background image

[6.2.3] Sensitivity Tests
[6.2.3.1] MOD400 or MOD400R Test 

After verification of alarm capability, use the MOD400R test mod-
ule with a voltmeter to check detector sensitivity as indicated in 
the test module’s manual. The housing cover must be removed to 
perform this test.
If test module readings indicate that the detector head is outside of 
the acceptable range that is printed on the label of the detector, the 
detector chamber requires cleaning per Section [7] of this manual.

[7] Detector Cleaning Procedures

Notify  the  proper  authorities  that  the  smoke  detector  system  is 
undergoing maintenance, and that the system will temporarily be 
out  of  service.  Disable  the  zone  or  system  undergoing  mainte-
nance to prevent unwanted alarms and possible dispatch of the 
fire department.

[7.1] Air Filters

1.  Turn off power to the system.
2.  Remove and inspect sampling tube filters.
3.   If  filters  are  heavily  coated  with  dirt,  replace  them  with  new 

filters. If they are not heavily coated, use a vacuum cleaner or 
compressed air nozzle to remove dust, then reinstall the filters. 

ALARM SIGNAL (+)

AUX POWER (–)

15

20

(+)

(–)

DUCT DETECTOR

DH100ACDCLP

PA400 (OPTIONAL)

AUDIBLE ALERT

ALARM SIGNAL (+)

AUX POWER (–)

15

20

(+)

(–)

DUCT DETECTOR

DH100ACDCLP

RA400Z (OPTIONAL)

REMOTE (LED)

ANNUNCIATOR

RED

D200-14-00 

I56-0084-009R

[7.2] Photo Detector Board 

1.   Remove the screen by gently grasping on each side and pull-

ing straight off.

2.   Lift  the  photo  chamber  in  the  same  fashion.  Vacuum  the 

screen  and  cover.  Use  clean,  compressed  air  to  loosen  and 
blow out any remaining debris. Replacement screens (S08-39-
01) are available.

3.   Vacuum  photo  chamber,  then  use  clean  compressed  air  to 

blow area clean.

4.   Replace the chamber by pressing it onto the base. Press the 

screen into place. It should fit tightly on the chamber. 

[8.0] Board Replacement
[8.1] Detector Board Replacement (part no. A5190)

1.  Remove the two detector board mounting screws.
2.  Pull gently on the board to remove it. 
3.   To replace the board, align the board mounting features, holes, 

and the interconnect terminals. Push the board into place.

4.  Secure board with the two mounting screws.

[8.2] Power Board replacement (part no. A5064)

1.  Disconnect wiring from the terminal block.
2.  Remove the two power board mounting screws.
3.  Pull gently on the board to remove it. 
4.   To replace the board, align the board mounting features, holes, 

and the interconnect terminals. Push the board into place.

5.  Secure board with the two mounting screws.
6.  Re-connect wiring to terminal block.

Figure 12. Wiring diagrams for optional accessories:

15 

ALARM SIGNAL

 3
14
 2 

RESET

11 

TEST

20 

AUX. POWER (–)

19 

AUX. POWER (+)

SSK451

FIELD INSTALLED

JUMPER FOR

TEMPORAL PATTERN

SUPERVISORY

CONTACT

NO

FIELD INSTALLED

JUMPER

DH100ACDCLP

COMMON      3

TEMPORAL SELECT      2

ALARM SIGNAL      1

SUPERVISORY SIGNAL      4

RESET      7

TEST      8

POWER (–)      6
POWER (+)      5

Figure 13. Wiring diagram for DH100ACDCLP to SSK451: 

H0162-00

Figure 14. Testing detector alarm:

H0161-01

H0160-00

NOTE:  Wiring  diagram  shown  is  for  DH100ACDCLP  4-wire  duct  smoke 
detector system equipped without a control panel.

Summary of Contents for DH100ACDCLP

Page 1: ...ry functions Auxiliary relays are also provided for fan shut down or signaling of up to 9 other detectors in the loop for multiple fan shut down These detectors are not designed for 2 wire applications For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm occurs A green LED flashe...

Page 2: ... in Figure 3 Use the two 11 4 long sheet metal screws to screw the detector housing to the duct CAUTION Do not overtighten the screws Figure 3 Installation of foam gaskets over sampling tube bushings SCREW HOLES FOR ATTACHING HOUSING TO DUCT WORK H0107 00 5 4 Sampling Tube Installation for Ducts Greater Than 11 2 Feet Wide The sampling tube is identified by a series of air inlet holes on the tube ...

Page 3: ...ng holes so that there are a total of 10 to 12 holes spaced as evenly as possible across the width of the duct NOTE Air currents inside the duct may cause excessive vibra tion especially when the longer sampling tubes are used In these cases a 3 floor flange available at most plumbing supply stores may be used to fasten the sampling tube to the other side of the duct When using the flange connecto...

Page 4: ...an 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12 gauge Smoke detectors and alarm system control panels have specifi cations for allowable loop resistance Consult the control panel manufacturer s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loop Wiring Instructions The DH100ACDCLP detec...

Page 5: ...ntial fall below 0 0015 inches of water 6 2 Standby Alarm and Sensitivity Tests The cover must be removed to perform these tests The use of a remote accessory for visible indication of power and alarm is recommended 6 2 1 Standby And Trouble Standby Look for the presence of the flashing green LED The LED should flash approximately ev ery 10 seconds Trouble If the detector LED does not flash then t...

Page 6: ...LE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC 16 6 17 7 18 8 N C C N O N O C N C ALARM AUXILIARY CONTACTS SHOWN IN STANDBY CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS SUPERVISORY TROUBLE CONTACTS TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT OPEN CONTACTS SIGNAL TROUBLE CONDITION TO P...

Page 7: ...er in the same fashion Vacuum the screen and cover Use clean compressed air to loosen and blow out any remaining debris Replacement screens S08 39 01 are available 3 Vacuum photo chamber then use clean compressed air to blow area clean 4 Replace the chamber by pressing it onto the base Press the screen into place It should fit tightly on the chamber 8 0 Board Replacement 8 1 Detector Board Replace...

Page 8: ...AC 50 60 Hz 120 VAC 50 60 Hz 220 240 VAC 50 60 Hz CURRENT REQUIREMENTS USING NO ACCESSORIES Max standby current 15 mA 35 mA RMS 25 mA RMS 15 mA RMS Max alarm current 70 mA 125 mA RMS 35 mA RMS 25 mA RMS CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC 10A 250 VAC 1 4 HP 240 VAC 1 8 HP 120 VAC Trouble contacts SPDT 2 0A 30 VDC resistive 2...

Reviews: