarm and sensor information at an 

associated sensor address and general alerts and faults on a 

different module address.

Summary of Contents for FL2011EI

Page 1: ...ator Characteristics Maximum rated switching current under short circuit Is max 0 9A 29V Maximum leakage current IL max with the switch open isolated state 15mA Maximum series impedance with the switc...

Page 2: ...xed in place This allows the installer to choose the language required for the installation from the Front Panel Labelling Pack Figure 2 shows where the labels need to be placed 1 2 3 4 5 6 7 8 9 10 F...

Page 3: ...Each unit has 2 pipe holes per channel so if installing a 1 channel unit holes 3 and 4 do not function Use Table 1 to locate the holes required for the installation Figure 8 Pipe Holes Table 1 Pipe H...

Page 4: ...EL 2 FILTER POWER AND ALARM CONNECTIONS CHANNEL 1 FILTER USB PORT SENSOR COVER POSITION FOR TEST MAGNET POSITION FOR TEST MAGNET Exhaust Pipe SAMPLING AREA SAMPLING AREA 5 6 EARTH BAR MOUNT EARTH BAR...

Page 5: ...B connection section later in this guide for more information on this and the FAAST LT Advanced Setup and Control Guide EXTERNAL RESET The default setting for the configurable external input is Device...

Page 6: ...Advanced Protocol Flow Level Test Reset and Disable Buttons 11c FL2022EI 2 Channel Detector ALARM PREALARM MODULE LEVEL SMOKE FAULT FAULT POWER IN P U T S E N S O R AS PIR AT OR E L B A S I D M E T S...

Page 7: ...when initialising POWER FAULT ON Yellow Low power alert high power fault Check the power supply voltage CHANNEL FLOW INDICATORS 1 2 ON Green The LED indicates the air flow for a channel Centre normal...

Page 8: ...operation will cause the unit to enter Service Mode The FILTER LEDs will blink the unit will switch off power to the fans and stops communicating with the fire panel the smoke sensors continue to comm...

Page 9: ...generateconfigurationparameters for correct set up and operation and facilitate commissioning and monitoring of the performance of FAAST LT Aspiration devices PipeIQLT provides a graphical interface o...

Page 10: ...puter in the normal way for your operating system Launching To launch the PipeIQLT application double click the PipeIQLT icon on the desktop Or click Start bottom left corner of the Windows screen and...

Reviews: