background image

[5.1] Verify Duct Air Flow Direction And Velocity

Model DH400ACDCP detectors are designed to be used in 
air  handling  systems  having  air  velocities  of  500  to  4000 
feet per minute. Be sure to check engineering specifications 
to ensure that the air velocity in the duct falls within these 
parameters. If necessary, use a velocity meter to check the 
air velocity in the duct.

[5.2] Drill The Mounting Holes

Remove  the  paper  backing  from  the  mounting  template 
supplied.  Affix  the  template  to  the  duct  at  the  desired 
mounting  location.  Make  sure  the  template  lies  flat  and 
smooth on the duct. Center punch holes A and B. Drill the 
holes  as  indicated  on  the  template.  Slide  the  two  speed 
nuts over the two small holes (hole A) next to the sampling 
tube bushing holes (hole B) previously drilled in the duct. 
(See 

Figure 3

.)

[5.3] Secure The Detector Housing To The Duct

Remove the duct housing cover. Slide the foam gaskets over 
the  tube  bushings  as  shown  in 

Figure  2

.  Make  sure  the 

two small holes in the gaskets line up with the two base 
mounting holes. Put one 

5

/

16

˝ O-ring over each of the two 

#10 sheet metal screws. Use the two sheet metal screws to 
screw the detector housing to the duct. CAUTION: Do not 
overtighten the screws.

Figure 2. Installation of foam gaskets over sampling 
tube bushings:

 

SCREW HOLES FOR ATTACHING

DETECTOR HOUSING TO DUCT

FOAM GASKETS

EXHAUST TUBE

(EXTENSION BUSHING)

DUCT DETECTOR

HOUSING

O-RINGS

MOUNTING

SCREWS

INLET SAMPLING

TUBE BUSHING

H0238-00

Figure 3. Speed nut mounting location:

HOLE B

HOLE A

DUCT

WALL

SPEED

NUT

H0116-00

[5.4] Install The Inlet

The inlet tube (shown in 

Figure 4

) is identified by a series 

of air inlet holes on the tube. This tube must be purchased 
separately.  Order  the  correct  length,  as  specified  in  Table 
1, for width of the duct where it will be installed. The ex-
haust tube is molded into the base of the duct housing, and 
the A2440-00 Exhaust Tube Extension is available as an ac-
cessory in those cases where the molded exhaust port does 
not extend at least 2˝ into the duct.
The inlet tube is always installed in the centermost hous-
ing  bushing,  with  air  inlet  holes  facing  into  the  air  flow. 
To assist proper installation, the tube’s mounting flange is 
marked with arrows. Make sure the inlet tube is mounted 
so that the arrows point into the air flow. 

Figure 5

 shows 

the various combinations of tube mounting configurations 
with respect to air flow. 
Mounting the detector housing in a vertical orientation is 
acceptable,  provided  that  the  air  flows  directly  into  the 
sampling tube holes as indicated in 

Figure 4

.

Table 1. Inlet tubes required for different duct widths:

 

Outside Duct Width 

Inlet Tube Required

 

1 to 2 ft. 

ST-1.5

 

2 to 4 ft. 

ST-3

 

4 to 8 ft. 

ST-5

 

8 to 12 ft. 

ST-10

[5.4.1] Installation For Ducts Less Than 8 Feet Wide

1.   If  the  tube  is  longer  than  the  width  of  the  air  duct, 

drill a 

3

/

4

˝ hole in the duct directly opposite the hole 

already  cut  for  the  inlet  tube.  If  the  tube  is  shorter 
than the width of the air duct, install the end plug into 
the inlet tube as shown in 

Figure 4

. Sampling tubes 

over 3 ft. long must be supported at the end opposite 
the duct detector.

2.   Slide the tube into the centermost housing bushing. Po-

sition the tube so that the arrows point into the air flow. 

3.   Secure the tube flange to the housing bushing with two 

#6 self-tapping screws.

4.   For tubes longer than the width of the air duct, the tube 

should  extend  out  of  the  opposite  side  of  the  duct.  If 
there are more than 2 holes in the section of the tube 
extending out of the duct, select a different length using 
Table 1. Otherwise, trim the end of the tube protruding 
through the duct so that 1˝ to 2˝ of the tube extend out-
side the duct. Plug this end with the end plug and tape 
closed any holes in the protruding section of the tube. 
Be sure to seal the duct when the tube protrudes.

WARNING

In no case should more than 2 air inlet holes be cut off the 
tube. There must be a minimum of 10 holes in the tube ex-
posed to the air stream.

D400-13-00 

I56-0555-010R

Summary of Contents for DH400ACDCP

Page 1: ...Fig 11 Detector Head Removal 9 Fig 12 RTS451 RTS451KEY Test Coil Installation 10 Fig 13 Photo Head Exploded View 10 1 General Description An HVAC system supplies conditioned air to virtually ev ery area of a building Smoke introduced into this air duct system will be distributed to the entire building Smoke detectors designed for use in air duct systems are used to sense the presence of smoke in t...

Page 2: ...ical power Frequently fire situations may cause an interruption of power The system safeguards should be discussed with your local fire protection specialist WARNING This device does not sense smoke unless the ventilation system is operating CAUTION For this detector to function properly it MUST be installed according to the instructions in this manual Furthermore the detector MUST be protected fr...

Page 3: ...sion is available as an ac cessory in those cases where the molded exhaust port does not extend at least 2 into the duct The inlet tube is always installed in the centermost hous ing bushing with air inlet holes facing into the air flow To assist proper installation the tube s mounting flange is marked with arrows Make sure the inlet tube is mounted so that the arrows point into the air flow Figur...

Page 4: ...ING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DETECTOR HOUSING INLET TUBE EXHAUST TUBE AIR FLOW DIRECTION EXHAUST TUBE INLET TUBE INLET TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION EXHAUST TUBE INLET TUBE DETECTOR HOUSING A B C D HORIZONTAL MOUNTING OF HOUSING VERTICAL MOUNTING OF HOUSING Figure 5 Tube mounting configurations with varying air flow direction H0109 00...

Page 5: ...nnection to UL listed control panels or for stand alone service per NFPA 90A Refer to the wiring diagrams of Figures 7 8 and 9 to select the appropriate circuit for your application 5 6 Install The Filters To install the sampling tube filters simply push the filter adapter into the exhaust tube and push the filter onto the adapter tube on the left as shown in Figure 6 Install the other filter over...

Page 6: ...N OPEN IN STANDBY CONTACTS CLOSE IN ALARM 8 9 ALARM INITIATION CONTACTS CONTACTS SHOWN OPEN IN STANDBY CONTACTS CLOSE IN ALARM ALARM INITIATION LOOP UL LISTED CONTROL PANEL FIRST DETECTOR IN THE LOOP DH400ACDCP LAST DETECTOR IN THE LOOP DH400ACDCP EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPP...

Page 7: ...ICES REFER TO MANUFACTURER S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER TROUBLE CONTACT RATING 0 3A 32 VAC DC POWER INPUTS ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR ALARM AUXILIARY CONTACT RATINGS 10A 30 VDC 10A 250 VAC 500mA MINIMUM 24 VDC NOT INTENDED FOR CONNECTION TO CONTROL PANELS ALARM INITIATI...

Page 8: ...12mA MAX 0mA 0mA 0mA ALARM 30mA MAX 15mA MAX 10mA MAX 10mA MAX ANY COMBINATION OF ACCESSORIES MAY BE USED SUCH THAT THE GIVEN CURRENT LOADS TOTAL RESET TEST NOTE WHEN INITIATING AN ALARM THE RTS451 RTS451KEY REQUIRES 95mA MAXIMUM IN PRE ALARM AND 103mA MAXIMUM IN ALARM NOMINAL STANDBY CURRENT IS 0mA ALARM CURRENT IS 10mA MAXIMUM WHEN TEST MAGNET IS REMOVED 100mA OR LESS IN THE STANDBY STATE 150mA ...

Page 9: ...wise Figure 10 Testing detector alarm Figure 11 Detector head removal TEST LOCATOR TEST MAGNET PAINTED SIDE TOWARD HOUSING DUCT HOUSING DETECTOR HEAD RESET LOCATOR TWIST COUNTERCLOCKWISE TO REMOVE DUCT HOUSING TWIST CLOCKWISE TO INSTALL DETECTOR HEAD H0530 00 H0531 00 4 Carefully reinsert the detector head into the duct hous ing and wait 50 seconds for power up Do not hold the swirl chamber to twi...

Page 10: ...the arrow on top with the field test port on the detector Press the screen into place It should fit tightly on the chamber 5 Replace the detector cover and rotate it clockwise to lock it in place 7 4 Reinstallation 1 Reinstall the detector in its housing 2 Restore system power 3 Perform Detector Check Section 5 7 4 Notify the proper authorities testing has been completed and the smoke detector sys...

Page 11: ...set switch with alarm LED PA400 Piezo Sounder APA451 Annunciator with piezo alarm power LEDs F36 05 00 Replacement Air Filter two per package M02 04 00 Replacement Test Magnet P48 21 00 Replacement End Plug for inlet sampling tube R59 18 00 Replacement Calibrated Test Card For photo units only RS24 Replacement Screen Photo A2650 01 Replacement Installation Kit mounting hardware Sampling Inlet Tube...

Page 12: ...s from date of manufacture System Sensor makes no other express warranty for the enclosed product No agent representative dealer or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty The Company s obliga tion of this Warranty shall be limited to the replacement of any part of the product which is found to be defective in materials or work...

Page 13: ...D400 13 00 13 I56 0555 010R NOTES ...

Page 14: ...NOTES D400 13 00 14 I56 0555 010R ...

Page 15: ...NOTES D400 13 00 15 I56 0555 010R ...

Page 16: ...________ ____________________________ ________ _ ___________ _ _______ _ ______________ ____________________________ ________ _ ___________ _ _______ _ ______________ ____________________________ ________ _ ___________ _ _______ _ ______________ ____________________________ ________ _ ___________ _ _______ _ ______________ ____________________________ ________ _ ___________ _ _______ _ ___________...

Reviews: