background image

[5.4.3] Modifications of Sampling Tubes

There  may  be  applications  where  duct  widths  are  not  what  is 
specified  for  the  installation.  In  such  cases,  it  is  permissible  to 
modify a sampling tube that is longer than necessary to span the 
duct width.
Use a 0.193-inch  diameter (#10) drill and add the appropriate num-
ber of holes so that the total number of holes exposed to the air flow 
in the duct is 10 to 12. Space the additional holes as evenly as pos-
sible over the length of the tube.

NOTE:

 This procedure should only be used as a temporary fix. It 

is not intended as a permanent substitute for ordering the correct 
length tubes.

[5.4.4] Alternate Method of Sampling Tube Installation

The detector arrangement can also incorporate the remote mount-
ing of the sampling tube and/or exhaust tube. In this case both 
the detector, sampling tube and exhaust tube (if included) should 
be rigidly mounted to withstand the pressure and resonant vibra-
tions  caused  by  the  air  velocity.    The  location  of  the  detector’s 
sampling tube should be such that there is uniform airflow in the 
cross section area.  
An air tight connection shall be made between the sampling tube, 
exhaust tube and their corresponding ports on the detector hous-
ing.  Upon selection of location in the system, pressure differential 
across  the  sampling  and  exhaust  ports  in  the  detector  housing 
shall  be  verified  to  be  within  the  allowable  range  of  the  detec-
tor.    This  is  accomplished  by  measuring  the  pressure  difference 
between the inlet and outlet ports on the detector housing using a 
manometer as described in Section 6 of this manual.

[5.5] Install The Filters 

To install the sampling tube filters, simply push the filters into the 
sampling and exhaust tube holes, as shown in Figure 6. If a metal 
sampling tube is used, install the filters over the tube ends.

Figure 6. Sampling tube filter installation:

H0159-00

CAUTION

Filters require periodic cleaning or replacement, depending on the 
amount of dust and dirt accumulated. Visually inspect the filters at 
least quarterly; inspect them more often if the dust accumulation 
warrants  it.  See  Section  [6]  for  more  information.  Replacement 
filters  can  be  ordered  from  System  Sensor,  3825  Ohio  Ave.,  St. 
Charles, IL 60174. (Exhaust tube/intake tube filter P/N F36-09-11)

[5.6] Field Wiring
Installation Guidelines

All wiring must be installed in compliance with the National Elec-
trical  Code  and  the  local  codes  having  jurisdiction.  Proper  wire 
gauges  should  be  used.  The  conductors  used  to  connect  smoke 
detectors to control panels and accessory devices should be color-
coded to prevent wiring mistakes. Improper connections can pre-
vent a system from responding properly in the event of a fire.

For  signal  wiring,  (the  wiring  between  interconnected  detectors 
or from detectors to auxiliary devices), it is usually recommended 
that single conductor wire be no smaller than 18 gauge. The duct 
smoke detector terminals accommodate wire sizes up to 12 gauge.
Smoke  detectors  and  alarm  system  control  panels  have  specifi-
cations  for  allowable  loop  resistance.  Consult  the  control  panel 
manufacturer’s specifications for the total loop resistance allowed 
for  the  particular  model  control  panel  being  used  before  wiring 
the detector loop. 

Wiring Instructions

The  DH100ACDCLP  detectors  are  designed  for  easy  wiring.  The 
housing provides a terminal strip with clamping plates.  Wiring 
connections are made by stripping about 3/8” of insulation from 
the  end  of  the  wire,  sliding  the  bare  end  under  the  plate,  and 
tightening the clamping plate screw. 

[5.7] Perform Detector Check 

1.   Perform STANDBY AND TROUBLE TEST per Section [6.2.1].
2.   Perform  MAGNET  TEST  per  Section  [6.2.2.1].  The  RTS451 

test of Section [6.2.2.2] may substitute for this requirement. 

3.  Perform AIR FLOW TEST per Section [6.1.1].
4.  Perform SMOKE RESPONSE TEST per Section [6.1.2].
5.  Perform SENSITIVITY TEST per Section [6.2.3].

[5.8] Install The Cover

Install the cover using the six screws that are captured in the hous-
ing  cover.  Be  certain  filters  are  installed  as  specified  in  Section 
[5.5]. Make sure that the cover fits into the base groove and that 
all gaskets are in their proper positions. Tighten the six screws.

[6] Duct Smoke Detector Maintenance and 
Test Procedures

Test and maintain duct smoke detectors as recommended in NFPA 
72. The tests contained in this manual were devised to assist main-
tenance personnel in verification of proper detector operation. 
Before  conducting  these  tests,  notify  the  proper  authorities  that 
the smoke detection system will be temporarily out of service. Dis-
able the zone or system under test to prevent unwanted alarms.

[6.1] Smoke Entry Tests
[6.1.1] Air Flow

The DH100ACDCLP is designed to operate over an extended air speed 
range of 100 to 4000 FPM. To verify sufficient sampling of ducted air, 
turn the air handler on and use a manometer to measure the dif-
ferential pressure between the two sampling tubes. The differential 
pressure should measure at least 0.0015 inches of water and no more 
than 1.2 inches of water. Because most commercially available ma-
nometers cannot accurately measure very low pressure differentials, 
applications with less than 500 FPM of duct air speed may require 
one of the following: 1) the use of a current-sourcing pressure trans-
mitter (Dwyer Series 607) per Section 6.1.4 or; 2) the use of aerosol 
smoke per section 6.1.2.

[6.1.2] Air Flow Test using Aerosol Smoke

This test is intended for low-flow systems (100-500 FPM). If the 
air speed is greater than 500 FPM, use a conventional manometer 
to measure differential pressure between the sampling tubes, as 
described in 6.1.1.
Drill a 

1

4

˝ hole 3 feet upstream from the duct smoke detector. With 

the air handler on, measure the air velocity with an anemometer. 
Air speed must be at least 100 FPM. Spray aerosol smoke* into 
the duct through the 

1

4

˝ hole for five seconds. Wait two minutes 

for  the  duct  smoke  detector  to  alarm.  If  the  duct  smoke  detec-

D200-14-00 

I56-0084-009R

Summary of Contents for DH100ACDCLP

Page 1: ...ry functions Auxiliary relays are also provided for fan shut down or signaling of up to 9 other detectors in the loop for multiple fan shut down These detectors are not designed for 2 wire applications For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm occurs A green LED flashe...

Page 2: ... in Figure 3 Use the two 11 4 long sheet metal screws to screw the detector housing to the duct CAUTION Do not overtighten the screws Figure 3 Installation of foam gaskets over sampling tube bushings SCREW HOLES FOR ATTACHING HOUSING TO DUCT WORK H0107 00 5 4 Sampling Tube Installation for Ducts Greater Than 11 2 Feet Wide The sampling tube is identified by a series of air inlet holes on the tube ...

Page 3: ...ng holes so that there are a total of 10 to 12 holes spaced as evenly as possible across the width of the duct NOTE Air currents inside the duct may cause excessive vibra tion especially when the longer sampling tubes are used In these cases a 3 floor flange available at most plumbing supply stores may be used to fasten the sampling tube to the other side of the duct When using the flange connecto...

Page 4: ...an 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12 gauge Smoke detectors and alarm system control panels have specifi cations for allowable loop resistance Consult the control panel manufacturer s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loop Wiring Instructions The DH100ACDCLP detec...

Page 5: ...ntial fall below 0 0015 inches of water 6 2 Standby Alarm and Sensitivity Tests The cover must be removed to perform these tests The use of a remote accessory for visible indication of power and alarm is recommended 6 2 1 Standby And Trouble Standby Look for the presence of the flashing green LED The LED should flash approximately ev ery 10 seconds Trouble If the detector LED does not flash then t...

Page 6: ...LE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC 16 6 17 7 18 8 N C C N O N O C N C ALARM AUXILIARY CONTACTS SHOWN IN STANDBY CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS SUPERVISORY TROUBLE CONTACTS TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT OPEN CONTACTS SIGNAL TROUBLE CONDITION TO P...

Page 7: ...er in the same fashion Vacuum the screen and cover Use clean compressed air to loosen and blow out any remaining debris Replacement screens S08 39 01 are available 3 Vacuum photo chamber then use clean compressed air to blow area clean 4 Replace the chamber by pressing it onto the base Press the screen into place It should fit tightly on the chamber 8 0 Board Replacement 8 1 Detector Board Replace...

Page 8: ...AC 50 60 Hz 120 VAC 50 60 Hz 220 240 VAC 50 60 Hz CURRENT REQUIREMENTS USING NO ACCESSORIES Max standby current 15 mA 35 mA RMS 25 mA RMS 15 mA RMS Max alarm current 70 mA 125 mA RMS 35 mA RMS 25 mA RMS CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC 10A 250 VAC 1 4 HP 240 VAC 1 8 HP 120 VAC Trouble contacts SPDT 2 0A 30 VDC resistive 2...

Reviews: