background image

D200-39-00                                                                                              5                                                                                          I56-1977-004R

[9.1] Smoke Entry Tests
[9.1.1] Air Flow

This product is designed to operate over an extended air speed range of 100 
to 4000 FPM. To verify sufficient sampling of ducted air, turn the air han-
dler on and use a manometer to measure the differential pressure between 
the two sampling tubes. The differential pressure should measure at least 
0.0015 inches of water and no more than 1.2 inches of water. Because most 
commercially available manometers cannot accurately measure very low 
pressure differentials, applications with less than 500 FPM of duct air speed 
may require one of the following: 1) the use of a current-sourcing pressure 
transmitter (Dwyer Series 607) per Section 9.1.4 or; 2) the use of aerosol 
smoke per section 9.1.2.

[

9.1.2] Air Flow Test using Aerosol Smoke

This test is intended for low-flow systems (100-500 FPM). If the air speed 
is greater than 500 FPM, use a conventional manometer to measure differ-
ential pressure between the sampling tubes, as described in 9.1.1.

Drill  a 

1

4

  hole  3  feet  upstream  from  the  duct  smoke  detector.  With  the 

air handler on, measure the air velocity with an anemometer. Air speed 
must be at least 100 FPM.

 

Spray aerosol smoke* into the duct through the 

1

4

 hole for five seconds. Wait two minutes for the duct smoke detector 

to  alarm.  If  the  duct  smoke  detector  alarms,  air  is  flowing  through  the 
detector. Remove the duct smoke detector cover and blow out the residual 
aerosol smoke from the chamber and reset the duct smoke detector. Use 
duct tape to seal the aerosol smoke entry hole.

*Aerosol  smoke  can  be  purchased  from  Home  Safeguard  Industries, 
Malibu, CA. Phone: 310/457-5813.

[9.1.3] Smoke Entry Test

To determine if smoke is capable of entering the sensing chamber, visually 
identify  any  obstructions.  Plug  the  exhaust  and  sampling  tube  holes  to 
prevent ducted air from carrying smoke away from the detector head, then 
blow smoke such as cigarette, cotton wick, or punk directly at the head to 
cause an alarm. REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST, 
OR THE DETECTOR WILL NOT FUNCTION PROPERLY.

[9.1.4] Air Flow Test using Dwyer Series 607 Differential Pressure 
Transmitter

Verify the air speed of the duct using an anemometer. Air speed must be at 
least 100 FPM. Wire the Dwyer transmitter as shown in Figure 8. Connect 
the leads of the meter to either side of the 1000

Ω

 resistor. Allow unit to 

warm up for 15 seconds. With both HIGH and LOW pressure ports open 
to  ambient  air,  measure  and  record  the  voltage  drop  across  the  1000

Ω

 

resistor (measurement 1), 4.00 volts is typical. Using flexible tubing and 
rubber stoppers, connect the HIGH side of the transmitter to the sampling 
tube of the duct smoke detector housing, and the LOW side of the trans-
mitter to the exhaust tube of the duct smoke detector housing. Measure 
and record the voltage drop across the 1000

Ω

 resistor (measurement 2). 

Subtract the voltage recorded in measurement 1 from the voltage recorded 
in  measurement  2.  If  the  difference  is  greater  than  0.15  volts,  there  is 
enough air flow through the duct smoke detector for proper operation.

Figure 8. Procedure for verifying air flow:

DIFFERENTIAL

PRESSURE

TRANSMITTER

MODEL #607-01

HIGH

LOW

TO SAMPLING TUBE

TO EXHAUST TUBE

VOLT METER

FLUKE MODEL 87

OR EQUIVALENT

1000 OHM 5% 1 WATT RESISTOR

9 VOLT

BATTERY

9 VOLT

BATTERY

9 VOLT

BATTERY

15 TO 36VDC

SUPPLY

H0163-01

[9.1.5] Filter Replacement

The filters do not substantially affect smoke performance even when up 
to  90%  of  the  filter  is  clogged.  Quarterly  visual  inspection  usually  suf-
fices to determine whether the filters should be replaced because only a 
high  percentage  of  contamination  affects  performance.  If  further  testing 
is required, compare differential pressure readings with and without the 
filters installed. If the difference exceeds 10% replace the filters. In no case 
should the pressure differential fall below 0.0015 inches of water.

Figure 9. Wiring Diagram for DH200RPL Duct Smoke Detector using a UL listed control panel:

NOTE:

  Jumper J1 shunt must be installed for 2-W applications. J1 shunt must be removed for power PCB supervision.

+

COM (+)

COM (-)

COM (+)

COM (-)

COMMUNICATION

LINE

UL LISTED CONTROL

PANEL

1ST DETECTOR

IN LOOP

2ND DETECTOR

IN LOOP

1 2

1 2

J1 JUMPER

J1 JUMPER

NOTE: J1 JUMPER MUST 
BE INSTALLED FOR 2W 
APPLICATIONS. THE 
J1 JUMPER MUST BE 
REMOVED FOR POWER 
BOARD SUPERVISION.

Summary of Contents for DH200RPL

Page 1: ... filters 4 One test magnet 5 Drilling template 6 Two foam gaskets 7 Four 6 self tapping mounting screws for the sampling tube and optional exhaust tube extension 8 One sampling tube end cap 9 One plastic sampling tube 10 One 8 self tapping screw for plastic sampling tube NOTE A detector sensor board DOES NOT need to be ordered separately INSTALLATION AND MAINTENANCE INSTRUCTIONS The DH200RPL air d...

Page 2: ...cause an interruption of power The system safeguards should be discussed with your local fire protection specialist WARNING This device will not sense smoke unless the ventilation system is operat ing WARNING In order to function properly this detector must be installed according to the instructions Do not exceed the electrical or ambient specifications or the detector will not function properly T...

Page 3: ...ange into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow Secure the tube flange to the housing bushing with two 6 self tapping screws 3 From inside the duct couple the other sections of the sampling tube to the section already installed using the 1 2 inch conduit fittings sup plied Make sure that the holes on both of the sampling tube...

Page 4: ... 004R NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch 75mm floor flange available at most plumb ing supply stores may be used to fasten the sampling tube to the other side of the duct When using the flange connector mounting technique drill a 1 inch to 11 4 inch 25 to 32mm hole where the flange will be used ...

Page 5: ...ERLY 9 1 4 Air Flow Test using Dwyer Series 607 Differential Pressure Transmitter Verify the air speed of the duct using an anemometer Air speed must be at least 100 FPM Wire the Dwyer transmitter as shown in Figure 8 Connect the leads of the meter to either side of the 1000Ω resistor Allow unit to warm up for 15 seconds With both HIGH and LOW pressure ports open to ambient air measure and record ...

Page 6: ...ion Trouble If the detector LEDs do not flash then the de tector lacks power check wiring panel pro gramming or power sup ply the detector board is missing replace or the unit is defec tive return for repair Additionally if the cover is removed for more than 20 minutes the LEDs of the detector will not flash Test The trouble condition can be caused intentionally to veri fy correct operation of the...

Page 7: ... 2 Lift the photo chamber in the same fashion Vacuum the screen and cover Use clean compressed air to loosen and blow out any remaining debris Replacement screens p n S08 39 01 are available 3 Vacuum photo chamber then use clean compressed air to blow area clean 4 Replace the chamber by pressing it onto the base Press the screen into place It should fit tightly on the chamber 10 Board Replacement ...

Page 8: ... encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help System Sensor warrants its enclosed air...

Reviews: