background image

Installation Guidelines

NOTE:

  Refer to the releasing device manufacturer’s 

instructions for connection instructions.

Allowable loop resistance is an important specification for 
control panels as well as for smoke detectors and their 
bases. The alarm system cannot be expected to operate 
correctly if system components have incompatible allow-
able loop resistances. Therefore, before beginning installa-
tion, refer to the control panel manufacturer’s loop resis-
tance specification to ensure that it is listed as compatible 
with the System Sensor base and smoke detector being 
installed.

All wiring must be installed in compliance with the 
National Electrical Code, all applicable local codes and any 
special requirements of the authority having jurisdiction, 
using the proper wire size. The conductors used to connect 
smoke detectors to control panels and accessory devices 
should be color-coded to reduce the likelihood of wiring 
errors. Improper connections can prevent a system from 
responding properly in the event of a fire.

Wiring

For signal wiring (the wiring between interconnected 
detectors), it is recommended that the wire be no smaller 
than AWG 18. However, the screws and clamping plate in 
the base can accommodate wire sizes up to AWG 12. The 
use of twisted pair wiring for the power (+ and -) loop is 
recommended to minimize the effects of electrical interfer-
ence.

NOTE: 

 To ensure that electrical connections are super-

vised, DO NOT loop wires under terminals 2, 3, 
and 5 –break the wire at each terminal.

To make electrical connections, strip approximately 3/8” (1 
cm) insulation from the end of each wire. Slide the wires 
under the clamp plate and tighten the terminal screw.

If the base is being installed in a zoned system, check the 
zone wiring before installing the smoke detector head. The 
built-in shorting spring makes it convenient to do this. 
After the detector base is wired and attached to the electri-
cal box, position the shorting spring against terminal 3. Use 
the slot in the retaining clip to hold the spring against the 
terminal, as shown in Figure 1. This shorts the negative-in 
and negative-out leads so that loop wiring can be tested 
for continuity.

The shorting spring in the base will disengage automati-
cally when the detector head is removed from the base. 
DO NOT remove the shorting spring since it reengages as 
the detector head is turned into the base, completing the 
circuit.

SNAP ON 

DECORATIVE 

RING

SCREWS 

(NOT SUPPLIED)

DETECTOR 

BASE

BOX

(NOT SUPPLIED)

SHORTING 

SPRING

C0503-00

Figure 1. Mounting base to box:

Tamper-resistance Feature

NOTE:

  DO NOT use the tamper-resistance feature if the 

System Sensor XR2 Removal Tool will be used to 
remove detectors from the base.

This detector base can be made tamper resistant so the 
detector cannot be removed without the use of a tool. To 
make the base tamper-resistant, break off the smaller tab at 
the scribed line on the tamper-resistance tab, on the detec-
tor mounting bracket (see Figure 3A), before installing the 
detector.

To remove the detector from the base after it has been made 
tamper resistant, remove the decorative ring by rotating it 
in either direction and pulling it away from the base. Then, 
insert a small screwdriver into the notch, as indicated in 
figure 3B, and press the plastic lever toward the mounting 
surface before rotating the detector counterclockwise for 
removal.

  

I56-597-04R 

 

 06-10

firealarmresources.com

Summary of Contents for B112LP

Page 1: ...ative Humidity Noncondensing Electrical Ratings includes base and detector System Voltage 24 VDC Maximum Ripple Voltage 4 Volts peak to peak Start Up Capacitance 0 02µF Maximum Standby Ratings 20 VDC Minimum 29 VDC Maximum 120 µA Maximum Alarm Ratings 17 mA Minimum 36 mA Maximum Reset Voltage 1 4 VDC Minimum Reset Time 0 3 Seconds Maximum The optional RA400Z operates within specified detector alar...

Page 2: ...ach wire Slide the wires under the clamp plate and tighten the terminal screw If the base is being installed in a zoned system check the zone wiring before installing the smoke detector head The built in shorting spring makes it convenient to do this After the detector base is wired and attached to the electri cal box position the shorting spring against terminal 3 Use the slot in the retaining cl...

Page 3: ...N LOOP EOL RESISTOR EOL RELAY NOTE Schematic Shown for Reference 1 2 3 4 5 8 9 10 11 12 13 14 UL LISTED 4 WIRE CONTROL PANEL REMOTE ANNUNCIATOR RELEASING DEVICE OPTIONAL 1 2 3 4 5 8 9 10 11 12 13 14 REMOTE ANNUNCIATOR POWER LOOP POWER LOOP ALARM CIRCUIT RELEASING DEVICE OPTIONAL EOL RELAY RESISTOR EOL Figure 2 Typical wiring diagram Figure 3A Activating the tamper resistance feature PLASTIC LEVER ...

Page 4: ...rization number send defective units postage prepaid to Honeywell 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use modifica tions or alterations occurring after the date of manufacture In no ...

Reviews: