background image

15

19

14

3

20

1

3

2

Alarm Signal

Aux. Power +

Sup. N. O.

Sup. COM

Aux. Power –

NOTE:  Wiring diagram shown is for DH100ACDCLP 4-wire duct
 

smoke detector system equipped without a control panel.

Alarm
(Red LED)

Power
(Green LED)
Common

APA451

DH100ACDCLP

NOTE:  A trouble condition is indicated when the green LED
 

is not illuminated.

D200-14-00 

I56-0084-009R

Figure 9. Wiring diagram for DH100ACDCLP  
to APA451:

H0158-01

Figure 8. System wiring diagram for 4-wire duct smoke detectors:

Figure 10. Wiring diagram for DH100ACDCLP to 
RTS451/RTS451KEY:

Important Interconnect Notes

•   When using the interconnect feature, all 

interconnected  units  must  be  powered 
with the same, independent supply.

•   Polarity must be maintained throughout 

the  interconnect  wiring.  Connect  termi-
nal 12 on unit 1 to terminal 12 on unit 2 
and so on. Similarly, connect terminal 1 
on unit 1 to terminal 1 on unit 2 and so 
on.

•    Up to 10 units may be interconnected.

Figure 11. Multiple fan shutdown (interconnect):

1

6

12

16

A

B

C

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

1

6

12

16

A

B

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

DETECTOR 1

C

DETECTOR 2

1

6

12

16

A

B

FAN

CONTROL

SYSTEM

CONTROL

POWER OR

THERMOSTAT

C

DETECTOR 10

OUT TO

10 DETECTORS

MAXIMUM

24V

9

10

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC.

16

6

17

7

18

8

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN

STANDBY. CONTACTS TRANSFER DURING

ALARM AS INDICATED BY THE ARROWS.

SUPERVISORY TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.

CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS

REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN 

CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.

24V

9

10

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC.

16

6

17

7

18

8

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN

STANDBY. CONTACTS TRANSFER DURING

ALARM AS INDICATED BY THE ARROWS.

SUPERVISORY  TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.

CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS

REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN 

CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.

14

3

3

14

4

5

ALARM

INITIATION

CONTACTS

CONTACTS SHOWN

OPEN IN STANDBY.

CONTACTS CLOSE

IN ALARM.

4

5

ALARM

INITIATION

CONTACTS

CONTACTS SHOWN

OPEN IN STANDBY.

CONTACTS CLOSE

IN ALARM.

ALARM

INITIATION

LOOP

UL LISTED 4-WIRE

CONTROL PANEL

FIRST DETECTOR IN THE LOOP

DH100ACDCLP

LAST DETECTOR IN THE LOOP

DH100ACDCLP

EOL RESISTOR

SPECIFIED BY

PANEL MANUFACTURER

CONNECT POWER SOURCE

TO APPROPRIATE TERMINALS

OF EACH DETECTOR. SEE

SPECIFICATIONS FOR

ADDITIONAL POWER SUPPLY

INFORMATION.

FOR WIRING OF AUXILIARY

DEVICES, REFER TO

MANUFACTURER'S

INSTALLATION INSTRUCTIONS

OR CONTACT MANUFACTURER.

NOTE:

 THE SUPERVISORY RELAY NOW

PROVIDES A "FORM C" CONTACT FOR

CUSTOMIZED APPLICATIONS.

FOR STANDARD APPLICATIONS, ONLY

THE "NO" CONTACT IS USED

POWER INPUTS ACCEPT

24 VDC, 24 VAC  50-60 HZ,

CONNECT POWER SOURCE

TO APPROPRIATE TERMINALS

OF EACH DETECTOR.      

AUX. CONTACT RATINGS

10A @ 30 VDC RESISTIVE

100mA MINIMUM @ 5 VDC

1/4 HP @ 240 VAC

1/8 HP @ 120 VAC

NOT INTENDED FOR

CONNECTION TO CONTROL

PANELS.

TROUBLE CONTACT RATING

2.0 A @ 30 VDC resistive

2.0 A @ 125 VAC resistive

+

120

VAC

220/240

VAC

A

B

C

220/240

VAC

A

B

C

120

VAC

15

19

14

3

20

2

11

2

6

1

Alarm Signal

Aux. Power +

Sup. N. O.

Sup. COM

Aux. Power –

Reset

Test

(Red LED) Alarm

(Green LED)
Power

DH100ACDCLP

RTS451/RTS451KEY

5

4

3

*

For RTS451KEY
only without a
control panel.

*

CAUTION

Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.

H0155-01

H0156-00

H0157-00

Summary of Contents for DH100ACDCLP

Page 1: ...ry functions Auxiliary relays are also provided for fan shut down or signaling of up to 9 other detectors in the loop for multiple fan shut down These detectors are not designed for 2 wire applications For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm occurs A green LED flashe...

Page 2: ... in Figure 3 Use the two 11 4 long sheet metal screws to screw the detector housing to the duct CAUTION Do not overtighten the screws Figure 3 Installation of foam gaskets over sampling tube bushings SCREW HOLES FOR ATTACHING HOUSING TO DUCT WORK H0107 00 5 4 Sampling Tube Installation for Ducts Greater Than 11 2 Feet Wide The sampling tube is identified by a series of air inlet holes on the tube ...

Page 3: ...ng holes so that there are a total of 10 to 12 holes spaced as evenly as possible across the width of the duct NOTE Air currents inside the duct may cause excessive vibra tion especially when the longer sampling tubes are used In these cases a 3 floor flange available at most plumbing supply stores may be used to fasten the sampling tube to the other side of the duct When using the flange connecto...

Page 4: ...an 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12 gauge Smoke detectors and alarm system control panels have specifi cations for allowable loop resistance Consult the control panel manufacturer s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loop Wiring Instructions The DH100ACDCLP detec...

Page 5: ...ntial fall below 0 0015 inches of water 6 2 Standby Alarm and Sensitivity Tests The cover must be removed to perform these tests The use of a remote accessory for visible indication of power and alarm is recommended 6 2 1 Standby And Trouble Standby Look for the presence of the flashing green LED The LED should flash approximately ev ery 10 seconds Trouble If the detector LED does not flash then t...

Page 6: ...LE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC 16 6 17 7 18 8 N C C N O N O C N C ALARM AUXILIARY CONTACTS SHOWN IN STANDBY CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS SUPERVISORY TROUBLE CONTACTS TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT OPEN CONTACTS SIGNAL TROUBLE CONDITION TO P...

Page 7: ...er in the same fashion Vacuum the screen and cover Use clean compressed air to loosen and blow out any remaining debris Replacement screens S08 39 01 are available 3 Vacuum photo chamber then use clean compressed air to blow area clean 4 Replace the chamber by pressing it onto the base Press the screen into place It should fit tightly on the chamber 8 0 Board Replacement 8 1 Detector Board Replace...

Page 8: ...AC 50 60 Hz 120 VAC 50 60 Hz 220 240 VAC 50 60 Hz CURRENT REQUIREMENTS USING NO ACCESSORIES Max standby current 15 mA 35 mA RMS 25 mA RMS 15 mA RMS Max alarm current 70 mA 125 mA RMS 35 mA RMS 25 mA RMS CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC 10A 250 VAC 1 4 HP 240 VAC 1 8 HP 120 VAC Trouble contacts SPDT 2 0A 30 VDC resistive 2...

Reviews: