background image

D200-39-00                                                                                              3                                                                                          I56-1977-004R

SCREW HOLES FOR
ATTACHING HOUSING
TO DUCT WORK.

Figure 3. Installation of foam gaskets over 
sampling tube bushings:

Figure 5. Tube mounting configurations with varying 
air flow direction:

Table 1. Sampling tubes recommended for different
duct widths:

         Outside Duct Width             Sampling Tube Recommended*

        1 to 2 ft. (0.3 to 0.6 m)                               ST-1.5
        2 to 4 ft. (0.6 to 1.2 m)                                 ST-3
        4 to 8 ft. (1.2 to 2.4 m)                                 ST-5
       8 to 12 ft. (2.4 to 3.7 m)                                ST-10
*Must extend a minimum of 

2

3

 the duct width

SAMPLING

TUBE

END CAP

AIR HOLES

ARROW

MUST FACE

INTO AIR FLOW

AIR FLOW DIRECTION

FLANGE

Figure 4. Air duct detector sampling tube:

H0108-02

AIR FLOW

DIRECTION

DETECTOR

HOUSING

DOTS INDICATE POSITION OF

SAMPLING TUBE HOLES

AIR FLOW

DIRECTION

DETECTOR

HOUSING

SAMPLING

TUBE

EXHAUST

TUBE

AIR FLOW

DIRECTION

EXHAUST

TUBE

SAMPLING

TUBE

SAMPLING

TUBE

EXHAUST

TUBE

DETECTOR

HOUSING

AIR FLOW

DIRECTION

DETECTOR

HOUSING

A.

B.

C.

D.

HORIZONTAL MOUNTING OF HOUSING

VERTICAL MOUNTING OF HOUSING

NOTE: Only metal sampling tubes can be installed in 

orientations C and D.

[4.2] Installation For Ducts More Than 8 Feet (2.4m) Wide

NOTE:

     To install sampling tubes in ducts more than 8 feet (2.4m) wide, 

work must be performed inside the air duct. Sampling of air in 
ducts  wider  than  8  feet  (2.4m)  is  accomplished  by  using  the 
ST-10 sampling tube. If the tube is shorter than the width of the 
air duct, install the end cap into the sampling tube as shown 
in Figure 4 and support the end opposite the duct smoke detec-
tor.

Install the sampling tube as follows:

1.  Drill  a  3⁄4-inch  (19mm)  hole  in  the  duct  directly  opposite  the  hole 

already drilled for the sampling tube. Make sure the hole is 1

 to 2

 

(25 to 50mm) below the inlet hole on the opposite side of the duct to 
allow for moisture drainage.

2.  Slide the sampling tube with the flange into the housing bushing that 

meets the air flow first. Position the tube so that the arrow points into 
the air flow. Secure the tube flange to the housing bushing with two 
#6 self-tapping screws.

3.  From inside the duct, couple the other sections of the sampling tube 

to the section already installed using the 

1

2

-inch conduit fittings sup-

plied. Make sure that the holes on both of the sampling tubes are lined 
up and facing into the air flow.

4.  Trim the end of the tube protruding through the duct so that 1

 to 2

 

(25 to 50mm) of the tube extend outside the duct. Plug this end with 
the end cap and tape closed any holes in the protruding section of the 
tube. Be sure to seal the duct where the tube protrudes.

NOTE:

     An alternate method to using the ST-10 is to use two ST-5 sam-

pling tubes. Remove the flange from one of the tubes and install 
as described above. After the installation, use electrical tape to 
close off some of the sampling holes so that there are a total of 
10 to 12 holes spaced as evenly as possible across the width of 
the duct.

2.  Slide the tube into the housing bushing that meets the air flow first. 

Position the tube so that the arrow points into the air flow, as shown 
in Figure 4. 

3.  Secure the tube flange to the housing bushing with two #6 self-tapping 

screws.

4.  For tubes longer than the width of the air duct, the tube should extend 

out of the opposite side of the duct. If there are more than 2 holes in 
the  section  of  the  tube  extending  out  of  the  duct,  select  a  different 
length using Table 1. Otherwise, trim the end of the tube protruding 
through  the  duct  so  that  1

  to  2

  (25  to  50mm)  of  the  tube  extend 

outside the duct. Plug this end with the end cap and tape closed any 
holes  in  the  protruding  section  of  the  tube.  Be  sure  to  seal  the  duct 
where the tube protrudes.

NOTE: 

The sampling tube end cap is critical to the proper operation of the 

duct smoke detectors. The end cap is needed to create the proper air flow 
to the sensor of the duct smoke detector.

Summary of Contents for DH200RPL

Page 1: ... filters 4 One test magnet 5 Drilling template 6 Two foam gaskets 7 Four 6 self tapping mounting screws for the sampling tube and optional exhaust tube extension 8 One sampling tube end cap 9 One plastic sampling tube 10 One 8 self tapping screw for plastic sampling tube NOTE A detector sensor board DOES NOT need to be ordered separately INSTALLATION AND MAINTENANCE INSTRUCTIONS The DH200RPL air d...

Page 2: ...cause an interruption of power The system safeguards should be discussed with your local fire protection specialist WARNING This device will not sense smoke unless the ventilation system is operat ing WARNING In order to function properly this detector must be installed according to the instructions Do not exceed the electrical or ambient specifications or the detector will not function properly T...

Page 3: ...ange into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow Secure the tube flange to the housing bushing with two 6 self tapping screws 3 From inside the duct couple the other sections of the sampling tube to the section already installed using the 1 2 inch conduit fittings sup plied Make sure that the holes on both of the sampling tube...

Page 4: ... 004R NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch 75mm floor flange available at most plumb ing supply stores may be used to fasten the sampling tube to the other side of the duct When using the flange connector mounting technique drill a 1 inch to 11 4 inch 25 to 32mm hole where the flange will be used ...

Page 5: ...ERLY 9 1 4 Air Flow Test using Dwyer Series 607 Differential Pressure Transmitter Verify the air speed of the duct using an anemometer Air speed must be at least 100 FPM Wire the Dwyer transmitter as shown in Figure 8 Connect the leads of the meter to either side of the 1000Ω resistor Allow unit to warm up for 15 seconds With both HIGH and LOW pressure ports open to ambient air measure and record ...

Page 6: ...ion Trouble If the detector LEDs do not flash then the de tector lacks power check wiring panel pro gramming or power sup ply the detector board is missing replace or the unit is defec tive return for repair Additionally if the cover is removed for more than 20 minutes the LEDs of the detector will not flash Test The trouble condition can be caused intentionally to veri fy correct operation of the...

Page 7: ... 2 Lift the photo chamber in the same fashion Vacuum the screen and cover Use clean compressed air to loosen and blow out any remaining debris Replacement screens p n S08 39 01 are available 3 Vacuum photo chamber then use clean compressed air to blow area clean 4 Replace the chamber by pressing it onto the base Press the screen into place It should fit tightly on the chamber 10 Board Replacement ...

Page 8: ... encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help System Sensor warrants its enclosed air...

Reviews: