background image

D200-39-00                                                                                              7                                                                                          I56-1977-004R

[9.2.2.2] RTS451/RTS451KEY Remote Station Test

The RTS451/RTS451KEY Remote Test Station facilitates test of the alarm 
capability  of  the  duct  smoke  detector.    These  accessories  provide  the 
stimulus  to  initiate  an  alarm  condition  at  the  detector.    The  detector  is 
self-restoring when the accessory test stimulus is removed.  Verify that the 
system control panel has reset; panel may need to be reset. 

  

[9.2.3] Sensitivity Tests

Notify the proper authorities that the smoke detector system is undergo-
ing maintenance, and that the system will temporarily be out of service. 
Disable the device or system undergoing maintenance to prevent unwant-
ed alarms and possible dispatch of the fire department.

[9.3] Maintenance of Duct Smoke Detectors [9.3.1] Air Filters

1.  Turn off power to the system.
2.  Remove and inspect sampling tube filters.
3.  If  filters  are  heavily  coated  with  dirt,  replace  them  with  new  filters 

(p/n F36-09-11). If they are not heavily coated, use a vacuum cleaner 
or compressed air nozzle to remove dust, then reinstall the filters. 

[9.3.2] Photo Detector Boards 

1.  Remove the screen by gently grasping on each side and pulling straight 

off

2.  Lift  the  photo  chamber  in  the  same  fashion.  Vacuum  the  screen  and 

cover. Use clean, compressed air to loosen and blow out any remaining 
debris. Replacement screens (p/n S08-39-01) are available.

3.  Vacuum  photo  chamber,  then  use  clean  compressed  air  to  blow  area 

clean.

4.  Replace the chamber by pressing it onto the base. Press the screen into 

place. It should fit tightly on the chamber. 

[10] Board Replacement
[10.1] Sensor Board Replacement

1.  Remove the two sensor board mounting screws.
2.  Pull gently on the board to remove it. 
3.  To replace the board, align the board mounting features, holes, and the 

interconnect terminals. Push the board into place.

4.  Secure board with the two mounting screws.

[10.2] Power Board Replacement

1.  Disconnect wiring from the terminal block.
2.  Remove the two power board mounting screws.
3.  Pull gently on the board to remove it. 
4.  To replace the board, align the board mounting features, holes, and the 

interconnect terminals. Push the board into place.

5.  Secure board with the two mounting screws.
6.  Re-connect wiring to terminal block.

[11] Model DH200RPL Air Duct Smoke Detector Specifications 

Operating Temperature Range  32° to 131°F (0° to 55°C)
Storage Temperature Range 

-22º to 158ºF (-30º to 70ºC)

Humidity Range 

 

10% to 93% (non-condensing)

Air Velocity 

 

100 to 4000 ft/min (0.5 to 20.32 m/sec.)

Dimensions 

 

14

3

8

 

 L x 5

1

2

 W x 2

3

4

 D (37 cm L x 

 

 

 

14 cm W x 7 cm D)

 

 

Summary of Contents for DH200RPL

Page 1: ... filters 4 One test magnet 5 Drilling template 6 Two foam gaskets 7 Four 6 self tapping mounting screws for the sampling tube and optional exhaust tube extension 8 One sampling tube end cap 9 One plastic sampling tube 10 One 8 self tapping screw for plastic sampling tube NOTE A detector sensor board DOES NOT need to be ordered separately INSTALLATION AND MAINTENANCE INSTRUCTIONS The DH200RPL air d...

Page 2: ...cause an interruption of power The system safeguards should be discussed with your local fire protection specialist WARNING This device will not sense smoke unless the ventilation system is operat ing WARNING In order to function properly this detector must be installed according to the instructions Do not exceed the electrical or ambient specifications or the detector will not function properly T...

Page 3: ...ange into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow Secure the tube flange to the housing bushing with two 6 self tapping screws 3 From inside the duct couple the other sections of the sampling tube to the section already installed using the 1 2 inch conduit fittings sup plied Make sure that the holes on both of the sampling tube...

Page 4: ... 004R NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch 75mm floor flange available at most plumb ing supply stores may be used to fasten the sampling tube to the other side of the duct When using the flange connector mounting technique drill a 1 inch to 11 4 inch 25 to 32mm hole where the flange will be used ...

Page 5: ...ERLY 9 1 4 Air Flow Test using Dwyer Series 607 Differential Pressure Transmitter Verify the air speed of the duct using an anemometer Air speed must be at least 100 FPM Wire the Dwyer transmitter as shown in Figure 8 Connect the leads of the meter to either side of the 1000Ω resistor Allow unit to warm up for 15 seconds With both HIGH and LOW pressure ports open to ambient air measure and record ...

Page 6: ...ion Trouble If the detector LEDs do not flash then the de tector lacks power check wiring panel pro gramming or power sup ply the detector board is missing replace or the unit is defec tive return for repair Additionally if the cover is removed for more than 20 minutes the LEDs of the detector will not flash Test The trouble condition can be caused intentionally to veri fy correct operation of the...

Page 7: ... 2 Lift the photo chamber in the same fashion Vacuum the screen and cover Use clean compressed air to loosen and blow out any remaining debris Replacement screens p n S08 39 01 are available 3 Vacuum photo chamber then use clean compressed air to blow area clean 4 Replace the chamber by pressing it onto the base Press the screen into place It should fit tightly on the chamber 10 Board Replacement ...

Page 8: ... encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help System Sensor warrants its enclosed air...

Reviews: